Plan Review Details - Permit 14050111
Plan Review Stops For Permit 14050111
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-19 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2014-08-19 Time 15:17 Sent To  
Notes
2014-08-19 16:30:12BUILDING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUES. AUGUST 19/ 2014
  
 ACTION:BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) 0211-A2.01/ BASEMENT LEVEL: REVISION IS REQUIRED.
 THE FIRST COMMENT ASKED WHY THER WAS STORAGE BINS IN
 THE CORRIDOR, THE RESPONSE INDICATES THESE ARE SOILED
 LAUNDRY BINS.
 SOILED LAUNDRY IS CONSIDERED AN INCIDENTIAL ACCESSORY
 OCCUPANY IN ITSELF, AND IS TO BE SEPARATE WITHIN A
 ROOM, NOT IN A EXIT ACCESS COORIDOR,
 SEE THE 2010 FBC-B TABLE 508.2.5. IT STATES THAT
 LAUNDRY ROOMS ARE TO BE SEPARATED BY 1 HR ROOM OR
 PROVIDE FIRE SPRINKLERS. PLEASE REVIEW 508.2.5.2
 NONFIRE-RESISTANCE-RATED SEPARATION AND PROTECTION.
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL ACCESSORY OCCUPANCIES SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE. THE WALLS
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE CEILING THAT IS
 A COMPONENT OF A FIRE-RESISTANCE-RATED FLOOR ASSEMBLY
 OR ROOF ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE. DOORS SHALL BE
 SELF- OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3. DOORS SHALL NOT HAVE
 AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN
 EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH
 NFPA 80. WALLS SURROUNDING THE INCIDENTAL ACCESSORY
 OCCUPANCY SHALL NOT HAVE AIR TRANSFER OPENINGS UNLESS
 PROVIDED WITH SMOKE DAMPERS IN ACCORDANCE WITH SECTION
 711.7.
  
 3) COMPLIED ,LULA LIFT.
  
 4A) NEW COMMENT/ SEMI NEW, NEW LOCATION, THE EXECUTIVE
 LOUNGE HAS BEEN MOVED TO ROOM # 207 THE COMMENTS STILL
 EXIST. THE EXECUTIVE LOUNGE HAS A OCCUPANT LOAD OF 73
 THIS IS AN ASSEMBLY OCCUPANCY PLEASE PROVIDE A
 FURNATURE LATOUT. SHEET A3.00 DOES NOT INCLUDE THIS
 ROOM IN THE PLUMBING FIXTURE COUNT. DEPENDING ON THE
 USAGE THIS MAY BE CONSIDERED EIHER AN A2 OR A3, IF
 CONSIDERED MORE AS A LOUNGE A-2 THE WATER CLOSET RATIO
 WILL BE 1/40 REQUIRING ADDITIONAL FIXTURES.
  
 4B) ROOM 207 THE EXECUTIVE LOUNGE, THERE IS A SMALL
 ROOM THAT NO INFORMATION HAS BEEN PROVIDED, IS THIS FOR
 STORAGE, BAR OR KITCHEN TO BE USED IN CONJUNCTION WITH
 THE LOUNGE? FBC-B 302.1. NOTE FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES. 4. EGRESS SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES.
  
 5) SHEET A4.20 SECTION THRU BUILDING A12.10 : 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION
 SHOW COMPLIANCE NOTES ON PLANS QUATING CODE DOES NOT
 MEAN COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM
 COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE WITH: 2010 FBC-B 1407.2 EXTERIOR WALL
 FINISH.
 MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF
 BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL
 WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL
 COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
  
 6) DEFFERED SUBMITTAL; A12.10 DETAILS 1 & 8 BOTH
 INDICATE THE PERIMETER SUN SCREEN , DETAIL 3 A12.09
 ALSO A CLOSE UP OF THE PERIMETER SUNSCREEN INDICATE THE
 USE OF STEEL EMBEDS W/ NELSON BOLTS PER THE
 MANUFACTURERS REQUIREMENTS. PLEASE PROVIDE ENGINEERING
 FOR THIS SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL
 MEET THE WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR
 THIS ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1
 DETERMINATION OF WIND LOADS. WIND LOADS ON EVERY
 BUILDING OR STRUCTURE SHALL BE DETERMINED IN ACCORDANCE
 WITH CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS
 OF THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
 L
  
 7) THE FPL VAULT REQUIRES 3 HR WALLS 2008 NEC THE DOORS
 ALSO REQUIRE A 3 HR RATING PER 2008 NEC 450.43(A) &
 2010 FBC-B TABLE 715.4.
  
  
 8) PLEASE CLARIFY: MICHAEL STELLINO & I HAVE SPOKEN ON
 THIS SUBJECT. WHAT APPEARS TO BE A LINEN CHUTE DOOR IS
 SUPPOSE TO BE A RECESSED FIRE EXTINGUISHER CABINET.
 PLEASE CLARIFY. THE RESPONSE INDICATES THAT THE LINEN
 CHUTE DOOR IS IDENTIFIED AS T26. PLEASE REVIEW THE DOOR
 SCHEDULE ON A14.01, T26 IS FOR THE ICE ROOM NEXT TO THE
 LAUNDRY CHUTE, THAT DOES NOT HAVE ANY DOOR, NOR IS THE
 ARK OF A DOOR INDICATED ON THE PLANS.
  
 SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE GRID
 LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID LINE
 WHICH IS LOCATED IN THE MAIDS ROOM.FLOORS 10-12 SEE
 SHEET A2.11 THE LAUBDRY CHUTE IS OFFSET TO THE
 NORTHEAST OR TO THE EAST OF GRID LINE Y.2 . THE PLANS
 SHOW THE ACCESS TO THE ACCESS CHUTE DOOR LOCATED WITH
 THE CORRADOR. PLEASE CONFORM WITH:
  
 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS
 ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3.
  
 8B) . SHEET A12.16 SHOWS A NEW DETAIL WITH A FIRE RISER
 WITHIN THE 2 HR FIRE RATED CHASE BUT THE SPRINKLER HEAD
 DOES NOT PENETRATE INTO THE THE LINEN CHUTE NOR DOES
 THERE SHOW HOW THE SPRINKLER HEAD HAS ACCESSIBILITY FOR
 MAINTENANCE.
 SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION THE
 REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS IN
 THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY PROVIDE
 A DEAIL ON FP0.01 INDICATING SERVICE CHUTE DETAIL.
 708.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE
 REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING THIS MAY BE A ISSUE WHERE
 THE RECESSED FIRE EXTINGUISHER BOXES ARE LOCATED ON THE
 10-12TH FLOORS IN FRONT OF THE LAUNDRY CHUTE.
  
 9A) DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT THE
 PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT ISSUANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9B) DEFERRED SUBMITTAL UNDER 107.3.4.2. 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-06 Cont ID  
Sent By jwitmer Date 2014-08-06 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2014-08-01 Time 07:05 Sent To  
Notes
2014-08-02 14:06:53BUILDING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 2ND REVIEW
 DATE: SAT. AUGUST 02/ 2014
  
 ACTION: DENIED
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) UNDER CONSIDERATION BY THE BUILDING OFFICIAL. THE
 APPLIED VALUE OF THE HOTEL IS VALUED AT $35,000,000.00.
 THE CALCULATED VALUE OF THE PROJECT IS $55,930,374.00
 (312,216 SQ FT X $179.14 BUILDING ONLY, NO SITE
 DEVELOPMENT) USING THE ICC BUILDING VALUATION DATA FOR
 BOTH AUGUST 2013 & FEB, 2014. W P B ADMINISTRTIVE CODE
 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
 IF A BUILDING BREAK OUT OF SQUARE FOOTAGE UNDER EACH
 OCCUPANCY CLASSIFICATION THIS NUMBER WOUD DROP SOME
 WHAT, THIS WAS UNOT COMPLETED UNDER THE OCCUPANCY
 CLASSIFICATION, PROBANLY BECAUSE OF UNLIMITED AREA FOR
 A TYPE 1A BUILDING TYPE.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 0210-A2.00:
  
 3) COMPLIED.
 4) 0211-A2.01/ BASEMENT LEVEL:
  
 4A) 2ND REQUEST, THE FIRST COMMENT ASKED WHY THER WAS
 STORAGE BINS IN THE CORRIDOR, THE RESPONSE INDICATES
 THESE ARE SOILED LAUNDRY BINS.
 SOILED LAUNDRY IS CONSIDERED AN INCIDENTIAL ACCESSORY
 OCCUPANY IN ITSELF, AND IS TO BE SEPARATE WITHIN A
 ROOM, NOT IN A EXIT ACCESS COORIDOR,
 SEE THE 2010 FBC-B TABLE 508.2.5. IT STATES THAT
 LAUNDRY ROOMS ARE TO BE SEPARATED BY 1 HR ROOM OR
 PROVIDE FIRE SPRINKLERS. PLEASE REVIEW 508.2.5.2
 NONFIRE-RESISTANCE-RATED SEPARATION AND PROTECTION.
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL ACCESSORY OCCUPANCIES SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE. THE WALLS
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE CEILING THAT IS
 A COMPONENT OF A FIRE-RESISTANCE-RATED FLOOR ASSEMBLY
 OR ROOF ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE. DOORS SHALL BE
 SELF- OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3. DOORS SHALL NOT HAVE
 AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN
 EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH
 NFPA 80. WALLS SURROUNDING THE INCIDENTAL ACCESSORY
 OCCUPANCY SHALL NOT HAVE AIR TRANSFER OPENINGS UNLESS
 PROVIDED WITH SMOKE DAMPERS IN ACCORDANCE WITH SECTION
 711.7.
  
 1ST REVIEW COMMENT. THE SERVICE COORIDOR B000 IN FRONT
 OF THE HOUSEMANS STORAGE AND HOUSE KEEPING LAUNDRY IT
 APPEARS THERE IS STORAGE CABINETS BEING STORED WITHIN
 THE CORRIDOR? PLEASE EXPLAIN THE USAGE OF THIS AREA?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4B) COMPLIED.
  
 5) 0212-A2.02/ LEVEL 0100
  
 5A-B) COMPLIED.
  
 5C) 2ND REQUEST. THE RESPONCE INDICATES THE LULA LIFT
 IS TO BE ON STANDBY POWER. THE NOTE ABOVE THE LULA LIFT
 INDICATES THAT IT IS GOING TO BE HOOKED UP TO JRH-31
 WHICH IS FOR THE JUNIOR BALL ROOM, ISN'T THE LIFT ON
 THE CONNVENTION CENTER SIDE OF THE PROPERTY LINE, AND
 SHOULDN'T ALL THE POWER FOR THIS SIDE OF THE PROPERTY
 BE COMING FROM THE CONVENTION CENTER?
 NOTE THE PERMIT FOR THE HOTEL STOPS AT THE PROPERTY
 LINE, A SECOND PERMIT WILL BE NEEDED FOR THE
 CONSTRUCTION ACTIVITIES ON THE CONVENTION CENTER
 PROPERTY. AGAIN THE LULA LIFT IS CONSIDERED AN ELEVATOR
 AND TREATED AS SUCH. FBC-B 403.4.7.2 (3) DOES NOT SAY
 ANYTHING ABOUT LIFTS.
 [F] 403.4.7.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 3.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008.
  
 5D-F COMPLIED.
  
 5G) 2ND REQUEST, NOT SHOWN ON THIS SHEET BUT A4.04 DOES
 SHOW THE WEST PROPERTY LINE GOING THROUGH THE CABANAS
 AND POOL ON THE WEST OF THE PROPERTY.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 6A-B) COMPLIED.
  
 6C) NEW COMMENT/ SEMI NEW, NEW LOCATION, THE EXECUTIVE
 LOUNGE HAS BEEN MOVED TO ROOM # 207 THE COMMENTS STILL
 EXIST. THE EXECUTIVE LOUNGE HAS A OCCUPANT LOAD OF 73
 THIS IS AN ASSEMBLY OCCUPANCY PLEASE PROVIDE A
 FURNATURE LATOUT. SHEET A3.00 DOES NOT INCLUDE THIS
 ROOM IN THE PLUMBING FIXTURE COUNT. DEPENDING ON THE
 USAGE THIS MAY BE CONSIDERED EIHER AN A2 OR A3, IF
 CONSIDERED MORE AS A LOUNGE A-2 THE WATER CLOSET RATIO
 WILL BE 1/40 REQUIRING ADDITIONAL FIXTURES.
  
 6D) ROOM 207 THE EXECUTIVE LOUNGE, THERE IS A SMALL
 ROOM THAT NO INFORMATION HAS BEEN PROVIDED, IS THIS FOR
 STORAGE, BAR OR KITCHEN TO BE USED IN CONJUNCTION WITH
 THE LOUNGE? FBC-B 302.1. NOTE FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES. 4. EGRESS SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES.
  
 7-15) COMPLIED.
  
 16) SHEET A4.20 SECTION THRU BUILDING A12.10 : 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
 SHOW COMPLIANCE NOTES ON PLANS QUATING CODE DOES NOT
 MEAN COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM
 COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE WITH: 2010 FBC-B 1407.2 EXTERIOR WALL
 FINISH.
 MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF
 BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL
 WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL
 COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
  
 16B) A12.10 DETAILS 1 & 8 BOTH INDICATE THE PERIMETER
 SUN SCREEN , DETAIL 3 A12.09 ALSO A CLOSE UP OF THE
 PERIMETER SUNSCREEN INDICATE THE USE OF STEEL EMBEDS W/
 NELSON BOLTS PER THE MANUFACTURERS REQUIREMENTS. PLEASE
 PROVIDE ENGINEERING FOR THIS SYSTEM THAT THE DESIGN AND
 ATTACHMENTS WILL MEET THE WINDLOADS AND HEIGHT
 ADJUSTMENT FACTORS FOR THIS ELEVATION, TO BE DESIGNED
 TO ASCE 7-10 .1609.1.1 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 30 OF
 ASCE 7 OR THE PROVISIONS OF THE ALTERNATE ALL HEIGHTS
 METHOD IN SECTION 1609.6. L
  
 17-21) COMPLIED.
  
 22A-C) COMPLIED.
  
 22D) THE FPL VAULT REQUIRES 3 HR WALLS 2008 NEC THE
 DOORS ALSO REQUIRE A 3 HR RATING PER 2008 NEC 450.43(A)
 & 2010 FBC-B TABLE 715.4.
  
  
 23) A5.18:
 WALL IDENTIFICATION TAGS ARE MISSING AND IDENTIFICATION
 OF FIRE RATED WALLS. ADDITIONAL INFORMATION IS
 REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING
 DISCREPANCY IN PLANS. 107.2.1.3.
  
 24-25) COMPLIED.
  
 26) 2ND REQUEST. THE RESPONSE INDICATES THAT THE LINEN
 CHUTE DOOR IS IDENTIFIED AS T26. PLEASE REVIEW THE DOOR
 SCHEDULE ON A14.01, T26 IS FOR THE ICE ROOM NEXT TO THE
 LAUNDRY CHUTE, THAT DOES NOT HAVE ANY DOOR, NOR IS THE
 ARK OF A DOOR INDICATED ON THE PLANS.
  
 SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE GRID
 LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID LINE
 WHICH IS LOCATED IN THE MAIDS ROOM.FLOORS 10-12 SEE
 SHEET A2.11 THE LAUBDRY CHUTE IS OFFSET TO THE
 NORTHEAST OR TO THE EAST OF GRID LINE Y.2 . THE PLANS
 SHOW THE ACCESS TO THE ACCESS CHUTE DOOR LOCATED WITH
 THE CORRADOR. PLEASE CONFORM WITH:
  
 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS
 ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3.
  
 27) 2ND REQUEST. SHEET A12.16 SHOWS A NEW DETAIL WITH A
 FIRE RISER WITHIN THE 2 HR FIRE RATED CHASE BUT THE
 SPRINKLER HEAD DOES NOT PENETRATE INTO THE THE LINEN
 CHUTE NOR DOES THERE SHOW HOW THE SPRINKLER HEAD HAS
 ACCESSIBILITY FOR MAINTENANCE.
 SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION THE
 REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS IN
 THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY PROVIDE
 A DEAIL ON FP0.01 INDICATING SERVICE CHUTE DETAIL.
 708.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE
 REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 28-32) COMPLIED.
  
 33) COMPLIED. 8/07/2014 SIGNED & SEALED ORIGINAL
 SUBMITTED BY APPLICANT.
  
 A DRAFT COPY OF A WIND TUNNEL TEST WAS PROVIDED, THIS
 COMMENT WILL STAY UNTIL THEWIND TUNNEL TEST IS A FINAL
 VERSION. SHEET S0.00 THE WIND DESIGN CRITERIA IS SHOWN
 IN VULT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE ALL
 PRODUCT APPROVALS ARE PRINTED IN VASD.
 TABLE 1609.3. IS THIS PROJECT GOING TO DO WIND TUNNEL
 TESTING TO REDUCE PRESSURES?
  
 34) 2ND REQUEST, NOTE UPON WRITTEN REQUEST THIS CODE
 ISSUE CAN BE A DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT
 THE PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT
 ISSUANCE. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 35) 2ND REQUEST, NOTE UPON WRITTEN REQUEST THIS CODE
 ISSUE CAN BE A DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT
 THE PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT
 ISSUANCE.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 36) THE SMOKE CONTROL NARRATIVE APPEARS TO HAVE BEEN
 PREPARED EARLY ON IN THE DEVELOPMENT OF THE PROJECT.
 THERE ARE STATEMENTS WITHIN THE NARRATIVE THAT DO NOT
 REFLECT THE ACTUAL CONFIGURATION OF THE BUILDING:
  
 36A) PAGE 7 HEADING PRESSURE DIFFERENCES FLOOR TO
 FLOOR. THE NARRATIVE STATE THE BASEMENT AND 1ST FLOOR
 WILL NOT BE PRESSURIZED DASED ON THE BUILDING
 CONFIGURATION THAT ALL STAIRS DISCHARGE TO THE
 EXTERIOR. STAIR WELL # 2 BY THE LOBBY DOES NOT LEAD
 DIRECTLY TO THE EXTERIOR OF THE BUILDING.
  
 36B) PAGE 7 HEADING PRESSURE DIFFERENCES FLOOR TO
 FLOOR. THE NARRATIVE STATE THE BASEMENT AND 1ST FLOOR
 WILL NOT BE PRESSURIZED DASED ON THE BUILDING
 CONFIGURATION THAT ALL STAIRS DISCHARGE TO THE
 EXTERIOR. THE NARRATIVE INDICATES TO REVIEW THE NATURAL
 METHODS OF POST FIRE SALVAGE OPERATION. PLEASE DIRECT
 WHERE THE CODE ALLOWS FOR NATURAL METHODS OF POST FIRE
 SALVAGE OPERATION IN LUE OF A ACTIVE SMOKE CONTROL
 SYSTEM.
 909.20.3 909.20.3 NATURAL VENTILATION ALTERNATIVE DEALS
 STRICTLY WITH THE STAIRWELLS NOT WHOLE FLOORS.
  
 THE SECOND ISSUE IS WITH THE BASEMENT NOT HAVING
 NATURAL VENTILATION AND ALSO USING THE EXIT ACCESS
 CORRIDOR TO STORE 25 + SOILED LAUNDRY CARTS WITHIN THE
 EXIT ACCESS COORIDOR. SEE EARLIER COMMENT 4A).
  
 36C) THIS IS A HIGH RISE BUILDING AND THIS STUDY HAS
 NOT SHOWN HOW SMOKE WILL BE REMOVED FROM THE BASEMENT,
 1ST FLOOR, BALLROOMS WITH HIGH CEILINGS AS WELL AS THE
 2 STORY ATRIUM. 909.2 GENERAL DESIGN REQUIREMENTS.
 BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS
 CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL
 HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS OF SECTION 909 AND THE
 GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF
 ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND
 DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE
 DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE
 SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE
 ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO
 DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS.
  
 36D ) PAGE 12 DEALS WITH THE STAIRWELL SHAFTS THAT WILL
 BE PRESSURIZED BY A FANS CONTROLLED BY A VARIABLE SPEED
 DRIVE WITH RELIEF VENTS. WILL BE REQUIRED TO BE TESTED
 IN ACCORDANCE WITH FBC-B 909.6.2./ 1008.1.2.
  
 37) PLEASE PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
  
 38) EMERGENCY RESPONDER RADIO COVERAGE SHALL BE
 PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA
 FIRE PREVENTION CODE.
  
 39) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B [F]
 911.1.5 REQUIRED FEATURES. THE FIRE COMMAND CENTER
 SHALL COMPLY WITH NFPA 72 AND SHALL CONTAIN THE
 FOLLOWING FEATURES: 1-17.
  
 40) THE SUBMITTED DOCUMENTS FOR 1ST REVIEW DID NOT
 PROVIDE DOCUMENTS FOR THE ENERGY CODE FOR COMPLIANCE.
 SEE 2010 FBC-ENERGY 103.2.1 & 103.2.3.1.2.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-17 Cont ID  
Sent By jwitmer Date 2014-06-17 Time 17:56 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 10:14 Sent To  
Notes
2014-06-05 06:31:33BUILDING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 1ST REVIEW
 DATE: TUESDAY JUNE 17TH/ 2014
  
 ACTION: DENIED
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) THE APPLIED VALUE OF THE HOTEL IS VALUED AT
 $35,000,000.00. THE CALCULATED VALUE OF THE PROJECT IS
 $55,930,374.00 (312,216 SQ FT X $179.14 BUILDING ONLY,
 NO SITE DEVELOPMENT) USING THE ICC BUILDING VALUATION
 DATA FOR BOTH AUGUST 2013 & FEB, 2014. W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
 IF A BUILDING BREAK OUT OF SQUARE FOOTAGE UNDER EACH
 OCCUPANCY CLASSIFICATION THIS NUMBER WOUD DROP SOME
 WHAT, THIS WAS UNOT COMPLETED UNDER THE OCCUPANCY
 CLASSIFICATION, PROBANLY BECAUSE OF UNLIMITED AREA FOR
 A TYPE 1A BUILDING TYPE.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 0210-A2.00:
  
 3A) HEADING: PROJECT NAME LIST THE ADDRESS FORTHIS
 PROJECT AS 901 FLORIDA AVENUE, PLEASE UPDATE THE
 ADDRESS FOR THIS SITE TO 600 OKEECHOBEE BLVD. WEST PALM
 BEACH, FL. (PALM BEACH COUNTY).
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. 2010 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW
 AND EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS.
  
 3B) HEADING: APPLICABLE CODES LIST THE (4) FLORIDA
 BUILDING CODE-TEST PROTOCOLS FOR HIGH VELOCITY
 HURRICANE ZONES- 2010 EDITION PLEASE NOTE THIS PORTION
 OF THE CODE IS FOR BROWARD AND MIAMI-DADE COUNTIES. THE
 ONLY REASON WE MAY LOOK AT THIS CODE IS IF A MIAMI-DADE
 NOA NOTICE OF ACCEPTANCE REPORT IS SUBMITTED, THE
 PRESCRIPTIVE REQUIREMENTS OF THIS CODE HAVE NOT AND CAN
 NOT BE USED IN THIS JURISDICTION.
  
 3C) HEADING CONSTRUCTION TYPE: LIST THE CODE SECTION
 FOR OPEN PARIKNG GARAGES FBC 406.3.5 OPEN PARKING
 GARAGES, PLEASE NOTE THE OPEN PARKING GARAGE IS ON
 ANOTHER PROPERTY, WITH A SEPARATE ADDRESS. THIS
 STRUCTURE WILL REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES, FOR RECORD RECORDING PURPOSES. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 105.1 PERMIT REQUIRED.
  
 3D) THE FIRE RESISTANCE REQUIREMENTS- WALLS DOES NOT
 PROVIDE THE RATING OF THE R-1 TENANT WALLS FOUND IN
 SECTION 2010 FBC-B 439.2 FIRE PARTITIONS.
  
 PLEASE PROVIDE THE ACTUAL SQUARE FOOTAGE OF THE
 BUILDING FOOT PRINT AS WELL AS THE SQUARE FOOTAGE FOR
 THE TOWER AND THE TOTAL OVER ALL SQUARE FOOTAGE UNDER
 ROOF, THESE ARE REQUIREMENTS FOR RECORD KEEPING AND
 PRINTING OF CERTIFICATE OF OCCUPANCY. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3E) SHEET A2.00 WHILE THIS SHEET PROVIDES TABLES FOR
 OCCUPANCY CLASSIFICATION & OCCUPANT LOAD FACTORS THE
 LIFR SAFETY SHEET DOES NOT PROVIDE OCCUPANT LOADS PER
 FLOOR OR FOR THE TOTAL BUILDING. 2010 FBC-B 1004.1
 DESIGN OCCUPANT LOAD.
  
 4) 0211-A2.01/ BASEMENT LEVEL:
  
 4A) THE SERVICE COORIDOR B000 IN FRONT OF THE HOUSEMANS
 STORAGE AND HOUSE KEEPING LAUNDRY IT APPEARS THERE IS
 STORAGE CABINETS BEING STORED WITHIN THE CORRIDOR?
 PLEASE EXPLAIN THE USAGE OF THIS AREA? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4B) THE 2 ROOMS TO THE LEFT OF STORAGE ROOM B005 DO NOT
 PROVIDE IDENTIFICATION, OR USAGE BUT INDICATE A 2 HR
 FIRE RATING PLEASE IDENTIFY ROOMS AND OCCUPANCY. FBC-B
 TABLE 508.4.
  
 5) 0212-A2.02/ LEVEL 0100
  
 5A) IN THE LAST MEETING ALOT OF DISCUSSION TOOK PLACE
 ABOUT THE CONNECTOR BETWEEN THE CONVENTION CENTER AND
 THE HOTEL PROPERTY. ONE TOPIC WAS A DELUGE SYSTEM
 REQUIRED FOR THE GLAZING. 3104.5 REQUIRES A 2 HR
 SEPARATION, WALKWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY NOT LESS THAN 2 HOURS.
 THERE ARE 4 EXCEPTIONS TO THE CODE. THERE ARE 4
 EXCEPTIONS TO THIS REQUIREMENT.
 WITHIN EXCEPTION # 1 THERE IS 3 COMPONENTS:
 1). THE THE WALL IS CAPABLE OF RESISTING THE PASSAGE OF
 SMOKE OR IS CONSTRUCTED OF A TEMPERED, WIRED OR
 LAMINATED GLASS WALL AND DOORS SUBJECT TO THE
 FOLLOWING:
 1.1. THE WALL OR GLASS SEPARATING THE INTERIOR OF THE
 BUILDING FROM THE PEDESTRIAN WALKWAY SHALL BE PROTECTED
 BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND THE SPRINKLER SYSTEM SHALL
 COMPLETELY WET THE ENTIRE SURFACE OF INTERIOR SIDES OF
 THE WALL OR GLASS WHEN ACTUATED;
 1.2. THE GLASS SHALL BE IN A GASKETED FRAME AND
 INSTALLED IN SUCH A MANNER THAT THE FRAMING SYSTEM WILL
 DEFLECT WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER OPERATES; AND
 1.3. OBSTRUCTIONS SHALL NOT BE INSTALLED BETWEEN THE
 SPRINKLER HEADS AND THE WALL OR GLASS.
  
 THE ISSUE WITH THIS EXCEPTION STATES THE INTERIOR SIDE
 OF THE GLASS SHALL BE PROTECTED WITH A SPRINKLER, WHEN
 THE DOORS ARE OPEN THEY WILL NOT BE PROTECTED.
  
 5B) ON THE EMERGENCY EXITING SIDE OF THE CONNECTOR THE
 PLANS STATE THAT THE DOORWAY WILL ACCEPT 640 OCCUPANTS.
 PLEASE REVIEW THE DOORWAY LEADING FROM THE JR.
 BALLROOMS WITH A OCCUPANT LOAD OF 320 OCCUPANTS, THE
 LEFT HAND DOOR BLOCKS ONE OF THE 4 EXIT DOORWAYS
 REDUCING THE CLEAR WIDTH OF THE OPENING. THE OTHER
 ISSUE WITH THIS CONFIGURATION IS THE SAME DOUBLE DOORS
 LEADING FROM THE JR BALLROOMS, THE RIGHT HAND DOOR IS
 PARTIALLY BLOCKED BY THE LEADING EDGE OF THE INSWING
 DOOR, THERE IS ONLY A FOOT UNTIL THIS DOOR SWING
 BECOMES AN OBSTRUCTION AGAIN DECREASING THE ABILITY TO
 GET THE DECLARED OCCUPANT LOAD OUT THIS EXIT THE ACTUAL
 OCCUPANT ACCESS LOADS ARE SKEWED. 2010 FBC-B 1005.1.,
 1005.2 & FBC-B 1008.1.1.1.
  
 5C) PLEASE PROVIDE IF THE LULA LIFT IS ON STANDBY
 POWER? IF THE 3 HOUR FIRE DOOR IS ACTIVATED BY THE FIRE
 ALARM AND IS CLOSED WILL A OCCUPANT IN THE LULA LIFT IF
 LOCATED ON THE LOWER LEVEL BE ABLE TO OPERATE THE LIFT
 TO THE UPPER LANDING TO BE ABLE TO ESCAPE FROM THE
 BUILDING? FBC-B 403.4.7.2 (3) DOES NOT SAY ANYTHING
 ABOUT LIFTS.
 [F] 403.4.7.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 3.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008.
  
 5D) WHAT APPEARS TO BE THE MENS RESTROOM, NOT LABELED,
 BY THE WOMENS RESTROOM # 116 THIS RESTROOM HAS 4
 QUESTION MARKS WITHIN THE RESTROOM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5E) THE LAST MEETING THERE WAS DISCUSSION ABOUT THE
 RATING OF THE COORIDOR IN FRONT OF THE RESTARAUNT 115.
 THE CODE ALLOWS FOR 250 FEET (FBC-B TABLE 1016.1)
 BEFORE HAVING TO REACH EITHER A PROTECTED EXIT FRONT
 THE ENTRANCE OF THE BALL ROOM TO THE FRONT ENTRY THE
 TRAVEL DISTANCE IS APPROXIMATELY 237 FEET. THE OTHER
 ISSUE IS REQUIED EXIT ACCESS CORRIDORS, FBC-B 1018.1
 FOR AN ASSEMBLY OCCUPANCY IN A FIRE SPRINKLERED
 BUILDING THERE IS NO FIRE RATING REQUIRED FOR THIS
 CORRIDOR, YOU SEE THIS IN CONFIGURATION IN MALLS &
 AIRPORT CONCOURSES AND TERMINAL.
  
 5F) MEETING ROOM 2 & 3 WHEN COMBINED THE DIAGONAL
 DISTANCE FROM CORNER TO CORNER APPEARS TO BE 57.2 FEET
 ON THE DIAGONAL AND THE TO ENTRY DOORS ONLY BEING
 13'-0" APART CENTERLINE TO CENTER LINE NOT THE 18'-7 "
 AS INDICATED ON THE PLANS. 2010 FBC-B 1015.2.1 EXCEP #
 2.
  
 5G) NOT SHOWN ON THIS SHEET BUT A4.04 DOES SHOW THE
 WEST PROPERTY LINE GOING THROUGH THE CABANAS AND POOL
 ON THE WEST OF THE PROPERTY.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 6) 0213-A-2.03 0200 LEVEL:
  
 6A) SERVICE ELEVATOR LOBBY TO MAKE CHANGES AS PER THE
 LAST MEETING AS DISCUSSED.
  
 6B) THE MEETING ROOM # 1, BOARDROOM & MEETING ROOM # 2
 ARE TO BE REWORKED AS THE LAST MEETING ALLOWING EACH OF
 THE ADJACENT ROOMS TO BE CONSIDERED INTERVENING ROOMS
 AS PER FBC-B 1014.2 AND THE CORRIDOR DOORS THAT
 SEPARATE THE 2 STORY ATRIUM BE MOVED CLOSER IN TO THE
 ATRIUM AREA ALLOWING EGRESS FROM MEETING ROOM 1 & 2
 INTO THE RATED PORTION OF THE CORRIDOR ACCHIEVING CODE
 COMPLIANCE WITH A HYBRID TYPE OF ATRIM WALL RATED 1 HR
 AND ACHIEVING EXITING WITHOUT HAVING TO TRAVEL THROUGH
 A UNPROTECTED ATRIUM.
  
 7) 0214-A-2.04 / 0300 LEVEL. PLEASE REVIEW GUEST ROOM #
 346 IT APPEARS TO BE MISSING A LAVATORY. SEE DEFITITION
 OF SLEEPING ROOM.
  
 8)0221-A2.11 0100 LEVEL: GUEST ROOM #1046 IS A SHELL
 ROOM, PLEASE PROVIDE A OCCUPANCY TYPE AND OCCUPANCY
 LOAD FOR THIS UNIT, AS DEPICTED THIS MAY BE A ASSMBLY
 OCCUPANCY, PLEASE PROVIDE ADDITIONAL DETAILS THIS ROOM
 IS AN ADJOINING ROOM WITH SUITE # 1044 WHAT IS THE FIRE
 RATING OF THE 2 COMMUNICATING DOORS. FBC-B 302.1, TABLE
 508.4 & TABLE 715.4.
  
 9A) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE
 LOUNGE HAS A OCCUPANT LOAD OF 96 THIS IS AN ASSEMBLY
 OCCUPANCY PLEASE PROVIDE A FURNATURE LATOUT. SHEET
 A3.00 DOES NOT INCLUDE THIS ROOM IN THE PLUMBING
 FIXTURE COUNT. DEPENDING ON THE USAGE THIS MAY BE
 CONSIDERED EIHER AN A2 OR A3, IF CONSIDERED MORE AS A
 LOUNGE A-2 THE WATER CLOSET RATIO WILL BE 1/40
 REQUIRING ADDITIONAL FIXTURES.
  
 9B) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE
 LOUNGE, THERE IS A SMALL ROOM THAT NO INFORMATION HAS
 BEEN PROVIDED, IS THIS FOR STORAGE, BAR OR KITCHEN TO
 BE USED IN CONJUNCTION WITH THE LOUNGE? FBC-B 302.1.
  
 10) A201 LIFE SAFETY BASEMENT PLAN VERSES A4.00 VERSES
 DOOR SCHEDULE.
  
 10A) THE DOMESTIC PUMP ROOM B002 IS SHOWN TO HAVE 2 HR
 RATED WALLS WHERE AS THE DOOR SCHEDULE INDICATESS THE
 DOOR TO BE A 45 MINUTE DOOR.
 2010 FBC-B TABLE 715.4/ 2HR RATED WALLS REQUIRES 1 1/2
 HR PROTECTIVES.
  
 10B) THE STORE ROOM B005 IS INDICATED TO HAVE 1 HR
 WALLS WHERE AS THE DOOR SCHEDULE INDICATES DOOR B005 TO
 BE 90 MIN. FBC-B TABLE 715.4.
  
 10C) THE LAUNDRY ROOM WALLS ARE SHOWN AS 1 HR RATED
 WALLS WHEREAS THE DOOR SCHEDULE INDICATES B006 TO BE A
 90 MIN. DOOR. FBC-B TABLE 715.4.
  
 10D) ROOM B013 SOILED LINEN ROOM IS ALSO THE
 TERMINATION ROOM FOR THE LAUNDRY CHUTE THE WALLS ARE
 INDICATED TO BE ONE HOUR WHERE AS THE DOORS SHOW AS 90
 MINUTE RATED. SEE 708.11 & 708.13.4. THE LAUNDRY CHUTE
 MUST HAVE A 2 HOUR FIRE RATING AT THE END OF THE CHUTE
 TO KEEP THE 1 HR FIRE RATING OF THE ROOM AND 45 MINUTE
 OPENING PROTECTIVES. FBC-B TABLE 715.4.
  
 10E) STAIR # 2, DOOR # B)16A BLOCKS THE STAIRWAY, 2010
 FBC-B 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH.
 1008.1.6 LANDINGS AT DOORS & 1009.5 STAIRWELL LANDINGS
 BLOCKS THE REQUIRED LANDING LENGHT.
  
 11) A2.02 VERSES A4.01 AND DOOR SCHEDULE:
  
 11A) WALLS SHOWN ON A2.02 TO BE 1 HOUR FIRE RATED,
 DOORS IDENTIFIED ON A4.01 AND DOOR SCHEDULE , DOORS
 MISSING RATING IN THE DOOR SCHEDULE ARE
 DOOR 121L, DOOR 121N & DOOR 121O. FBC-B TABLE 715.4
  
 11B) STAIR # 6 A 2 HOUR FIRE RATING AND DOOR SCHEDULE
 MISSING 1 1/2 HR PROTECTIVE . FBC-B TABLE 715.4.
  
 11C) ROOM POOL STORAGE IS A 1 HR RATING , DOOR SCHEDULE
 MISSING FIRE RATING. FBC-B TABLE 715.4.
  
 12) A2.02 VERSES A4.02 AND DOOR SCHEDULE:
  
 12A) FPL VAULT 3 HR FIRE RATING THE DOOR SCHEDULE IS
 MISSING THE1 1/2 HOUR FIRE RATING PER NEC 450.21.
  
 13) SHEET A2.02 & A4.03, SHEET A4.03 COUNTING ROOM 112N
 TABLE IS BLOCKING THE EGRESS DOOR. 2010 FBC-B
 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH.
  
 14) SHEET A2.03 VS A4.07:
  
 14A) SHEET A2.03 INDICATES A 1HR FIRE RATING BETWEEN
 SLEEPING ROOMS IN ACCORDANCE WITH 709.1, PLEASE NOTE
 709.3 DOES NOT GIVE THE 1/2 HR REDUCTION IN WALL RATINS
 SINCE THIS IS A TYPE IA CONSTRUCTION. THE EXCEPTION IS
 FOR IIB, IIIB & VB CONSTRUCTION. THE COMMUNICATING
 DOORS T12 WILL REQUIRE A 3/4 HR FIRE RATED DOOR. THE
 DOOR SCHEDULE DOES NOT INDICATE ANY FIRE RATING. IF
 TRYING TO USE 2/ 20 MIN DOORS, PLEASE SHOW A TESTED
 ASSEMBLY MEETING THE 3/4 HR FIRE RATING. THIS COMMENT
 WILL STAND FOR ALL FLOORS WITH SLEEPING ROOMS WITH
 INTER-CONNECTING DOORS.
  
 14B) DOOR # 219 NOTE # 20 INDICATES THE USE OF A CARD
 READER TO GAIN ACCESS TO THE VERTICAL EXIT STAIRWAY.
 SHEET A2.00 DOES NOT PROVIDE THE ACTUAL OCCUPANT LOADS
 FOR ANY FLOORS PLEASE PROVIDE A MATRIX WITH OCCUPANT
 LOADS PER FLOOR. FBC-B TABLE 1021.1 ONLY REQUIRES 2
 VERTICAL EXITS IF THE OCCUPANT LOAD IS 500 OR LESS,
 REMOTENESS IS MET WITH STAIRWELL 1 &3 WITH THE
 EXCEPTION OF THE TOP 3 FLOORS THERE THE CARD READER
 WOULD NEED TO BE REMOVED. THE TOP FLOOR IS LESS THAN
 120'-0" IN HEIGHT, A FIRE SERVICE ELEVATOR (403.6.1
 REQUIRED AT 120 FT OCCUPIED FLOOR LEVEL) IS NOT
 REQUIRED, THIS STAIR AND ELEVATOR COULD BE FOR BACK OF
 HOUSE USE ONLY AND LIMITED TO EMPLOYEES ONLY. IF THE
 ELEVATORS ARE TO BE FOR THE FIREMEN THEN THE ACCESS
 CARD READERS WOULD NEED TO BE CONNECTED TO THE FIRE
 COMMAND ROOM FOR THIER USE IN CASE OF EMERGENCY.
  
 14C) THE OTHER ISSUE IS THE WAY THE ATRIUM WALL RATING
 IS BEING CONSIDERED AS THE 1 HOUR WALL AT THE MEETING
 ROOMS & BOARD ROOM. THE LAST MEETING IT WAS DISCUSSED
 THAT THERE WOULD BE FIRE RATED DOOR OPENINGS AT EACH
 SIDE OF THE ATRIUM AREA AND NEW COMMUNACATING DOORS
 WITHIN THE BOARDROOM AND MEETING ROOMS TO CREATE
 INTERVENING ROOMS AND A WAY FOR THE OCCUPANTS WITH THE
 BOARD & MEETING ROOMS TO EXIT INTO A EXIT ACCESS
 CORRIDOR.
 TO DO THIS WILL THERE BE EXIT DIRECTIONAL SIGNS SHOWING
 THIS AS A PART OF THE EGRESS PATH. THE OTHER QUESTION
 IS THE A3 ASSEMBLY BOARD & MEETING ROOMS WILL REQUIRE A
 INTERIOR FINISH FOR THE ROOMS AS A C AND THE CORRIDORS
 AS A B, NOW WILL THE MEETING ROOMS BE CONSIDERED
 CORRIDORS AND A B INTERIOR JUST AS THE CORRIDOR. NOTE
 THE ASSEMBLY OCCUPANCY NOW WILL BE EXITING INTO THE
 PORTION OF THE CORRIDOR FOR THE HOTEL ROOMS BUT WILL
 NEED TO MAINTAIN THE FINISH FOR CORRIDORS AS FOR A3
 OCCUPANCY A B FINISH. TABLE 803.9.
  
 ROOMS 201- 217 HAVE THE TWO MEANS OF EGRESS, ROOMS 235
 THRU 250 WILL BE REQUIRED TO TRAVEL THRU THE MEETING
 ROOMS TO MEET THE REQUIRED 2 MEANS OF EGRESS. FBC-B
 TABLE 1018.1 FINSHES & TABLE 1021.1 MINIMUM EXITS.
  
 14D) PLEASE SEE MEETING ROOM # 2 THE LOCAION OF THE ONE
 HOUR RATED WALLTHE PURPLE LINE REPRESENTING THE RATED
 WALL GOES AROUND THE DUCTWOK THAT COMES UP FROM THE 1ST
 FLOOR 48"X15", THE MECHANICAL SHEET M-1.08 DOES NOT
 SHOW A DAMPER IN IT. IT APPEARS THE FIRE RATING SHOULD
 BE ONLY BEHIND THE DUCTWORK, THEN NO DAMPER WOULD BE
 REQUIRED, 713.1.1 DUCTS AND AIR TRANSFER OPENINGS.
  
 15) SHEET A2.03 VS A4.08:
  
 15A) DETAIL 7/12.05 IS A FIRE EXTINGUISHER CABINET IN A
 FIRE RATED WALL, THE DETAILS ON 12.05 DO NOT INDICATE
 HOW THE FIRE RATINGS ARE TO BE MAINTAINED IN THE FIRE
 RATED WALLS. ON SOME OF THE DETAILS FEC RATING SHOULD
 BE SIMILAR TO WALL RATING. PLEASE PROVIDE HOW THE FIRE
 RATING WILL BE MAINTAINED.
  
 15B) SUITE OF ROOMS 240 & 247 DO HAVE INTERVENING ROOMS
 AND DO MEET THE COMMON PATH OF TRAVEL OF 50 FT. ALL
 SUITES WILL NEED TO MEET THE 50' COMMON PATH OF TRAVEL
 FOR A R1 OCCUPANCY. FBC-B 1014.3 ECP # 6.
  
 16) SHEET A4.20 SECTION THRU BUILDING A12.10 :
  
 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM
 COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE WITH: 2010 FBC-B
 1407.2 EXTERIOR WALL FINISH.
 MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF
 BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL
 WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL
 COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
  
 16B) A12.10 DETAILS 1 & 8 BOTH INDICATE THE PERIMETER
 SUN SCREEN , DETAIL 3 A12.09 ALSO A CLOSE UP OF THE
 PERIMETER SUNSCREEN INDICATE THE USE OF
 STEEL EMBEDS W/ NELSON BOLTS PER THE MANUFACTURERS
 REQUIREMENTS. PLEASE PROVIDE ENGINEERING FOR THIS
 SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL MEET THE
 WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR THIS
 ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1
 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 30 OF
 ASCE 7 OR THE PROVISIONS OF THE ALTERNATE ALL HEIGHTS
 METHOD IN SECTION 1609.6. L
  
 17A) SHEET # A5.00 THIS COMMENT WILL STAND FOR ALL
 FLOORS. TYPICAL STANDARD KING. THE PLANS INDICATE A
 WALL TAG 28C WITHIN THE BATHROOM THAT BACKS UP TO
 ANOTHER SLEEPING UNIT. TENANT SEPARATION WALL NOT
 RATED. FBC-B 709.1(6). THE WALL TAG 28C USES
 ABBREVIATIONS GMGB AND SAFB NOT FOUND IN THE
 ABBRREVIATIONS FOUND ON SHEET A0.02. PLEASE PROVIDE
 WHAT THIS STAND FOR? ALSO SEE COMPLIANCE WITH 2010
 FBC-B 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 17B) TYPICAL STANDARD KING TENANT SEPERATION WALL, WALL
 TAG 5B DETAIL SHEET 11/1200 INDICATES FIRE RATING NOT
 REQUIRED. FBC-B 709.1(6).
  
 18) ) SHEET A5.11:
 A) SHEET A5.11 VERSES A2.02 SEE WALL RATINGS OF 1 HOUR
 WALL TAGS 7, 5C & 13 DO NOT SHOW THE 1 HOUR FIRE RATING
 THAT THE LIFE SAFETY PLANS INDICATE.
  
 B) SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT
 MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG
 10A IS INDICATED AS A 2 HR WALL THIS WALL IS A COMMON
 WALL TO THE FPL VAULT A 3 HR RATED WALL. WALL TAG 3B IS
 INDICATED AS NOT RATED BY WALL TAG, A2.02 THE LIFE
 SAFETY PLANS INDICATES THIS WALL TO BE A 1 HOUR FIRE
 RATED WALL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, DISCREPANCY IN PLANS.
  
 C)SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT
 MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG
 3B IS INDICATED AS A NON-RATED WALL A2.02 LIFE SAFETY
 SHEET A 1 HOUR RATED WALL. 107.2.1.3 DISCREPANCY IN
 PLANS. ADDITIONAL INFORMATION IS REQUIRED.
  
 19) SHEET A5.12 :
 A) WALL TAGS 5A COMMON TO RESTROOM 124 AND PRE-FUNCTION
 AREA ARE INDICATED NOT TO BE FIRE RATED WHERE AS A2.02
 LIFE SAFETY SHEET INDICATES THEM TO BE A 1 HOUR FIRE
 RATING. 107.2.1.3 DISCREPANCY IN PLANS. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 B) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE
 COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW
 THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3
 DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 C) ) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE
 COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW
 THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3
 DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 20) SHEET A5.15:
 A) ADMINISTRATIVE OFFICES WALL IDENTIFICATION TAGS LIFE
 SAFETY SHEET INDICATES THIS TO BE A 1 HOUR FIRE RATING
 WHERE AS THE WALL IDENTIFICATION TAGS INDICATE A 2 HR.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 B) SHEET A5.15 COMMON WALL OF SERVICE CORRIDOR AND
 PAYMASTER AT WATER FOUNTAINS WALL IDENTIFICATION TAG
 28C. THIS WALL TAG INDICATES THIS A NON-FIRE RATED WALL
 WHERE AS THE LIFE SAFETY PLAN SHOW THE ONE HOUR FIRE
 RATING GOING THROUGH BEHIND THE WATER FOUNTAINS.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 21) SHEET A5.16 DOCK OFFICE WALL IDENTIFICATION TAGS 4A
 & 2A BOTH INDICATE A 1 HOUR FIRERATING WHERE AS THE
 LIFE SAFETY PLAN INDICATES THESE WALLS AS 2 HR FIRE
 RATING. WINDOW IN A 2 HR RATED WALL 1 1/2 HOUR
 PROTECTIVE. 107.2.1.3.DISCREPANCY. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 22) SHEET A5.17:
 A) THE FPL VAULT SWITH ROOMS DO NOT HAVE WALL
 IDENTIFICATION TAGS, NOR DOES THE 2 SWITCH ROOMS HAVE
 ROOM IDENTIFICATION NUMBERS.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING.
  
 B) NEITHER THE LIFE SAFETY PLAN NOR A5.17 PROVIDE
 WHATTHE REQUIRED FIRE RATING OF THE FPL VAULT CEILING
 IS? SEE A2.00 FPL TRANSFORMER VAULT 2008 NEC 450.21.
  
 C) SHEET A5.17 FPL VAULT DOOR # 143 DOOR HARDWARE
 SCHEDULE UPDATE HARDWARE SEE SECTION FBC-B 1008.1.10
 PANIC AND FIRE EXIT HARDWARE. ELECTRICAL ROOMS WITH
 EQUIPMENT RATED 1,200 AMPERES OR MORE AND OVER 6 FEET
 (1829 MM) WIDE THAT CONTAIN OVERCURRENT DEVICES,
 SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT OR EXIT
 ACCESS DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE OR
 FIRE EXIT HARDWARE. THE DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL.
  
 23) A5.18:
 WALL IDENTIFICATION TAGS ARE MISSING AND IDENTIFICATION
 OF FIRE RATED WALLS. ADDITIONAL INFORMATION IS
 REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING
 DISCREPANCY IN PLANS. 107.2.1.3.
  
 24) A7.03, A7.05 & A7.10 THE STAIR FLOOR PLANS DO NOT
 INDICATE THE REQUIRED STANDPIPES 2010 FBC-B 905.3. [F]
 403.3.1.1 RISER LOCATION.
 SPRINKLER RISERS SHALL BE PLACED IN EXIT ENCLOSURES
 THAT ARE REMOTELY LOCATED IN ACCORDANCE WITH SECTION
 1015.2.
  
  
 25) SHEET A7.15 THE LINEN CHUTE DETAIL AT THE 12TH
 FLOOR THE 2 HOUR RATED SHAFT STOPS SHORT OF THE ROOF
 DECK, YET THE LAUNDRY CHUTE CONTINUES THROUGH THE ROOF.
 708.12 ENCLOSURE AT THE TOP. A SHAFT ENCLOSURE THAT
 DOES NOT EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING,
 DECK OR SLAB OF THE BUILDING SHALL BE ENCLOSED AT THE
 TOP WITH CONSTRUCTION OF THE SAME FIRE-RESISTANCE
 RATING AS THE TOPMOST FLOOR PENETRATED BY THE SHAFT,
 BUT NOT LESS THAN THE FIRE-RESISTANCE RATING REQUIRED
 FOR THE SHAFT ENCLOSURE.
  
 26) SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE
 GRID LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID
 LINE WHICH IS LOCATED IN THE MAIDS ROOM.
 FLOORS 10-12 SEE SHEET A2.11 THE LAUBDRY CHUTE IS
 OFFSET TO THE NORTHEAST OR TO THE EAST OF GRID LINE Y.2
 . THE PLANS SHOW THE ACCESS TO THE ACCESS CHUTE DOOR
 LOCATED WITH THE CORRADOR. PLEASE CONFORM WITH:
  
 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS
 ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3.
  
 27) SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION
 THE REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS
 IN THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY
 PROVIDE A DEAIL ON FP0.01 INDICATING SERVICE CHUTE
 DETAIL.
 708.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE
 REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 28A) SHEET A7.03, A7.07 & A7.10 THE STAIR PLANS AND
 NOTES DO NOT INDICATE COMPLIANCE WITH 2010 FBC-B
 403.5.5 AND SECION 1024 LUMINOUS EGRESS PATH MARKINGS.
  
 28B) THESE SHEETS ALSO ARE MISSING COMPLIANCE WITH
 403.5.3.1 STAIRWAY COMMUNICATION SYSTEMS.
  
 29) SHEET A12.20 DETAILS 4A & 4B SHOW THE USE OF PIING
 PILE CAPS AND GRADE BEAMS, AREN'T THE PILES BEING
 ELIMINATED? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 30) SHEET A12.22 DETAIL # 1 SPRAY APPLIED
 FIRE-RESISTANCE MATERIALS INDICATES SEE DETAIL ON
 A12.04 SPRAY APPLIED RESISTIVE MATERIAL. PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 403.2.4 SPRAYED FIRE-RESISTANT
 MATERIALS (SFRM).
 THE BOND STRENGTH OF THE SFRM INSTALLED THROUGHOUT THE
 BUILDING SHALL BE IN ACCORDANCE WITH TABLE
 403.2.4.HEIGHT OF BUILDING (A FOOTNOTE)
 SFRM MINIMUM BOND STRENGTH UP TO 420 FEET 430 PSF (A)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS.
  
 31) SHEET A12.09.2 ALUMINUM FRAMED GLASS CANOPY DETAILS
 PLEASE PROVIDE COMPLIANCE WITH GLAZING REQUIREMENTS
 FOUND UNDER THE 2010 FBC-B
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1. FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING MATERIAL
 OF THE SINGLE LIGHT OR LAYER SHALL BE LAMINATED GLASS
 WITH A MINIMUM 30-MIL (0.76 MM) POLYVINYL BUTYRAL (OR
 EQUIVALENT) INTERLAYER, WIRED GLASS, LIGHT-TRANSMITTING
 PLASTIC MATERIALS MEETING THE REQUIREMENTS OF SECTION
 2607, HEAT-STRENGTHENED GLASS OR FULLY TEMPERED GLASS.
 2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR
 LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3.
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610. GLASS-BLOCK CONSTRUCTION SHALL CONFORM TO
 THE REQUIREMENTS OF SECTION 2101.2.5.
  
 32)) SHEET A5.04 PLEASE REVIEW THE HOSPITALITY SUITES
 DETAIL 1 & 2 NEITHER OF THESE SUITES SHOW UP ON THE
 FLORIDA ACCESSIBLITY ROOM MATRIX. PLEASE REVIEW 2010 FL
 ACCESSIBILITY SECTION 224.5 THESE UNITS DO HAVE
 KITCHENS IN THEM WHERE AS NONE OF THE OTHER UNITS IN
 THE MATRIX INDICATE SUITES WITH KITCHENS NOR ARE THE
 BATHROOMS ACCESSIBLE.
  
 33) SHEET S0.00 THE WIND DESIGN CRITERIA IS SHOWN IN
 VULT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE ALL
 PRODUCT APPROVALS ARE PRINTED IN VASD.
 TABLE 1609.3. IS THIS PROJECT GOING TO DO WIND TUNNEL
 TESTING TO REDUCE PRESSURES?
  
 34) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 35) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 36) SHEET M5.1 SMOKE CONTROL NOTES UNDER THE HEADING
 GENERAL , SMOKE CONTROL NOTES AND SMOKE CONTROL
 SEQUENCE THE NOTES DO NOT MAKE IT CLEAR HOW THE SMOKE
 CONTROL SYSTEM IS TO OPERATE.
 2010 FBC-B 03.4.6 SMOKE REMOVAL.SMOKE CONTROL SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 909. SECTION 909
 PROVIDES VARIOUS METHODS OF COMPLYING WITH SMOKE
 CONTROL:
 909.6 PRESSURIZATION METHOD.
 909.7 AIRFLOW DESIGN METHOD.
 909.8 EXHAUST METHOD.
 909.9 DESIGN FIRE.
  
 [F] 909.2 GENERAL DESIGN REQUIREMENTS.
 BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS
 CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL
 HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS OF SECTION 909 AND THE
 GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF
 ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND
 DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE
 DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE
 SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE
 ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO
 DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS.
  
 [F] 909.3 SPECIAL INSPECTION AND TEST REQUIREMENTS.
 IN ADDITION TO THE ORDINARY INSPECTION AND TEST
 REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND PARTS
 THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL SYSTEMS
 SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL UNDERGO
 SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO VERIFY THE
 PROPER COMMISSIONING OF THE SMOKE CONTROL DESIGN IN ITS
 FINAL INSTALLED CONDITION. THE DESIGN SUBMISSION
 ACCOMPANYING THE CONSTRUCTION DOCUMENTS SHALL CLEARLY
 DETAIL PROCEDURES AND METHODS TO BE USED AND THE ITEMS
 SUBJECT TO SUCH INSPECTIONS AND TESTS. SUCH
 COMMISSIONING SHALL BE IN ACCORDANCE WITH GENERALLY
 ACCEPTED ENGINEERING PRACTICE AND, WHERE POSSIBLE,
 BASED ON PUBLISHED STANDARDS FOR THE PARTICULAR TESTING
 INVOLVED.
  
 [F] 909.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6.
  
 37) PLEASE PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
  
 38) EMERGENCY RESPONDER RADIO COVERAGE SHALL BE
 PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA
 FIRE PREVENTION CODE.
  
 39) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B [F]
 911.1.5 REQUIRED FEATURES. THE FIRE COMMAND CENTER
 SHALL COMPLY WITH NFPA 72 AND SHALL CONTAIN THE
 FOLLOWING FEATURES: 1-17.
  
 40) THE SUBMITTED DOCUMENTS FOR 1ST REVIEW DID NOT
 PROVIDE DOCUMENTS FOR THE ENERGY CODE FOR COMPLIANCE.
 SEE 2010 FBC-ENERGY 103.2.1 & 103.2.3.1.2.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By dhayes Date 2014-08-20 Time 16:26 Rev Time 0.00
Received By dhayes Date 2014-08-13 Time 16:22 Sent To  
Notes
2014-08-15 12:48:02DATE: 8/15/2014
 PROJECT: WPB HILTON CONVENTION CENTER HOTEL
 PERMIT#: 14050111
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SHEET E1-01
 A. ELECTRICAL RM, FIRE PUMP RM, ELEVATOR EQUIPMENT ROOM
 MECHANICAL RM AND SIMILAR ROOMS, SHOULD NOT HAVE AN OS
 SWITCH DUE TO FBC 505.2.2 EXCEPTION #4 SPACES WHERE AN
 AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT SAFETY OR
 SECURITY.
  
 2) SHEET E1.09
 A. 680.10 UNDERGROUND WIRING LOCATION. UNDERGROUND
 WIRING SHALL NOT BE PERMITTED UNDER THE POOL OR WITHIN
 THE AREA EXTENDING 1.5 M (5 FT) HORIZONTALLY FROM THE
 INSIDE WALL OF THE POOL UNLESS THIS WIRING IS NECESSARY
 TO SUPPLY POOL EQUIPMENT PERMITTED BY THIS ARTICLE.
 WHERE SPACE LIMITATIONS PREVENT WIRING FROM BEING
 ROUTED A DISTANCE 1.5 M (5 FT) OR MORE FROM THE POOL,
 SUCH WIRING SHALL BE PERMITTED WHERE INSTALLED IN
 COMPLETE RACEWAY SYSTEMS OF RIGID METAL CONDUIT,
 INTERMEDIATE METAL CONDUIT, OR A NONMETALLIC RACEWAY
 SYSTEM. ALL METAL CONDUIT SHALL BE CORROSION RESISTANT
 AND SUITABLE FOR THE LOCATION. THE MINIMUM COVER DEPTH
 SHALL BE AS GIVEN IN TABLE 680.10.
 B. 680.22 (5)(C)(1) MEASUREMENTS. IN DETERMINING THE
 DIMENSIONS IN THIS SECTION ADDRESSING RECEPTACLE
 SPACING THE DISTANCE TO BE MEASURED SHALL BE THE
 SHORTEST PATH THE SUPPLY CORD OF AN APPLIANCE CONNECTED
 TO THE RECEPTACLE WOULD FOLLOW WITHOUT PIERCING A
 FLOOR, WALL, CEILING, DOORWAY WITH HINGED OR SLIDING
 DOOR, WINDOW OPENING, OR OTHER EFFECTIVE PERMANENT
 BARRIER.
 (C) LUMINAIRES, LIGHTING OUTLETS, AND CEILING-SUSPENDED
 (PADDLE) FANS.
 (1) NEW OUTDOOR INSTALLATION CLEARANCES. IN OUTDOOR
 POOL AREAS, LUMINAIRES, LIGHTING OUTLETS, AND CEILING
 SUSPENDED (PADDLE) FANS INSTALLED ABOVE THE POOL OR THE
 AREA EXTENDING 1.5 M (5 FT) HORIZONTALLY FROM THE
 INSIDE WALLS OF THE POOL SHALL BE INSTALLED AT A HEIGHT
 NOT LESS THAN 3.7 M (12 FT) ABOVE THE MAXIMUM WATER
 LEVEL OF THE POOL.
  
 3) SHEET E4.01
 A. PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
 B. IDENTIFY ALL SWITCHGEAR. SEE NEC 110.22
 IDENTIFICATION OF DISCONNECTING MEANS. AND 240.86(A)
 (A) GENERAL. EACH DISCONNECTING MEANS SHALL BE LEGIBLY
 MARKED TO INDICATE ITS PURPOSE UNLESS LOCATED AND
 ARRANGED SO THE PURPOSE IS EVIDENT. THE MARKING SHALL
 BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT INVOLVED.
 (B) NEC 230.95 GROUNDFAULT PROTECTION OF EQUIPMENT
 SHALL BE PROVIDED FOR SOLIDLY GROUNDED WYE ELECTRIC
 SERVICES OF MORE THAN 150 VOLTS TO GROUND BUT NOT
 EXCEEDING 600 VOLTS PHASE-TO-PHASE FOR EACH SERVICE
 DISCONNECT RATED 1000 AMPERES OR MORE.
 (C) NEC 230.95 (C) THE GROUND-FAULT PROTECTION SYSTEM
 SHALL BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON
 SITE. THE TEST SHALL BE CONDUCTED IN ACCORDANCE WITH
 INSTRUCTIONS THAT SHALL BE PROVIDED WITH THE EQUIPMENT.
 A WRITTEN RECORD OF THIS TEST SHALL BE MADE AND SHALL
 BE AVAILABLE TO THE AUTHORITY HAVING JURISDICTION.
 (D) ENGINEERED SERIES COMBINATION SYSTEMS.
 NEC 240.86 SERIES RATINGS. WHERE A CIRCUIT BREAKER IS
 USED ON A CIRCUIT HAVING AN AVAILABLE FAULT CURRENT
 HIGHER THAN THE MARKED INTERRUPTING RATING BY BEING
 CONNECTED ON THE LOAD SIDE OF AN ACCEPTABLE OVERCURRENT
 PROTECTIVE DEVICE HAVING A HIGHER RATING, THE CIRCUIT
 BREAKER SHALL MEET THE REQUIREMENTS SPECIFIED IN (A) OR
 (B), AND (C)
 C. PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE PUMP
 FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL WIRING
 AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED.
 INDICATE THE FIRE RATING AND MATERIAL REQUIRED. NEC
 695.6, 695.14
 D. VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORIES. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT
 MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN
 THE MOTOR IS OPERATING AT 115% OF THE FULL ?LOAD
 CURRENT RATING. NEC 695.6, 695.7
 INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE
 IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY
 INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC
 700.9
 E. PROVIDE SIGNS AT THE SERVICE INDICATING THE TYPE AND
 LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC
 700.8
  
 4) SHEET E5.01, E5.04
 PANEL 2CH, PANEL M1, AND POSSIBLY OTHERS NOT NOTED IN
 THIS REVIEW INDICATE MORE CIRCUITS THAN THE PANEL BOARD
 IS RATED FOR. 2, AND 3 POLE CIRCUITS SHALL BE
 CONSIDERED 2 OR 3 POLE DEVICES. IDENTIFY ALL
 PANELBOARDS ACCORDINGLY NEC 408.54. REVISE PANEL
 SCHEDULES TO COMPLY.
  
 5) GENERAL NOTES:
 A. PROVIDE MANUFACTURER DATA SHEETS FOR FLOOR BOXES,
 B. A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATOR, SWIMMING POOL, FIRE ALARM,
 SECURITY, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING,
 AUDIO/VIDEO, AND SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-11 Cont ID  
Sent By albarran Date 2014-06-11 Time 11:39 Rev Time 0.00
Received By albarran Date 2014-06-03 Time 09:07 Sent To  
Notes
2014-06-11 11:41:29PERMIT 14050111, WEST PALM BEACH CONVENTION CENTER
 HILTON HOTEL
 THE FIRST ELECTRICAL REVIEW FAILED AS LISTED BELOW:
 THE FOLLOWING IS A LIST OF THE CHANGEMARKS, NOTES AND
 CORRECTIONS ENTERED AS RESULT OF THE ELECTRICAL REVIEW
 ON THE ABOVE MENTIONED PERMIT. THE DIGITAL SET HAS BEEN
 MARKED WITH EVERY NOTE AND COMMENT THAT APPEARS BELOW.
 FOR EASE OF CORRECTING, PLEASE NOTE THAT THE COMMENTS
 ARE ARRANGED WITH PAGE NUMBERS AND THE RESPECTIVE
 CHANGEMARK NUMBER PER PAGE.
 PAGE E0.00
 1. THE ADOPTED VERSION OF THE NEC AT THE TIME OF THIS
 REVIEW IS THE 2008 EDITION, WHICH IS THE ONE THAT SHALL
 APPLY.
 2. NEED MORE SPECIFICS ON THE WIND LOAD CRITERIA. IS
 THE REFERENCE TO ULTIMATE OR NOMINAL?
 3. CORRECT THIS QUOTE/REFERRAL TO NEC SECTION 368.6 AS
 IT DOES NOT EXIST IN THE 2008 EDITION OF THE NEC.
 4. A SEPARATE PERMIT AND SHOP DRAWINGS ARE REQUIRED FOR
 THE FIRE ALARM INSTALLATION.
 PAGE E1.01
 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY
 CONSERVATION, SEC. 505.
 PAGE E1.06, E1.07
 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY
 CONSERVATION, SEC. 505.
 PAGE E1.22
 1. PER NEC 406.8, ALL 15 AND 20 AMPERE, 125 AND 250
 VOLT NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE.
 PAGE E2.00, E2.01, E2.03, E2.04
 1. THE 2010 EDITION OF THE FLORIDA BUILDING CODE -
 ENERGY CONSERVATION SECTION 505.2.1.3(3) SLEEPING UNIT
 CONTROLS HAS SPECIFIC LIGHTING CONTROL REQUIREMENTS FOR
 HOTEL GUEST SUITES WHICH HAVE TO BE COMPLIED WITH. SEE
 CLOUDED AREAS ON PLANS.
 2. AS PER 2008 NEC 210.60, RECEPTACLE PLACEMENT IN
 HOTEL ROOMS SHALL COMPLY WITH NEC SECTIONS 210.52(A) &
 (D)
 3. PAGE E2.04, E2.05 CIRCUIT ?L? IS NOT IDENTIFIED.
 THIS CIRCUIT APPEARS TO BE IN A KITCHEN AREA. THOUGH
 NOT INDICATED, IF PERMANENT COOKING FACILITIES ARE
 INSTALLED, OUTLET PLACEMENT SHALL BE AS PER NEC 210.52
 PAGE E3.09
 1. ADDED NOTE: EVERY GENERAL PURPOSE OUTLET INSTALLED
 WITHIN 6' OF A SINK SHALL BE GFI PROTECTED, AS PER NEC
 210.8(B)(5)
 2. REFERRAL TO AN OUTLET IN A PORTABLE POOL BAR IS
 MADE. ELABORATE FURTHER ON THIS. IF THE POOL BAR IS
 PORTABLE WHAT OUTLET ARE YOU REFERRING TO?
 PAGE E4.01
  REFERENCE TO THE ARC-FLASH LABEL REQUIREMENTS OF NEC
 110.16 IS MADE.
 1. ACCORDING TO THE PANEL SCHEDULE FOR MDP "M1", THIS
 GOES TO CKT 12
 2. NOT USED
 3. MISSING OCPD FOR PANEL "1LB", FROM PANEL "1L" ON
 RISER PAGE 501 PANEL "1L"
 4. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G"
 PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES
 "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE
 SAME? IF SO, CORRECT TO MATCH
 5. THIS PANEL IS LABELED "GL" IN THE PANEL SCHEDULE FOR
 "BRH".
 6. THE MAINS FOR THESE TWO PANELS ARE INVERTED
 ACCORDING TO THE PANEL SCHEDULE FOR "M2" ON PAGE E5.05.
 7. THIS DISCONNECT & TRANSFORMER ARE MISSING FROM THE
 RISER DIAGRAM
 8. SAME AS NOTE 7, THIS DISCONNECT AND TRANSFORMER DO
 NOT APPEAR ON THE PANEL SCHEDULE.
 9. THE PANEL SCHEDULE OF PANEL "12NLA" HAS CKTS FOR
 THIS PANEL RATHER THAN FROM PANEL "12NL" AS INDICATED
 HERE. CORRECT TO MATCH.
 10. THIS PANEL APPEARS TO BE LABELED "ILDE" ON THE
 PANEL SCHEDULE PAGE E4.03
 PAGE E4.02
  ALL WIRE SHALL BE LISTED FOR THE APPLICATION
 1. AS INDICATED HEREIN THAT 120V FOR LIGHTING CONTROL
 PROVIDED BY OTHER. UNLESS THIS WORK IS INITIATED &
 COMPLETED BY THE ELECTRICAL CONTRACTOR OF RECORD, A
 SEPARATE PERMIT SHALL BE REQUIRED FOR THE LOW VOLTAGE
 CONTROL WORK.
 PAGE E4.03
 1. ON THE RISER DIAGRAM OF PAGE E4.01, THIS PANEL
 APPEARS TO BE LABELED "1LDE" RATHER THAN "ILDE".
 CORRECT TO MATCH.
 PAGE E5.01
 1. REFERENCE MADE ON PANEL ?L?, ?2L? OF GFCI
 REQUIREMENTS OF NEC 422.52
 2. MISSING OCPD FOR PANEL "1LB", PER RISER ON PG. E4.01
 PAGE E5.02
 1. REFERENCE NOTE TO THE NEC 210.8 GFCI REQUIREMENT FOR
 OUTLETS ON ROOFS.
 2. SOURCE REFERENCE FOR PANELS ?2LS? & ?2LSA?
 3. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G"
 PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES
 "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE
 SAME? IF SO, CORRECT TO MATCH
 PAGE E5.04
 1. ACCORDING TO THE RISER DIAGRAM OF PAGE E4.01 THE
 SOURCE FOR PANEL "2CH" IS "M2". HERE IT INDICATES "M1"
 CORRECT ACCORDINGLY.
 2. NEC 422.52 REQUIRES ELECTRIC DRINKING FOUNTAINS TO
 BE ON A GFCI CKT.
 3. NEC 422.51 HAS SPECIFIC REQUIREMENTS FOR VENDING
 MACHINE CKTS.
 4. THERE ARE NUMEROUS GFI REQUIREMENTS NOT ADDRESSED
 WITH RESPECT TO THE POOL AS WELL AS THE ELECTRIC
 DRINKING FOUNTAIN.
 PAGE E5.05
 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3"
 WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2"
 PAGE E5.06
 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3"
 WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2"
 PAGE E5.07
 1. THE RISER DIAGRAM OF PAGE E4.01 SHOWS PANEL "PSLD"
 AS BEING FED FROM PANEL "12NL" NOT "12NLA" CORRECT TO
 MATCH.
 PAGE E5.08
 1. INDICATE THAT THIS PANEL ("KEQL") IS FED THROUGH
 TRANSFORMER "T75", TO MATCH RISER DIAGRAM
 2. INDICATE THAT THIS PANEL "("3EQL") IS FED THROUGH
 THE DISCONNECT VIA TRANSFORMER "T45".
 PAGE E5.09
 1. PER NFPA REQUIREMENTS, THESE CKT/BKRS SHALL BE RED
 AND MECHANICALLY PROTECTED AS REQUIRED.
 PAGE FA0.00
  SEPARATE PERMIT & SHOP DRAWINGS REQUIRED FOR THE FIRE
 ALARM
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-08-13 Cont ID  
Sent By Mgonzale Date 2014-08-13 Time   Rev Time 1.00
Received By mgonzale Date 2014-08-13 Time   Sent To E
Notes
2014-08-13 10:18:45NO OBJECTION

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By Mgonzale Date 2014-06-27 Time   Rev Time 1.00
Received By mgonzale Date 2014-06-27 Time   Sent To I
Notes
2014-06-27 12:58:44PLEASE ADDRESS PLANNING'S COMMENTS.THANK YOU!
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By wjolin Date 2014-08-20 Time 11:50 Rev Time 0.00
Received By wjolin Date 2014-07-30 Time 17:01 Sent To  
Notes
2014-08-08 11:26:07600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL
 PERMIT #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER
 TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS).
  
  
 NEW COMMENT - SHEETS A3.00 - A3.14: DRAWING SERIES WILL
 NEED TO BE UPDATED TO INCORPORATE THE NEW FLOOR PLANS
 REPRESENTED ON THE OTHER SHEETS.
  
 NEW COMMENT - SHEET A4.03: FIRE COMMAND #150 HAS BEEN
 RECONFIGURED RESULTING IN A MINIMUM ROOM DIMENSION OF
 LESS THAN 10'-0" (FBC 911.1.3).
  
 NEW COMMENT - SHEET A4.04: FITNESS (#104) FREE-WEIGHTS
 STORAGE RACK IS OBSTRUCTING EXIT DOOR #104A.
  
 RESPONSE COMMENT: FIRE PIT (SKY TERRACE) HAS NOT BEEN
 ACCEPTED OR REJECTED AT THIS TIME. PRODUCT DATA AND
 SHOP DRAWINGS TO BE SUBMITTED BY CONTRACTOR. OPEN
 FLAMES WILL NEED TO BE GUARDED AGAINST ACCIDENTAL OR
 INTENTIONAL CONTACT BY OCCUPANTS.
 ORIGINAL COMMENT - GENERAL: PROVIDE ADDITIONAL
 INFORMATION ON THE PROPOSED GAS FIRED PIT LOCATED NEAR
 THE OPEN SKY TERRACE/BAR. SHEET E1-05 REFERENCES A GAS
 FIRED PIT CONTROLLER, BUT NO OTHER DESIGN INFORMATION
 WAS FOUND.
  
 RESPONSE COMMENT: ONLY ONE EXIT SIGN PROVIDED. THIS ONE
 FIXTURE WILL BE INSUFFICIENT TO CLEARLY AND OBVIOUSLY
 DIRECT OCCUPANTS TO THE EXITS.
 ORIGINAL COMMENT - SHEET E1-06: NO EXTERIOR EXIT SIGNS
 DIRECTING POOL OCCUPANTS TO EGRESS THROUGH THE
 CONNECTOR.
  
 NEW COMMENT - SHEET E3.04: PROVIDE EMERGENCY LIGHTING
 IN UNDERGROUND POOL EQUIPMENT ROOM IF NOT ALREADY
 PROVIDED.
  
 RESPONSE COMMENT: PORTIONS OF THE SYSTEM UPSTREAM OF
 ANY PRVS WILL BE SUBJECT TO PRESSURES EXCEEDING 150 PSI
 DUE TO THE FIRE PUMP CHURN PRESSURE (+140 PSI) PLUS AN
 ADDITIONAL +70 PSI FROM THE CITY SUPPLY SIDE.
 ORIGINAL COMMENT - SHEET FP0-01: FIRE SPRINKLER NOTE
 #15 - PER NFPA 13 SECTION 24.2.1.2 PORTIONS OF THE
 SYSTEM NORMALLY SUBJECTED TO SYSTEM WORKING PRESSURES
 IN EXCESS OF 150 PSI SHALL BE TESTED AT A PRESSURE OF
 50 PSI IN EXCESS OF SYSTEM WORKING PRESSURE.
  
 MODIFIED COMMENT: SHEET FP1-04, PROVIDE AN ADDITIONAL
 2-1/2" FIRE DEPARTMENT HOSE VALVE IN HOTEL LOBBY #100
 CORRIDOR.
 ORIGINAL COMMENT - FIRE PROTECTION LEVEL 1: DUE TO THE
 SIZE OF THE FLOOR PLATE, PLEASE PROVIDE 2-1/2" FIRE
 DEPARTMENT HOSE VALVES THROUGHOUT THE CORRIDORS.
  
 NEW COMMENT: SHEET FP1-04, VERIFY AND CONFIRM ANY
 EXTERIOR ROOFS, CANOPIES AND PORTE-COCHERES COMPLY WITH
 NFPA 13 SECTION 8.15.7.
  
 RESPONSE COMMENT: DRAWINGS HAVE NOT BEEN MODIFIED TO
 ADDRESS THE ORIGINAL COMMENT.
 ORIGINAL COMMENT - SHEET FP1-13: THE SPRINKLERS
 PROTECTING THE SPACES ON THE ROOF LEVEL WILL NEED TO BE
 SUPPLIED BY A SEPARATE SUPERVISED CONTROL VALVE AND
 FLOW SWITCH SO FIREFIGHTERS CAN DISTINGUISH A FIRE ON
 THE 12TH FLOOR FROM A FIRE ON THE ROOF LEVEL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-11 Cont ID  
Sent By wjolin Date 2014-06-11 Time 16:26 Rev Time 0.00
Received By wjolin Date 2014-05-06 Time 17:19 Sent To  
Notes
2014-05-07 08:31:54600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL
 PERMIT #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER
 TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS).
  
  
 SHEET A2.02: FITNESS (#104) IS USING AN OCCUPANT LOAD
 FACTOR OF 100 SQUARE FEET PER PERSON. EXERCISE ROOMS
 WITH EQUIPMENT OR WITHOUT EQUIPMENT SHALL USE AN
 OCCUPANT LOAD FACTOR OF 15 SQUARE FEET PERSON OR 50
 SQUARE FEET PERSON RESPECTIVELY PER TABLE 7.3.1.2.
 PROVIDE AN EQUIPMENT LAYOUT.
  
 SHEET A2.02: A DELUGE SPRINKLER SYSTEM IS INDICATED TO
 PROTECT THE CONNECTOR AND ACHIEVE AN EQUIVALENT 2-HOUR
 FIRE RATED ENCLOSURE. TO MY KNOWLEDGE, THERE IS NOT A
 LISTED DELUGE SYSTEM CAPABLE OF ACHIEVING THIS FIRE
 RESISTANCE RATING. A MORE APPROPRIATE DESIGN MAY
 INCLUDE THE USE OF THE TYCO WIINDOW SPRINKLERS. IF THE
 DESIGN INTENT IS TO USE TYCO WINDOW SPRINKLERS TO
 ACHIEVE UP TO A TWO-HOUR FIRE RATED SEPARATION, THE
 SPRINKLERS MUST BE INSTALLED ACCORDING TO THE UL
 LISTING DATA AND SHALL WET THE ENTIRE GLAZING SURFACE.
 SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE DOORS OR
 WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW HORIZONTAL
 WINDOW MULLIONS AND REQUIRE THE GLASS CURTAIN WALL TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO INCHES AWAY FROM THE
 GLAZING. PAY SPECIAL ATTENTION TO THE GLAZING ASSEMBLY
 AS THE SPRINKLER POSITIONING VARIES FOR BUTT-GLAZED
 INSTALLATIONS COMPARED TO VERTICAL MULLION
 INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A DEPTH
 THAT PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS.
 THE SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW
 SPRINKLER MODEL WILL BE USED (HORIZONTAL SIDEWALL OR
 PENDENT VERTICAL SIDEWALL).
  
 SHEET A2.03: THE TWO STORY OPENING (PRE-FUNCTION #221)
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 8.6 FOR
 VERTICAL OPENINGS AS EITHER A "COMMUNICATING SPACE",
 "ATRIUM" OR " CONVENIENCE OPENING." FOR EXAMPLE, A
 COMMUNICATING SPACE REQUIRES THE ENTIRE FLOOR AREA TO
 BE OPEN AND UNOBSTRUCTED SUCH THAT A FIRE IN ANY PART
 OF THE SPACE WILL BE READILY OBVIOUS TO THE OCCUPANTS
 OF THE SPACE PRIOR TO THE TIME A FIRE BECOMES A HAZARD.
 ANOTHER EXAMPLE, A CONVENIENCE OPENING REQUIRES THAT
 THE FLOOR OPENING BE SEPARATED FROM EXIT ACCESS
 CORRIDORS.
  
 SHEET A2.03: THE PLAN SHOWS THE 1-HOUR FIRE RATING
 CROSSING THE CORRIDOR AT DOOR #221A; HOWEVER, THERE IS
 NO 1-HOUR FIRE RATING INDICATED FOR THE WALL CROSSING
 THE CORRIDOR AT DOOR #221B. ALSO THE DOOR SCHEDULE
 (SHEET A14.01) DOES NOT INDICATE A FIRE RATING FOR
 EITHER SET OF DOORS.
  
 SHEET A3.0: PROVIDE DIRECT ACCESS INTO THE FIRE PUMP
 ROOM (B003) FROM THE CORRIDOR WITHOUT HAVING TO TRAVEL
 THROUGH THE DOMESTIC PUMP ROOM (B002) FIRST.
  
 SHEET A3.01: STAIR #2 TERMINATES INSIDE THE BUILDING
 WHICH IS PERMITTED BY SECTION 28.2.7.2; HOWEVER, THE
 TRAVEL DISTANCE FROM THE TERMINATION OF THE EXIT
 ENCLOSURE TO AN EXTERIOR EXIT DOOR LEADING TO A PUBLIC
 WAY SHALL NOT EXCEED 100 FEET.
  
 SHEET A4.01: CONNECTOR DOORS (#156-#156F & 118A)
 INDICATE THE USE OF TEMPERED GLASS. DOOR GLAZING WILL
 NEED TO BE FIRE RATED AS SPRINKLERS ARE NOT LISTED TO
 PROTECT OPERABLE DOOR/WINDOW GLAZING AND PROVIDE AN
 EQUIVALENT FIRE RATING.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A TWO-HOUR WALL RATING AROUND STAIR #6;
 HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES NOT
 INDICATE A DOOR FIRE RATING OR CLOSER.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND POOL STORAGE
 #126; HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES
 NOT INDICATE A DOOR FIRE RATING OR CLOSER.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND PARTITION
 STORAGE #121N; HOWEVER, THE DOOR SCHEDULE (SHEET
 A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER
 FOR DOORS #121N AND #121O.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND PARTITION
 STORAGE #121L; HOWEVER, THE DOOR SCHEDULE (SHEET
 A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER
 FOR DOORS #121L.
  
 SHEET A4.04: DOOR #103C IN CORRIDOR #103C IS MISSING
 PANIC HARDWARE IN DOOR SCHEDULE (SHEET A14.00).
  
 SHEET A4.04: DOOR #104 IN FITNESS #104 IS MISSING PANIC
 HARDWARE IN THE DOOR SCHEDULE (SHEET A14.00). OCCUPANT
 LOAD WILL EXCEED 100 PERSONS IN THE FITNESS ROOM ONCE
 THE APPROPRIATE OCCUPANT LOAD FACTOR IS APPLIED.
 EXITING STAIR #2 AND THEN TRAVELING THROUGH THE HOTEL
 LOBBY EXCEEDS 100 FEET. ADDITIONALLY THIS PATH OF
 TRAVEL IS NOT OBVIOUS AND DIRECT.
  
 LEVEL 100: THE OVERALL LIFE SAFETY EXITING CONCEPT
 NEEDS TO BE COORDINATED WITH THE ELECTRICAL DRAWINGS
 REGARDING THE PLACEMENT OF EXIT SIGNAGE. FOR EXAMPLE,
 SHEET E1-09 SHOWS EXIT SIGNS AT DOORS #100E AND #106B
 LEADING TO THE BAR TERRACE. HOW ARE OCCUPANTS BEING
 DIRECTED TO THE PUBLIC WAY ONCE THEY ENTER THE BAR
 TERRACE AREA? DOOR #100E IS NOT EQUIPPED WITH PANIC
 HARDWARE. ADDITIONALLY AN EXIT SIGN HAS BEEN PLACED AT
 DOOR #105A LEADING BAR OCCUPANTS THROUGH THE KITCHEN
 AREA TO REACH AN EXIT.
  
 SHEET A4.06 (STAIR #3/BOILER ROOM #229/ELECTRICAL
 #224): PER SECTION 28.3.2.1 ALL ROOMS CONTAINING
 HIGH-PRESSURE BOILERS, TRANSFORMERS OR OTHER SERVICE
 EQUIPMENT SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE
 LOCATED DIRECTLY ADJACENT TO EXITS.
  
 SHEET A4.07: LEVEL 200 HAS ASSEMBLY USE ROOMS WITH
 OCCUPANT LOADS EXCEEDING 100 PERSONS. THE EXIT ACCESS
 DOORS FROM THESE ROOMS ARE EQUIPPED WITH PANIC/FIRE
 EXIT HARDWARE; HOWEVER, THE OTHER EXIT ACCESS DOORS ON
 THE FLOOR ARE NOT EQUIPPED WITH PANIC/FIRE EXIT
 HARDWARE SUCH AS DOOR T08, 219, 219A, 221A, 221B, &
 223. PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN
 OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE
 OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY AND THE
 MOST STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF
 EACH OCCUPANCY SHALL APPLY TO THE BUILDING.
  
 SHEET A4.07: THE SERVICE ELEVATOR LOBBY (ALL FLOORS)
 INDICATES AN EXIT ACCESS DOOR (#219) WITH A CARD
 READER. A CARD READER ON THE EGRESS SIDE IS NOT
 PERMITTED AS THIS REQUIRES SPECIAL KNOWLEDGE AND A TOOL
 TO GAIN ACCESS TO AN EXIT.
  
 SHEET A4.07 - DOOR T12 (SUITES #204 & #205): PER
 SECTION 28.3.7.2, IN BUILDINGS PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM,
 EACH HOTEL GUEST ROOM, INCLUDING GUEST SUITES SHALL BE
 SEPARATED FROM OTHER GUEST ROOMS BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM 1/2-HOUR
 FIRE RESISTANCE RATING. DOORS IN THE FIRE BARRIERS
 SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN
 20-MINUTES AND SHALL NOT BE REQUIRED TO BE
 SELF-CLOSING.
  
 SHEET A4.08: PER SECTION 28.3.7.2, IN BUILDINGS
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM, EACH HOTEL GUEST ROOM,
 INCLUDING GUEST SUITES SHALL BE SEPARATED FROM OTHER
 GUEST ROOMS BY WALLS AND FLOORS CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM 1/2-HOUR FIRE RESISTANCE
 RATING. DOORS IN THE FIRE BARRIERS SHALL HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN 20-MINUTES AND SHALL
 NOT BE REQUIRED TO BE SELF-CLOSING. APPLIES TO SEVERAL
 SUITES INCLUDING SUITES, #235, #240, #247 ETC. CHECK
 OTHER FLOORS AS WELL. ALSO NO DOOR TAGS PROVIDED FOR
 DOORS COMMUNICATING BETWEEN TWO ROOMS SUCH AS SUITE
 #240 AND SUITE #247.
  
 SHEET A4.19: EXECUTIVE LOUNGE #1136 APPEARS TO BE AN
 ASSEMBLY USE ROOM; HOWEVER, NO PANIC HARDWARE IS SHOWN
 ON DOORS #1136 OR #1136D.
  
 GENERAL: PROVIDE ADDITIONAL INFORMATION ON THE PROPOSED
 GAS FIRED PIT LOCATED NEAR THE OPEN SKY TERRACE/BAR.
 SHEET E1-05 REFERENCES A GAS FIRED PIT CONTROLLER, BUT
 NO OTHER DESIGN INFORMATION WAS FOUND.
  
 SHEET M1-00: COULD NOT OPEN DRAWING. FILE CONSISTENTLY
 CRASHES COMPUTER.
  
 SHEET M1-04: KITCHEN #105 EXHAUST LOUVER FROM EXHAUST
 FAN #3 (WALL TERMINATION) APPEARS TO BE WITHIN 10 FEET
 OF OPERABLE DOORS #100F, #104A AND #105C (REFERENCE
 SHEET A4.04). PER NFPA 96, SECTION 7.8.3 WALL
 TERMINATIONS. WALL TERMINATIONS SHALL BE ARRANGED WITH
 OR PROVIDED WITH THE FOLLOWING PROPERTIES: (1) THROUGH
 A NONCOMBUSTIBLE WALL WITH A MINIMUM OF 10 FEET OF
 CLEARANCE FROM THE OUTLET TO ADJACENT BUILDINGS,
 PROPERTY LINES, GRADE LEVEL, COMBUSTIBLE CONSTRUCTION,
 ELECTRICAL EQUIPMENT OR LINES, AND THE CLOSEST POINT OF
 ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW AT OR BELOW
 THE PLANE OF THE EXHAUST TERMINATION.
  
 SHEET M1-04: VERIFY THERE ARE NO OPERABLE WINDOWS ABOVE
 KIITCHEN #105 EXHAUST LOUVER FROM FAN #3 (WALL
 TERMINATION). PER NFPA 96 SECTION 7.8.3, THE CLOSEST
 POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW
 ABOVE THE PLANE OF THE EXHAUST TERMINATION SHALL BE A
 MINIMUM OF 10 FEET IN DISTANCE, PLUS 3-INCHES FOR EACH
 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE BEING
 MEASURED FROM THE CENTER OF THE EXHAUST TERMINATION TO
 THE CENTER OF THE AIR INTAKE OR OPERABLE DOOR OR
 WINDOW, AS INDICATED IN FIGURE 7.8.3.
  
 SHEET E1-06: SOUTH DIRECTION INDICATING CHEVRONS ARE
 NEEDED AT THE EXIT SIGN PLACED AT THE CONNECTOR (HOTEL
 TO CONVENTION CENTER). OCCUPANTS WILL NOT BE ABLE TO
 EXIT THROUGH THE CONNECTOR (FROM HOTEL) IF THE FIRE
 SHUTTER ACTIVATES.
  
 SHEET E1-06: NO EXTERIOR EXIT SIGNS DIRECTING POOL
 OCCUPANTS TO EGRESS THROUGH THE CONNECTOR.
  
 SHEET E1-08: ONLY ONE EXIT SIGN PROVIDED IN MAIN
 KITCHEN. ALSO, EXIT SIGNS LOCATED CORRIDOR
 INTERSECTIONS SUCH AS SERVICE CORRIDOR #127 MAY NEED TO
 HAVE TWO EXIT SIGNS IN LIEU OF ONLY ONE SIGN. THE
 CURRENT SIGN PLACEMENT WILL ALLOW OCCUPANTS TRAVELING
 NORTH/SOUTH TO VIEW THE SIGN; HOWEVER, OCCUPANTS
 TRAVELING EAST/WEST WILL NOT BE ABLE TO VIEW THE SIGN.
  
 SHEET E1-09: EXIT SIGN IS ROUTING OCCUPANTS THROUGH THE
 KITCHEN AREA.
  
 SHEET E1-09: NO EXIT SIGNS PROVIDED IN MEETING ROOM
 #101.
  
 SHEET E1-09: EXIT SIGN NOT VIEWABLE FROM LONG PORTION
 OF CORRIDOR #103A.
  
 SHEET E1-16 & E1-17: NO EXIT SIGNS PROVIDED IN ASSEMBLY
 ROOMS. EXIT SIGNS IN THE CORRIDOR ADJACENT TO THE
 ASSEMBLY ROOMS ONLY DIRECT OCCUPANTS TO USE THE CENTER
 EXIT STAIR. ADDITIONAL EXIT SIGNAGE IS NEEDED NOTIFYING
 OCCUPANTS THEY CAN ALSO USE THE SOUTH OR WEST STAIRS AS
 WELL.
  
 SHEET E1-17: EXIT SIGN ALSO NEEDED ON SOUTHEAST SIDE OF
 CORRIDOR DOORS.
  
 SHEET E1-20: NO EXIT SIGNS IN EXECUTIVE LOUNGE #1136.
  
 SHEET E3.00: COULD NOT LOCATE FIREFIGHTERS' SMOKE
 CONTROL PANEL (KEY NOTE 9) IN THE FIRE COMMAND ROOM.
  
 SHEET E4.01: CONFIRM SMOKE CONTROL SYSTEM IS CONNECTED
 TO THE EMERGENCY GENERATOR AND THE LOAD IS ACCOUNTED
 FOR.
  
 SHEET FA0.00: PER LOCAL AHJ POLICY, DUCT SMOKE
 DETECTORS SHALL INITIATE AN ALARM CONDITION IN LIEU OF
 A SUPERVISORY ALARM.
  
 SHEET FA1-01: NO NOTIFICATION APPLIANCES LOCATED IN
 CORRIDOR JUST EAST OF JUNIOR BALLROOM #121.
  
 SHEET FA1-09: ADD FIRE ALARM DEVICE (POSSIBLY TACTILE
 WARNING DEVICES) SHOWN IN GUESTROOM #305 TO THE FIRE
 ALARM LEGEND (B SYMBOLS).
  
 FIRE ALARM: INDICATE ALL GUESTROOMS THAT WILL BE ADA
 COMPLIANT. APPEARS ONLY ROOM #305 HAS BEEN SETUP FOR
 ADA REQUIREMENTS ON ALL FLOORS.
  
 SHEET FA1-12: PLAN NOTE INDICATES TO PROVIDE A FIRE
 ALARM INTERFACE WITH BI-DIRECTIONAL ANTENNA SYSTEM. ARE
 BOTH WIRED FIREFIGHTER PHONE JACKS AND BI-DIRECTIONAL
 AMPLIFIER BEING PROVIDED? IF BOTH ARE NOT INTENDED,
 PROVIDE BI-DIRECTIONAL RADIO AMPLIFIER SYSTEM IN LIEU
 OF WIRED COMMUNICATION SYSTEM (FIREFIGHTER PHONE/JACKS)
 PER FBC SECTION 907.2.13.2.
  
 SHEET FA1-13: CONFIRM SMOKE DETECTORS LOCATED AT THE
 TOP OF THE ELEVATOR SHAFTS ARE TO BE INSTALLED TO
 ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT;
 OTHERWISE, NFPA 72 SECTION 21.3.6 PROHIBITS SMOKE
 DETECTORS FROM BEING INSTALLED IN THESE LOCATIONS.
  
 SHEET FP0-01: FIRE SPRINKLER NOTE #15 - PER NFPA 13
 SECTION 24.2.1.2 PORTIONS OF THE SYSTEM NORMALLY
 SUBJECTED TO SYSTEM WORKING PRESSURES IN EXCESS OF 150
 PSI SHALL BE TESTEDAT A PRESSURE OF 50 PSI IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 FIRE PROTECTION LEVEL 1: DUE TO THE SIZE OF THE FLOOR
 PLATE, PLEASE PROVIDE 2-1/2" FIRE DEPARTMENT HOSE
 VALVES THROUGHOUT THE CORRIDORS.
  
 SHEET FP1-08: COULD NOT LOCATE SPRINKLER PROTECTION FOR
 LARGE OPEN AREA (COMMUNICATING SPACE). SPRINKLERS
 PROTECTING HIGH CEILING OF COMMUNICATING SPACE WILL
 NEED TO BE SUPPLIED AND ZONED FROM THE FIRST FLOOR
 SYSTEM.
  
 SHEET FP1-13: THE SPRINKLERS PROTECTING THE SPACES ON
 THE ROOF LEVEL WILL NEED TO BE SUPPLIED BY A SEPARATE
 SUPERVISED CONTROL VALVE AND FLOW SWITCH SO
 FIREFIGHTERS CAN DISTINGUISH A FIRE ON THE 12TH FLOOR
 FROM A FIRE ON THE ROOF LEVEL.
  
 FIRE PROTECTION: COULD NOT LOCATE ANY HYDRANT FLOW TEST
 DATA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-19 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2014-08-19 Time 15:12 Sent To  
Notes
2014-08-19 15:12:03FUEL GAS PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUES. AUGUST 19/2014
  
 ACTION: FUEL GAS PROVISO
  
 NOTE: FUEL GAS PERMITS ARE A SEPARATE PERMIT AND FEES,
 THE REVIEW WILL BE COMPLETED UNDER THE MASTER SET OF
 PLANS NO OTHER PLANS REQUIRED.
  
 1) SHEET P3.02 THERE ARE (3) AREAS OF CONCERN, THE PIPE
 SIZING IS CORRECT, THERE SEEMS TO BE A DISCREPANCY IN
 THE BTU LOADS:
  
 1A) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE TOTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1B) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1C) THE (3RD) AREA OF INTEREST IS THE RESTAURANT
 KITCHEN, IN TOTALING UP ALL THE TOTAL BTU LOADS FOR THE
 KITCHEN I COME UP WITH 922,000 BTU'S PLEASE RECHECK THE
 TOTAL LOADS, 107.2.1.3 ADDITIONAL INFORMATION,
 DISCREPANCY IN PLANS IN THIS AREA. NOTE THIS WILL
 INCREASE THE TOTAL BTU LOAD FOR THE SYSTEM, BUT NOT
 AFFECT THE PIPE SIZING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS.
 THIS ITEM CAN BE A DEFERRED SUBMITTAL BUT WILL BE
 REQUIRED TO VARIFY NOT OVER LOADING THE CAPACITY OF THE
 FUEL GAS SYSTEM AND FOR SIZING. SUBMIT MANUFACTURE
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC.
 402.2
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-05 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2014-08-05 Time 14:01 Sent To  
Notes
2014-08-05 14:36:24FUEL GAS PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 2ND REVIEW
 DATE: TUES. AUGUST 05/2014
 ACTION: DENIED
  
 NOTE: FUEL GAS PERMITS ARE A SEPARATE PERMIT AND FEES,
 THE REVIEW WILL BE COMPLETED UNDER THE MASTER SET OF
 PLANS NO OTHER PLANS REQUIRED.
  
 1) SHEET P3.02 THERE ARE (3) AREAS OF CONCERN, THE PIPE
 SIZING IS CORRECT, THERE SEEMS TO BE A DISCREPANCY IN
 THE BTU LOADS:
  
 1A) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE TOTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1B) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1C) THE (3RD) AREA OF INTEREST IS THE RESTAURANT
 KITCHEN, IN TOTALING UP ALL THE TOTAL BTU LOADS FOR THE
 KITCHEN I COME UP WITH 922,000 BTU'S PLEASE RECHECK THE
 TOTAL LOADS, 107.2.1.3 ADDITIONAL INFORMATION,
 DISCREPANCY IN PLANS IN THIS AREA. NOTE THIS WILL
 INCREASE THE TOTAL BTU LOAD FOR THE SYSTEM, BUT NOT
 AFFECT THE PIPE SIZING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS.
 THIS ITEM CAN BE A DEFERRED SUBMITTAL BUT WILL BE
 REQUIRED TO VARIFY NOT OVER LOADING THE CAPACITY OF THE
 FUEL GAS SYSTEM AND FOR SIZING. SUBMIT MANUFACTURE
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC.
 402.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-06-20 Cont ID  
Sent By jwitmer Date 2014-06-20 Time 06:27 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 05:31 Sent To  
Notes
2014-06-20 06:27:42FUEL GAS PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 1ST REVIEW
 DATE: FRIDAY JUNE 20/2014
 ACTION: DENIED
  
 NOTE: FUEL GAS PERMITS ARE A SEPARATE PERMIT AND FEES,
 THE REVIEW WILL BE COMPLETED UNDER THE MASTER SET OF
 PLANS NO OTHER PLANS REQUIRED.
  
 1) SHEET P3.02 THERE ARE (3) AREAS OF CONCERN, THE PIPE
 SIZING IS CORRECT, THERE SEEMS TO BE A DISCREPANCY IN
 THE BTU LOADS:
  
 1A) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1B) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1C) THE (3RD) AREA OF INTEREST IS THE RESTAURANT
 KITCHEN, IN TOTALING UP ALL THE TOTAL BTU LOADS FOR THE
 KITCHEN I COME UP WITH 922,000 BTU'S PLEASE RECHECK THE
 TOTAL LOADS, 107.2.1.3 ADDITIONAL INFORMATION,
 DISCREPANCY IN PLANS IN THIS AREA. NOTE THIS WILL
 INCREASE THE TOTAL BTU LOAD FOR THE SYSTEM, BUT NOT
 AFFECT THE PIPE SIZING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS.
 THIS ITEM CAN BE A DEFERRED SUBMITTAL BUT WILL BE
 REQUIRED TO VARIFY NOT OVER LOADING THE CAPACITY OF THE
 FUEL GAS SYSTEM AND FOR SIZING. SUBMIT MANUFACTURE
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC.
 402.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-20 Cont ID  
Sent By cpuell Date 2014-08-20 Time 16:56 Rev Time 0.00
Received By cpuell Date 2014-07-15 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-27 Cont ID  
Sent By cpuell Date 2014-06-27 Time 13:39 Rev Time 0.00
Received By cpuell Date 2014-05-06 Time 09:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-06-21 Cont ID  
Sent By jwitmer Date 2014-06-21 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2014-06-21 Time 15:00 Sent To  
Notes
2014-06-21 15:01:39PAID ON THE FOUNDATION PERMIT .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-04-30 Cont ID  
Sent By hmoser Date 2015-04-30 Time 14:07 Rev Time 0.00
Received By hmoser Date 2015-04-30 Time 14:03 Sent To  
Notes
2015-04-30 14:07:22SHOP DRAWINGS OK FOR FLOOR 3 - 8 HM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-15 Cont ID  
Sent By hmoser Date 2014-08-15 Time 13:51 Rev Time 0.00
Received By hmoser Date 2014-08-13 Time 14:57 Sent To  
Notes
2014-08-15 13:51:37PASS PROVISO
 1) PROVIDE SEPARATE APPLICATION, PLANS, AND PERMIT FOR
 KITCHEN HOOD AND COOLERS.
 2) PROVIDE DRYER MANUFACTURERS INSTALLATION
 INSTRUCTIONS
 AT ROUGH INSPECTION.
 3) PROVIDE A DETAIL ON ROOF TOP EQUIPMENT PER SECTION
 301.12 WIND RESISTANCE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By hmoser Date 2014-06-27 Time 09:31 Rev Time 0.00
Received By hmoser Date 2014-06-25 Time 14:54 Sent To  
Notes
2014-06-27 09:30:12PLAN DENIED
 1) REFER TO SECTION 506.3.12.2 TERMINATION THROUGH AN
 EXTERIOR WALL.
 2010 FBC (M) (FOR HOOD EXHAUST)
 2) REFER TO SECTION 607 DUCT AND TRANSFER OPENING. WHAT
 TYPE OF
 PROTECTION OF DUCT PENETRATION ARE USED FOR MEETING
 ROOMS AND SUITES
 2ED LEVEL AND UP 2010 FBC (M)
 3) PROVIDEE DRYER MANUFACTURERS INSTRUCTIONS WITH THE
 PLANS PER
 SECTION 504.7 COMMERCIAL CLOTHES DRYER. 2010 FBC (M)
 REFER TO DRYER BOOSTER FAN DETAIL.
 4) PLEASE MOVE THE DIESEL FUEL PIPING ISOMETRIC TO THE
 MECHANICAL PLAN
 PER SECTION 1301 FBC (M)
 5) PROVIDE AN ISOMETRIC OF THE GENERATOR EXHAUST ON THE
 MECHANICAL PLAN.
 PER SECTION 510 FBC (M)
 6) PROVIDE STATIC PRESSURE OF AIR CONDITIONING SYSTEMS
 ON THE PLAN.
 PROVID A DETAIL ON THE TYPE OF DUCT REINFORCEMENT
 REQUIRED ON THE PLAN.
 CHAPTER 2 SMACNA
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-19 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2014-08-19 Time 15:13 Sent To  
Notes
2014-08-19 15:17:31P B CONVENTION CENTER HILTON HOTEL PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUESDAY AUGUST 19/ 2014
  
 ACTION: PLUMBING PROVISO
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN
 LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL.
 THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET
 KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT
 ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON
 THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE
 TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE
 # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT
 IDENTIFIED ON THE PLAN.
  
 2) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 INDICATES A
 NEW 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 NOTE 36 SEE SHEET P3.01D FOR THE CONTINUATION OF GREASY
 WASTE. PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE
 CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE
 IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND
 TABLE 1003.5.1.
  
 3) SHEET P1.03 LEVEL 1 AREA Q3. SHEET P1.03 LEVEL 1
 AREA Q3, NOTE# 01 INDICATES A NEW 1,250 GALLON CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, NOTE REFERS TO SHEET
 P4.03 THE GREASE INTERCEPTOR DETAIL. SHEET P3.00
 INDICATES 132 FU DRAINING INTO THE GREASE INTERCEPTOR.
 IF SIZING USING TABLE 1003.3.4.1 THIS TABLE IS TO BE
 USED WHEN THE DESIGN IS FOR HYDRO MECHANICAL GREASE
 INTERCEPTORS. PLEASE PROVIDE THE SIZING CALCULATIONS
 FOR THE CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING
 IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1
 AND TABLE 1003.5.1.
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 4) SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , NO GREASY
 WASTE IS SHOWN ON THE PLANS, NOTE # 15 INDICATES SEE
 P2.04 FOR CONTINUATION. THIS SHEET IS A EQUIPMENT
 SCHEDULE, PLEASE PROVIDE A GREASY WASTE ISOMETRIC OR
 WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH 2010
 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-05 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2014-08-01 Time 07:05 Sent To  
Notes
2014-08-05 15:42:09P B CONVENTION CENTER HILTON HOTEL 1ST PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 2ND REVIEW
 DATE: TUESDAY AUGUST 05/ 2014
  
 ACTION: DENIED
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1-2) COMPLIED.
 3) SHEET P0.01 BASEMENT LEVEL:
  
 3A) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN
 LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL.
 THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET
 KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT
 ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON
 THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE
 TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE
 # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT
 IDENTIFIED ON THE PLAN.
  
 3B)(1)(2)(3)(4) COMPLIED.
  
 3C) COMPLIED.
  
 3D) COMPLIED.
  
 3E) COMPLIED.
  
 3F) FOUND, NO COMMENT.
  
 3G) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P4.02.
 SHEET P0.01 THE BASEMENT LEVEL/ POOL EQUIPMENT ROOM
 NOTE #10 INDICATES THE USE OF A SUMP PUMP TO PUMP THE
 POOL BACK WASH TO SANITARY, THERE IS NO PIT SHOWN ON
 THE PLANS, NOR IS THERE A NOTE PROVIDING DETAILS SIZE
 OF PUMP OR DISCHARGE REQUIRED. SUMPS ARE TO COMPLY WITH
 2010 FBC-P 712.
  
 3H) COMPLIED.
  
 4 ) COMPLIED.
  
 5) SHEET P1.02 LEVEL 1 AREA Q2:
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21
 INDICATES A NEW 750 GALLON CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, NOTE 36 SEE SHEET P3.01D FOR THE
 CONTINUATION OF GREASY WASTE. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR,
 SIZING IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION
 1003.5.1 AND TABLE 1003.5.1.
  
 5C) REVIEWED BY MECHANICAL PLAN REVIEW.NO ACTION
 REQUIRED. SHEET P1.02 LEVEL 1 AREA Q2, NOTES 22-25
 DEALS WITH FUEL LINES, PLEASE NOTE DIRECTLY ABOVE THE
 NEXT STORY IS THE DIESEL EMERGENCY GENERATOR. DIESEL,
 FUEL TANKS AND ASSOCIATED LINES WILL BE REVIEWED BY THE
 MECHANICAL REVIEWER AND INSPECTED BY THE MECHANICAL
 INSPECTOR. DETAIL P4.04.
  
 6) 2ND REQUEST. SHEET P1.03 LEVEL 1 AREA Q3. SHEET
 P1.03 LEVEL 1 AREA Q3, NOTE# 01 INDICATES A NEW 1,250
 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR, NOTE
 REFERS TO SHEET P4.03 THE GREASE INTERCEPTOR DETAIL.
 SHEET P3.00 INDICATES 132 FU DRAINING INTO THE GREASE
 INTERCEPTOR. IF SIZING USING TABLE 1003.3.4.1 THIS
 TABLE IS TO BE USED WHEN THE DESIGN IS FOR HYDRO
 MECHANICAL GREASE INTERCEPTORS.
 PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE IN
 ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND TABLE
 1003.5.1.
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 7) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P2.01 FOR
 THIS AREA. SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 ,
 NO GREASY WASTE IS SHOWN ON THE PLANS, NOTE # 15
 INDICATES SEE P2.04 FOR CONTINUATION. THIS SHEET IS A
 EQUIPMENT SCHEDULE, PLEASE PROVIDE A GREASY WASTE
 ISOMETRIC OR WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE
 THE SIZING CALCULATIONS FOR THE CONCRETE VAULT TYPE
 GREASE INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH
 2010 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED
  
 11) COMPLIED.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-21 Cont ID  
Sent By jwitmer Date 2014-06-21 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 10:14 Sent To  
Notes
2014-06-17 17:59:22P B CONVENTION CENTER HILTON HOTEL 1ST PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 1ST REVIEW
 DATE: TUESDAY JUNE 17TH/ 2014
  
 ACTION: DENIED
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOW-VOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) SHEET A3.00 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES:
  
 2A) HEADING: A-2 OCCUPANCY (BANQUET HALL) GRAND BALL
 ROOM, JR. BALLROOM & MEETING ROOMS ARE FIGURED AT 1/75
 FOR WATER CLOSETS & 1/200 FOR LAVS.
 THE USE OF THESE ROOMS WILL VARY DEPENDING ON THE
 EVENT, EVEN THOUGH THE OCCUPANT LOAD WILL STAY THE SAME
 THE MINIMUM NUMBER OF REQUIRED FIXTURES WILL CHANGE. IF
 IT IS TO BE CONSIDERED A DANCE HALL THE MINIMUM NUMBER
 OF REQUIRED FIXTURES (W.C.) WOULD BE CONSIDERED AT 1/40
 OR IF A EXHIBITION HALL THE WOMEN?S (W. C.) WOULD DROP
 TO 1/65. THE VARIOUS BALLROOMS AND MEETING ROOMS MAY BE
 RENTED OUT BY VARIOUS ORGANIZATIONS WITH DIFFERENT
 EVENT TYPES THIS LOADING FACTOR NEEDS TO BE REFIGURED.
  
 2B) HEADING: POOL AN A4 OCCUPANCY. WITHIN THE CHART THE
 CELL FOR REQUIRED DRINKING FOUNTAIN & SERVICE SINK IS
 STRUCK THROUGH. TABLE 403.1 UNDER THE ASSEMBLY HEADING
 A4 POOLS UNDER THE REQUIRED MINIMUM FIXTURES LIST
 DRINKING FOUNTAINS AND SERVICE SINKS.
  
 2C) HEADING SPORTS BAR & TERRACE A-2 OCCUPANCY
 INDICATES THE LAVS FIGURED AT 1/200, THAT IS FOR
 RESTAURANTS, PLEASE SEE TABLE 403.2 LAVS ARE TO BE
 FIGURED AT 1/40 FOR BARS AND SIMILAR PURPOSES.
  
 2D) HEADING FOR THE FITNESS CENTER IS A BUSINESS
 OCCUPANCY THIS WOULD BE ACCEPTABLE IF THERE IS TO BE A
 INSTRUCTOR THERE ALL THE TIME FOR PERSONAL TRAINING AND
 FITNESS OTHERWISE THIS HEADING SHOULD BE AN A3
 OCCUPANCY FOR A GYM THE OCCUPANT LOAD WOULD CHANGE.
  
 3) SHEET P0.01 BASEMENT LEVEL:
 3A) THE ASSOCIATES CAFETERIA PLUMBING PLAN LIST
 EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL. THE
 PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET KITCHEN
 & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT ON THIS
 LIST ALL FIXTURES & EQUIPMENT ON THIS SHEET ARE LISTED
 WITH A Q. I CAN'T IDENTIFY THE TYPE OF EQUIPMENT FOR
 THE TYPE OR WASTE REQUIRED. NOTE # 10 REFERS TO GREASY
 WASTE FOR THIS SHEET BUT NOT IDENTIFIED ON THE PLAN.
  
 3B)(1) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE DETAIL SHOWS THE 2" DISCHARGE PIPE
 VERTICALLY THEN MAKING A 90 DEGREE TURN BENEATH THE
 SLAB, THERE INSTALLED A FLANGED CHECK VALVE FOR EACH
 PUMP AND A FLANGED GATE VALVE (1) FOR EACH PUMP. PLEASE
 SEE SECTION FBC-P 712.2 FOR REQUIRED COMPLIANCE.
 2010 FBC-PLUMBING 712.2 VALVES REQUIRED.
 A CHECK VALVE AND A FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED IN
 THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE PUMP
 OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. ACCESS
 SHALL BE PROVIDED TO SUCH VALVES. SUCH VALVES SHALL BE
 LOCATED ABOVE THE SUMP COVER REQUIRED BY SECTION 712.1
 OR, WHERE THE DISCHARGE PIPE FROM THE EJECTOR IS BELOW
 GRADE, THE VALVES SHALL BE ACCESSIBLY LOCATED OUTSIDE
 THE SUMP BELOW GRADE IN AN ACCESS PIT WITH A REMOVABLE
 ACCESS COVER.
  
 3B)(2) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE DETAIL OF THE LIFT STATION ALSO DOES NOT
 PROVIDE ANY DETAILS ON THE ACCESS COVER, SIZE,
 THICKNESS OF COVER, TYPE OF MATERIAL OR HOW ACCESS
 COVER WILL BE ATTACHED TO THE FLOOR, OR HOW THE COVER
 WILL BE ACCESSIBLE FOR MAINTENANCE.
 2010 FBC-P 712.3.2 SUMP PIT.
 THE SUMP PIT SHALL BE NOT LESS THAN 18 INCHES (457 MM)
 IN DIAMETER AND 24 INCHES (610 MM) DEEP, UNLESS
 OTHERWISE APPROVED. THE PIT SHALL BE ACCESSIBLE AND
 LOCATED SUCH THAT ALL DRAINAGE FLOWS INTO THE PIT BY
 GRAVITY. THE SUMP PIT SHALL BE CONSTRUCTED OF TILE,
 CONCRETE, STEEL, PLASTIC OR OTHER APPROVED MATERIALS.
 THE PIT BOTTOM SHALL BE SOLID AND PROVIDE PERMANENT
 SUPPORT FOR THE PUMP. THE SUMP PIT SHALL BE FITTED WITH
 A GAS-TIGHT REMOVABLE COVER ADEQUATE TO SUPPORT
 ANTICIPATED LOADS IN THE AREA OF USE.
  
 3B)(3) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE PLUMBING SHEET P0.01 NOR HAS THIS DETAIL
 P4.01 PROVIDED THE TOTAL DRAINAGE FIXTURE UNITS/
 GALLONS PER MINUTE OF WASTE THAT IS TO DRAIN INTO THE
 SANITARY LIFT STATION. PLEASE PROVIDE THIS DATA TO SEE
 THAT THE SPECKED PUMPS WILL MEET THE DEMAND AND PROVIDE
 COMPLIANCE WITH 2010 FBC-P 712.4.2 CAPACITY.
 712.4.2 CAPACITY.
 A SEWAGE PUMP OR SEWAGE EJECTOR SHALL HAVE THE CAPACITY
 AND HEAD FOR THE APPLICATION REQUIREMENTS. PUMPS OR
 EJECTORS THAT RECEIVE THE DISCHARGE OF WATER CLOSETS
 SHALL BE CAPABLE OF HANDLING SPHERICAL SOLIDS WITH A
 DIAMETER OF UP TO AND INCLUDING 2 INCHES (51 MM). OTHER
 PUMPS OR EJECTORS SHALL BE CAPABLE OF HANDLING
 SPHERICAL SOLIDS WITH A DIAMETER OF UP TO AND INCLUDING
 1 INCH (25.4 MM). THE MINIMUM CAPACITY OF A PUMP OR
 EJECTOR BASED ON THE DIAMETER OF THE DISCHARGE PIPE
 SHALL BE IN ACCORDANCE WITH TABLE 712.4.2.
  
 3B)(4) SHEET P1.03 LEVEL 1 AREA Q3 IS WHERE THE LIFT
 STATION TIES INTO THE BUILDING DRAIN, NOTE # 29
 IDENTIFIES THE WASTE LINE. HERE THERE IS 2 ISSUES, THE
 CONNECTION OF THE DISCHARGE PIPING IS TO OCCUR EITHER
 TO THE BUILDING SEWER OR TO A WYE FITTING IN THE
 BUILDING DRAIN. THE CONNECTION TO THE BUILDING DRAIN,
 WYE FITTING MUST BE A MINIMUM OF 10 FEET AWAY FROM
 OTHER PIPE CONNECTIONS OR FIXTURES TO REDUCE THE
 LIKELIHOOD THAT DISCHARGE FROM THE PUMP/ EJECTOR WILL
 INTERFERE WITH THE GRAVITY FLOW IN THE DRAINAGE SYSTEM.
  
 THERE IS A 2 INCH HUB DRAIN CONNECTION WITHIN THE 2"
 DISCHARGE LINE OF THE SUMP/ EJECTOR PIPING SYSTEM, THIS
 2 INCH HUB DRAIN WILL NEED TO TIE INTO BUILDING DRAIN
 LINE DIRECTLY.
  
 THE 2ND ISSUE IS THERE IS ANOTHER 2 INCH HUB DRAIN LINE
 THAT TIES INTO THE BUILDING DRAIN LINE WITHIN THE 10
 FEET WHERE THE SUMP/ EJECTOR PUMP IS TYING INTO THE
 BUILDING DRAIN LINE. WHEN VIEWING WHERE AND HOW THE
 SUMP/ EJECTOR PUMP DISCHARGE INTO THE BUILDING DRAIN IT
 IS DEPICTED AS THE WYE ON ITS SIDE. SEE 2010 FBC-P
 712.3.5 EJECTOR CONNECTION TO THE DRAINAGE SYSTEM.
 PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO
 THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN
 THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM
 THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE
 DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE
 THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING.
  
 3C) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM AT THE THREE COMMERCIAL WASHING
 MACHINES THERE IS NO DRAINAGE, NO TRENCH DRAIN, ONLY A
 3 INCH FLOOR DRAIN. PLEASE PROVIDE THE MANUFACTURERS
 SPECS ON THE COMMERCIAL CLOTHES WASHERS, WILL THEY BE A
 GRAVITY DRAIN OR PUMP, IF PUMP WHAT WILL THE GPM FLOW
 BE? WILL THESE UNITS BE USING A TRENCH DRAIN? SHOW
 COMPLIANCE WITH
 2010 FBC-PLUMBING 406.3 WASTE CONNECTION. TABLE 709.1
 COMMERCIAL FOOTNOTES (A & G).
  
 3D) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE SERVICE
 ELEVATOR B016 THE PLANS DO NOT SHOW A SUMP PUMP DETAIL
 AS DOES THE SERVICE ELEVATOR ST4B NOTE # 9 PROVIDES
 DETAILS ON P4.01.
 2010 FBC-P 1003.4 OIL SEPARATORS REQUIRED. AT REPAIR
 GARAGES, CAR-WASHING FACILITIES, AT FACTORIES WHERE
 OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND IN
 HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE INSTALLED
 INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR FLAMMABLE
 WASTES SHALL BE DISCHARGED BEFORE EMPTYING INTO THE
 BUILDING DRAINAGE SYSTEM OR OTHER POINT OF DISPOSAL.
  
 3E) SHEET P0.01 THE BASEMENT LEVEL NOTE # 2 A/C
 CONDENSATE DRAIN PIPE TO RUN BELOW BASEMENT SLAB, SIZE
 IS NOT PROVIDED, NOTE THIS PIPE IS SHOWN ON THE FLOOR
 PLANS TO DRAIN INTO THE SUMP PIT WHERE AS IT IS NOT
 SHOWN ON THE DETAIL OF THE SUMP PIT, NOTE SURE AT WHAT
 LEVEL IT WILL DISCHARGE INTO THE SUMP PIT.
 THE OTHER ISSUE IS A/C CONDENSATE DUMPING INTO THE CITY
 SEWER. WEST PALM BCH MUNI CODE SEC. 90-126
 PROHIBITIONS & LIMITATIONS OF DISCHARGE (A)GENERALLY.
 USERS SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF
 UNLESS IN ACCORDANCE WITH THIS ARTICLE.
 (5)STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
 3F) FOUND, NO COMMENT.
  
 3G) SHEET P0.01 THE BASEMENT LEVEL/ POOL EQUIPMENT ROOM
 NOTE #10 INDICATES THE USE OF A SUMP PUMP TO PUMP THE
 POOL BACK WASH TO SANITARY, THERE IS NO PIT SHOWN ON
 THE PLANS, NOR IS THERE A NOTE PROVIDING DETAILS SIZE
 OF PUMP OR DISCHARGE REQUIRED. SUMPS ARE TO COMPLY WITH
 2010 FBC-P 712.
  
 3H) NOTE THE POOL EQUIPMENT ROOM IS MISSING A HOSE BIBB
 PER SECTION 2010 FBC-B 424.1.5.9.
  
 4) SHEET P1.01 LEVEL 1 AREA Q1: NOTE OUTSIDE OF THE
 POOL STORAGE EQUIPMENT ROOM THERE IS DEPICTED HOSE BIBB
 PLEASE INDICATE WHERE COMPLIANCE WITH SECTION 2010
 FBC-B 424.1.6.2 RINSE SHOWER CAN BE FOUND?
  
 5) SHEET P1.02 LEVEL 1 AREA Q2:
  
 5A) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 35 INDICATES CAN
 WASH SEE P4.01 CAN WASH DETAIL:
 5A) (1) THE SIDE ELEVATION SECTION AND FRONT ELEVATION,
 THERE ARE QUESTIONS, NOTE # 5 INDICATES THE HOT WATER
 TO THE CAN WASH WILL BE 180 DEGREES BUT NOTE 4
 INDICATES HOSE BIBB NIBCO- SCOTT 760 (W/ CREST WASHER -
 100 DEGREES. THE SIDE VIEW OF THE HOSE BIBBS AND FRONT
 VIEW IT APPEARS THERE WILL BE TO INDEPENDENT HOSE BIBBS
 WHERE WATER CANNOT MIX AS IF IT WERE GOING THROUGH A
 MIXING VALVE, WATER HOTTER THAN 140 DEGREES WILL NEED
 TO COMPLY WITH:
 2010 FBC-P 701.7 CONNECTIONS.
 DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP
 PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE
 SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING
 DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER
 THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST,
 APPROVED COOLING METHODS SHALL BE PROVIDED.
  
 5B) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 INDICATES A
 NEW 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 NOTE 36 SEE SHEET P3.01D FOR THE CONTINUATION OF GREASY
 WASTE. PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE
 CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 SIZING IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION
 1003.5.1 AND TABLE 1003.5.1.
  
 5C) SHEET P1.02 LEVEL 1 AREA Q2, NOTES 22-25 DEALS WITH
 FUEL LINES, PLEASE NOTE DIRECTLY ABOVE THE NEXT STORY
 IS THE DIESEL EMERGENCY GENERATOR. DIESEL, FUEL TANKS
 AND ASSOCIATED LINES WILL BE REVIEWED BY THE MECHANICAL
 REVIEWER AND INSPECTED BY THE MECHANICAL INSPECTOR.
 DETAIL P4.04.
  
 6) SHEET P1.03 LEVEL 1 AREA Q3. SHEET P1.03 LEVEL 1
 AREA Q3, NOTE# 01 INDICATES A NEW 1,250 GALLON CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, NOTE REFERS TO SHEET
 P4.03 THE GREASE INTERCEPTOR DETAIL. SHEET P3.00
 INDICATES 132 FU DRAINING INTO THE GREASE INTERCEPTOR.
 IF SIZING USING TABLE 1003.3.4.1 THIS TABLE IS TO BE
 USED WHEN THE DESIGN IS FOR HYDRO MECHANICAL GREASE
 INTERCEPTORS.
 PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE IN
 ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND TABLE
 1003.5.1.
  
 7) SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , NO GREASY
 WASTE IS SHOWN ON THE PLANS, NOTE # 15 INDICATES SEE
 P2.04 FOR CONTINUATION. THIS SHEET IS A EQUIPMENT
 SCHEDULE, PLEASE PROVIDE A GREASY WASTE ISOMETRIC OR
 WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH 2010
 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 8) SHEET P1.06 NOTE # 15 INDICATES 3 ELECTRIC WATER
 HEATERS FOR USE IN THE KITCHEN THIS IS REVISION 4.5 IS
 THIS PART OF A REVISION FOUND IN THE GAS PLAN REVISION
 3.5 WHERE THERE IS A DISCREPANCY IN THE AMOUNT OF
 BOILERS FOR THE KITCHEN AND BTU'S.
  
 9) SHEET P3.04 RWL # 2. WITH THE 4 " ROOF DRAIN 1106 S.
 F. BEING ADDED TO THE HORIZONTAL LOAD OF2597 SQ FT
 TABLE 1106.3/ 1 % SLOPE . WILL REQUIRE 5 " HORIZONTAL
 DRAIN PIPE. WHEN 4 " RD 739 S F IS ADDED, THE LOAD IS
 3336 S F / 1 % SLOPE, A 6 IN HORIZONTAL PIPE WILL BE
 REQUIRED.
  
 10) SHEET P3.05:
 10A) SHEET P3.05 (MARK UP # 1) THE COMBINED SQUARE
 FOOTAGE OF RWL 15 & 16 = 1748 OVER THE 1652 SQ FT @ 4.5
 IN/ 100 YR RAIN OF 1652 IF USING 1% SLOPE? SLOPE NOT
 INDICATED. 2010 FBC-P TABLE 1106.3.
  
 10B) SHEET P3.05 (MARK UP # 2) THE COMBINED SQUARE
 FOOTAGE OF RWL UNKNOWN NOT MARKED & 17 = 2254 OVER THE
 1652 SQ FT @ 4.5 IN/ 100 YR RAIN OF 1652 IF USING 1%
 SLOPE? SLOPE NOT INDICATED. 2010 FBC-P TABLE 1106.3.
  
 11) SHEET P3.09 (MARK UP # 1) THE 2 X 770 S F= 1540 S F
 + 603 S F+2143 SQ FT, OVER THE ALLOWED 1652 SQ FT @ 4.5
 IN/ 100 YR RAIN OF 1652 IF USING 1% SLOPE? SLOPE NOT
 INDICATED. 2010 FBC-P TABLE 1106.3.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2014-08-22 Cont ID  
Sent By skennedy Date 2014-08-22 Time 11:31 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-08-21 Cont ID  
Sent By skennedy Date 2014-08-21 Time 09:11 Rev Time 0.00
Received By skennedy Date 2014-08-19 Time 14:17 Sent To  
Notes
2014-08-21 09:26:231ST REVIEW; FBC 2010:
  
 THE SIGNATURE REPORT FOR ANDREW P SULLIVAN IS MISSING
 THE FILE NAME FOR THE FOLLOWING PAGES:
 501, 502, 505, 508, 510, 512, 513, 514, 515, 516, 517,
 518, 520, 532, 555, 556, 557, 559, 560, 561, 568, 569,
 570, 573, 574, 576, 580, 582, 585, 586, 591, 592, 594,
 596, & 597.
  
 THE SIGNATURE REPORT FOR STEVEN FELLER IS MISSING THE
 FILE NAME FOR THE FOLLOWING PAGES:
 600, 601, 608, 616, 618-624, 627, 629, 701, 708-714,
 717-721, 733, 734, 737, 740, 756-762, 769, 806,
 817-823, 826, 828, 830, 834, 836-838, 840, 841.
  
 THE SIGNATURE REPORT FOR MICHAEL SPRUCE IS MISSING
 MULTIPLE PAGES:
  
 THE SIGNATURE REPORT FOR THE SURVEYS IS MISSING.
  
 SPOKE TO ALDOPHO REYNA. HE WILL SUPPLY MISSING PEDDS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-20 Cont ID  
Sent By eschneid Date 2014-08-20 Time 11:32 Rev Time 1.50
Received By eschneid Date 2014-08-20 Time 11:32 Sent To  
Notes
2014-08-20 11:32:28PASSED W/PROVISOS
  
 1) PROVISO: THE FOLLOWING CONDITION WAS LISTED IN
 RESOLUTION NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE
 OF THE FIRST BUILDING PERMIT IN ORDER TO ADDRESS
 PERMANENT CONSTRUCTION ACROSS THE PROPERTY LINE. THE
 BUILDING OFFICIAL HAS DETERMINED THAT THE CURRENT
 TEMPORARY CONSTRUCTION EASEMENT WILL SUFFICE FOR
 BUILDING PERMIT TO BE ISSUED; HOWEVER, HE HAS STATED
 THAT THE PERMANENT INSTRUMENT SHALL BE RECORDED IN
 ACCORDANCE WITH THE CONDITION (A. BELOW) PRIOR TO
 ISSUANCE OF THE CO OR TCO, OR THE CONNECTOR BETWEEN THE
 HOTEL AND THE CONVENTION CENTER AND ANY OTHER
 STRUCTURES OR SYSTEMS THAT CROSS THE SHARED PROPERTY
 LINE SHALL BE REMOVED.
  
 A. PRIOR TO THE ISSUANCE OF THE SPECIFIC BUILDING
 PERMIT FOR STRUCTURES OR SYSTEMS THAT CROSS THE SHARED
 PROPERTY LINE WITH THE PALM BEACH COUNTY CONVENTION
 CENTER PARCEL, TO INCLUDE WALKWAY CONNECTIONS, THE
 POOL, POOL DECK, POOL EQUIPMENT, IRRIGATION LINES,
 ETC., THE APPLICANT SHALL RECORD IN THE PUBLIC RECORD A
 UNITY OF TITLE, UNITY OF CONTROL, A RESTRICTIVE
 COVENANT, IN LIEU OF UNITY OF TITLE, OR OTHER
 APPROPRIATE INSTRUMENT, AS APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY, TO ADDRESS THE HOTEL STRUCTURES OR
 SYSTEMS THAT ARE ON THE CONVENTION CENTER PARCEL OR
 WHICH CROSS THE SHARED PROPERTY LINE.
  
 2) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION
 NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE
 FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION;
 HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY
 SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT
 HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE
 ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY.
  
 A. PROVISO: RECORD EASEMENTS IN FAVOR OF THE CITY FOR
 ANY PUBLIC SIDEWALKS OR UTILITIES ON THE HOTEL OR
 PARKING STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS
 WILL BE BASED ON THE AS BUILT SURVEY OF THE SITE.****
  
 B. PROVISO: SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY
 FOR THE RECONFIGURATION OF THE MEDIANS AND INSTALLATION
 OF LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE
 MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE
 SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN
 CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE
 LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). ****THE ENGINEERING SERVICES
 DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO
 ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL
 RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE
 CONSTRUCTION IS FURTHER ALONG.****
  
 3) PROVISO: AS PART OF A PERMIT REVISION PRIOR TO THEIR
 INSTALLATION, PROVIDE SHEET E6.02, THE FIXTURE SHEET
 WHICH SHOWS THE SPECIFIC LIGHTING WHICH WILL BE
 PROVIDED FOR THE ART NICHES. THIS SHEET IS REFERENCED
 AS INCLUDED, BUT IS NOT ON THE ELECTRONIC UPLOAD. ALSO,
 PLEASE INCLUDE THE SPEC SHEET.
  
 4) PROVISO: PRIOR TO THE FIRST INSPECTION, THE
 ARCHITECTURAL FLOOR PLAN SHEETS (A3.** SERIES) WHICH DO
 NOT MATCH THE ELEVATIONS AND SHOW THE SOUTHERN WINDOWS
 SHALL BE EITHER CORRECTED OR REMOVED FROM THE PERMIT
 RECORD DRAWINGS (ANY INFORMATION SHALL BE TRANSFERRED
 TO DRAWINGS WHICH REMAIN) SO THAT THERE IS NO FURTHER
 CONFUSION AS TO WHICH FLOOR PLAN DESIGNS APPLY. THE
 A4.** SERIES FLOOR PLANS SHOW THE INFORMATION CORRECTLY
 AND HAVE BEEN STAMPED BY ZONING.
  
 5) PROVISO: PRIOR TO FIRST INSPECTION, THE DATA ON
 SHEET A0.03 SHALL BE REVISED TO BE CORRECT AND TO MATCH
 THE MINOR AMENDMENT DATA.
  
 6) PROVISO: SHEET A3.01 SHOWS DIFFERENT SQUARE FOOTAGE
 NUMBERS FOR THE PUBLIC AREAS (RESTAURANT, BAR, ETC.)
 THAN ON THE SUBMITTED MINOR AMENDMENT AND THE LIFE
 SAFETY PLAN (SHEET A2.02). ADDITIONALLY, NO SQUARE
 FOOTAGE IS PROVIDED FOR THE MARKET. PRIOR TO FIRST
 INSPECTION, THE PLANS SHALL BE REVISED WITH ALL THE
 NUMBERS SHOWN AND BE CONSISTENT AMONG ALL PLANS.
  
 7) PRIOR TO C.O., SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED FOR THE FOLLOWING ITEMS. THE VALUE OF THE WORK
 SHALL BE SUBMITTED WITH EACH PERMIT AND NOT THE MAIN
 PERMIT. FULL ZONING REVIEW WILL OCCUR UPON SUBMITTAL OF
 THE SEPARATE PERMITS PLANS.
  
 A. SITE FURNITURE THAT WILL BE PERMANENTLY AFFIXED TO
 THE GROUND (EX. TRASH CANS, BENCHES, FIRE PIT, ETC.)
 STAFF HAS REVIEWED THE LOCATIONS OF THE SITE FURNITURE
 AND THEY COMPLY WITH THE APPROVED SITE PLAN.
 B. SITE LIGHTING
 C. BICYCLE RACKS
 D. ENTRY DRIVE - A RIGHT-OF-WAY PERMIT IS REQUIRED FOR
 THE CONNECTION TO FLORIDA AVENUE.
 E. CIVIL PLANS AND RIGHT-OF-WAY PERMIT (THROUGH
 ENGINEERING SERVICES)
 F. SIGNS - SEE COMMENT 10 FOR ADDITIONAL INFORMATION.
 G. POOL, SPA AND POOL DECK H
 H. FENCES/GATES - THE OVERALL HEIGHT OF THE
 FENCE/RETAINING WALL/COLUMNS MAY NOT EXCEED EIGHT (8)
 FEET IN HEIGHT WHEN MEASURED ON THE EXTERIOR SIDE
 (CONVENTION CENTER SIDE) FROM GRADE. DIMENSIONS WERE
 NOT PROVIDED.
 I. CABANAS, INCLUDING THE TOWEL ISSUE CABANA
 J. SUN SHADE
 K. FOUNTAIN WALL
 L. SIDEWALKS, COVERED WALKWAY AND OTHER ITEMS WHOLLY ON
 THE CONVENTION CENTER PARCEL.
 M. IRRIGATION PERMIT
  
 8) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 RESUBMITTAL AND THE FULL ZONING REVIEW OF THE PLANS
 SUBMITTED WITH THE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-08-12 Cont ID  
Sent By eschneid Date 2014-08-12 Time 16:24 Rev Time 8.00
Received By eschneid Date 2014-08-04 Time 08:03 Sent To  
Notes
2014-08-04 08:03:53FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS.
  
 1) THE FOLLOWING CONDITION WAS LISTED IN RESOLUTION NO.
 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE FIRST
 BUILDING PERMIT IN ORDER TO ADDRESS PERMANENT
 CONSTRUCTION ACROSS THE PROPERTY LINE. THE BUILDING
 OFFICIAL HAS DETERMINED THAT THE CURRENT TEMPORARY
 CONSTRUCTION EASEMENT WILL SUFFICE FOR BUILDING PERMIT
 TO BE ISSUED; HOWEVER, HE HAS STATED THAT THE PERMANENT
 INSTRUMENT SHALL BE RECORDED IN ACCORDANCE WITH THE
 CONDITION PRIOR TO ISSUANCE OF THE CO OR TCO, OR THE
 CONNECTOR BETWEEN THE HOTEL AND THE CONVENTION CENTER
 AND ANY OTHER STRUCTURES OR SYSTEMS THAT CROSS THE
 SHARED PROPERTY LINE SHALL BE REMOVED.
  
 A. PRIOR TO THE ISSUANCE OF THE SPECIFIC BUILDING
 PERMIT FOR STRUCTURES OR SYSTEMS THAT CROSS THE SHARED
 PROPERTY LINE WITH THE PALM BEACH COUNTY CONVENTION
 CENTER PARCEL, TO INCLUDE WALKWAY CONNECTIONS, THE
 POOL, POOL DECK, POOL EQUIPMENT, IRRIGATION LINES,
 ETC., THE APPLICANT SHALL RECORD IN THE PUBLIC RECORD A
 UNITY OF TITLE, UNITY OF CONTROL, A RESTRICTIVE
 COVENANT, IN LIEU OF UNITY OF TITLE, OR OTHER
 APPROPRIATE INSTRUMENT, AS APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY, TO ADDRESS THE HOTEL STRUCTURES OR
 SYSTEMS THAT ARE ON THE CONVENTION CENTER PARCEL OR
 WHICH CROSS THE SHARED PROPERTY LINE.
  
 2) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION
 NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE
 FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION;
 HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY
 SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT
 HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE
 ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY.
  
 A. RECORD EASEMENTS IN FAVOR OF THE CITY FOR ANY PUBLIC
 SIDEWALKS OR UTILITIES ON THE HOTEL OR PARKING
 STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS WILL BE
 BASED ON THE AS BUILT SURVEY OF THE SITE.****
  
 B. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE
 RECONFIGURATION OF THE MEDIANS AND INSTALLATION OF
 LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE
 MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE
 SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN
 CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE
 LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). ****THE ENGINEERING SERVICES
 DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO
 ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL
 RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE
 CONSTRUCTION IS FURTHER ALONG.****
  
 3) REPEAT COMMENT: LIGHTING SHALL BE PROVIDED FOR THE
 ART NICHES. WHILE A NOTE WAS ADDED TO THE ENLARGED
 ELEVATIONS REFERRING TO THE ELECTRICAL DRAWINGS FOR THE
 LIGHTING IN THE NICHES, THE REVIEWER IS UNABLE TO
 LOCATE THE LIGHTING ON THE ELECTRICAL DRAWINGS. PLEASE
 CLEARLY IDENTIFY ON WHAT SHEETS THE LIGHTING DETAILS
 ARE LOCATED.
  
 4) PARTIAL REPEAT COMMENT: THE FLOOR PLANS FAIL TO SHOW
 THE NEW GLAZING AND ARCHITECTURAL DETAILS ON THE
 SOUTHERN ELEVATION OF THE TOWER THAT WAS SHOWN ON THE
 MINOR AMENDMENT AND THE REVISED ELEVATIONS. EXAMPLE
 HALLWAY AND END ROOMS DO NOT HAVE WINDOWS.
  
 5) DATA ON SHEET A0.03 SHALL BE REVISED TO MATCH THE
 MINOR AMENDMENT DATA.
  
 6) SHEET A3.01 SHOWS DIFFERENT SQUARE FOOTAGE NUMBERS
 FOR THE PUBLIC AREAS (RESTAURANT, BAR, ETC.) THAT ON
 THE SUBMITTED MINOR AMENDMENT AND THE LIFE SAFETY PLAN
 (SHEET A2.02). ADDITIONALLY, NO SQUARE FOOTAGE IS
 PROVIDED FOR THE MARKET. THE NUMBERS SHALL BE SHOWS AND
 BE CONSISTENT AMONG ALL PLANS.
  
 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING ITEMS. THE VALUE OF THE WORK SHALL BE
 SUBMITTED WITH EACH PERMIT AND NOT THE MAIN PERMIT.
 FULL ZONING REVIEW WILL OCCUR UPON SUBMITTAL OF THE
 SEPARATE PERMITS PLANS.
  
 A. SITE FURNITURE THAT WILL BE PERMANENTLY AFFIXED TO
 THE GROUND (EX. TRASH CANS, BENCHES, FIRE PIT, ETC.)
 STAFF HAS REVIEWED THE LOCATIONS OF THE SITE FURNITURE
 AND THEY COMPLY WITH THE APPROVED SITE PLAN.
 B. SITE LIGHTING
 C. BICYCLE RACKS
 D. ENTRY DRIVE - A RIGHT-OF-WAY PERMIT IS REQUIRED FOR
 THE CONNECTION TO FLORIDA AVENUE.
 E. CIVIL PLANS AND RIGHT-OF-WAY PERMIT (THROUGH
 ENGINEERING SERVICES)
 F. SIGNS - SEE COMMENT 10 FOR ADDITIONAL INFORMATION.
 G. POOL, SPA AND POOL DECK H
 H. FENCES/GATES - THE OVERALL HEIGHT OF THE
 FENCE/RETAINING WALL/COLUMNS MAY NOT EXCEED EIGHT (8)
 FEET IN HEIGHT WHEN MEASURED ON THE EXTERIOR SIDE
 (CONVENTION CENTER SIDE) FROM GRADE. DIMENSIONS WERE
 NOT PROVIDED.
 I. CABANAS, INCLUDING THE TOWEL ISSUE CABANA
 J. SUN SHADE
 K. FOUNTAIN WALL
 L. SIDEWALKS, COVERED WALKWAY AND OTHER ITEMS WHOLLY ON
 THE CONVENTION CENTER PARCEL.
 M. IRRIGATION PERMIT
  
 8) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 RESUBMITTAL AND THE FULL ZONING REVIEW OF THE PLANS
 SUBMITTED WITH THE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
  
2014-07-01 12:59:067/1/14 ZONING SENT TO ES. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-09 Cont ID  
Sent By eschneid Date 2014-06-09 Time 10:23 Rev Time 8.00
Received By eschneid Date 2014-06-09 Time 10:23 Sent To  
Notes
2014-06-09 11:20:28FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS.
  
 1) THE FOLLOWING ITEMS REQUIRED BY RESOLUTION NO.
 329-13 HAVE NOT BEEN MET.
  
 A. PRIOR TO THE ISSUANCE OF THE SPECIFIC BUILDING
 PERMIT FOR STRUCTURES OR SYSTEMS THAT CROSS THE SHARED
 PROPERTY LINE WITH THE PALM BEACH COUNTY CONVENTION
 CENTER PARCEL, TO INCLUDE WALKWAY CONNECTIONS, THE
 POOL, POOL DECK, POOL EQUIPMENT, IRRIGATION LINES,
 ETC., THE APPLICANT SHALL RECORD IN THE PUBLIC RECORD A
 UNITY OF TITLE, UNITY OF CONTROL, A RESTRICTIVE
 COVENANT, IN LIEU OF UNITY OF TITLE, OR OTHER
 APPROPRIATE INSTRUMENT, AS APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY, TO ADDRESS THE HOTEL STRUCTURES OR
 SYSTEMS THAT ARE ON THE CONVENTION CENTER PARCEL OR
 WHICH CROSS THE SHARED PROPERTY LINE.
  
 B. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT
 FOR VERTICAL CONSTRUCTION, THE APPLICANT SHALL:
  
 I. SUBMIT A MINOR AMENDMENT SHOWING THE LOCATIONS OF
 THE STREET LIGHTS AND THE PEDESTRIAN SCALE LIGHTING.
 THE MINOR AMENDMENT SHALL SHOW THAT THE STREET LIGHTS
 MEET THE DOWNTOWN MASTER PLAN SPECIFICATIONS AND SHALL
 SPECIFY AND PROVIDE DETAILS OF THE LIGHTING FIXTURES
 USED FOR THE PEDESTRIAN SCALE LIGHTING. NO LIGHTING
 SHALL CONFLICT WITH PROPOSED LANDSCAPE.
  
 II. RECORD EASEMENTS IN FAVOR OF THE CITY FOR ANY
 PUBLIC SIDEWALKS OR UTILITIES ON THE HOTEL.
  
 III. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE
 RECONFIGURATION OF THE MEDIANS AND INSTALLATION OF
 LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE
 MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE
 SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN
 CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE
 LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD).
  
 IV. THE LANDSCAPE PLANS SHALL BE SUBMITTED AS A
 LANDSCAPE PERMIT AND INCLUDE THE NOTATION AND DETAILS
 THAT ROOT BARRIERS AND STRUCTURAL SOILS SHALL BE USED
 FOR ALL THE OAK TREE PLANTINGS IN SIDEWALK CUTOUTS OR
 WITHIN CLOSE PROXIMITY TO SIDEWALKS TO ENSURE PROPER
 ROOT GROWTH WHILE LIMITING THE POTENTIAL FOR ROOT
 DAMAGE.
  
 2) THE SITE LAYOUT, INCLUDING THE ELEVATIONS, HAS
 CHANGED. SUBMIT A MINOR PLANNED DEVELOPMENT AMENDMENT
 TO THE PLANNING DIVISION FOR REVIEW WHICH SHOWS THE
 PROPOSED CHANGES.
  
 3) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING ITEMS. THE VALUE OF THE WORK SHALL BE
 SUBMITTED WITH EACH PERMIT AND NOT THE MAIN PERMIT.
 FULL ZONING REVIEW WILL OCCUR UPON SUBMITTAL OF THE
 SEPARATE PERMITS PLANS.
  
 A. SITE FURNITURE THAT WILL BE PERMANENTLY AFFIXED TO
 THE GROUND (EX. TRASH CANS, BENCHES, FIRE PIT, ETC.)
 STAFF HAS REVIEWED THE LOCATIONS OF THE SITE FURNITURE
 AND THEY COMPLY WITH THE APPROVED SITE PLAN.
 B. SITE LIGHTING - SEE COMMENT 1)B.I FOR ADDITIONAL
 APPLICATION REQUIREMENTS.
 C. BICYCLE RACKS
 D. LANDSCAPE - LANDSCAPE IN THE RIGHT-OF-WAY REQUIRES A
 RIGHT-OF-WAY PERMIT.
 E. ENTRY DRIVE - A RIGHT-OF-WAY PERMIT IS REQUIRED FOR
 THE CONNECTION TO FLORIDA AVENUE.
 F. CIVIL PLANS AND RIGHT-OF-WAY PERMIT (THROUGH
 ENGINEERING SERVICES)
 G. SIGNS - SEE COMMENT 10 FOR ADDITIONAL INFORMATION.
 H. POOL, SPA AND POOL DECK - SEE COMMENT 1
 I. FENCES/GATES - SEE COMMENT 1 - THE OVERALL HEIGHT OF
 THE FENCE/RETAINING WALL/COLUMNS MAY NOT EXCEED SIX (6)
 FEET IN HEIGHT WHEN MEASURED ON THE EXTERIOR SIDE
 (CONVENTION CENTER SIDE) FROM GRADE. DIMENSIONS WERE
 NOT PROVIDED. SHEET LS505 AND LS506. (LS101H)
 J. CABANAS - SEE COMMENT 1
 K. SUN SHADE
 L. FOUNTAIN WALL - SEE COMMENT 1
 M. SIDEWALKS, COVERED WALKWAY AND OTHER ITEMS WHOLLY ON
 THE CONVENTION CENTER PARCEL.
  
 4) THE ELEVATION DRAWINGS TO NOT SHOW THE FULL
 CONVENTION CENTER CONNECTOR (APPEARS THAT PLAN LAYERS
 WHERE NOT TURNED ON).
  
 5) THE SOUTH FACADE FOR FLOORS 3-10, AT THE END OF THE
 CORRIDOR, MAY NOT BE A BLANK FACADE. THE CITY
 COMMISSION APPROVED PLANS SHOW WINDOWS AND A WALL THAT
 IS NOT FLAT AT THIS LOCATION.
  
 6) THERE IS SOME EQUIPMENT SHOWN PROJECTING ABOVE THE
 ROOF PARAPET ON THE ELEVATIONS. PER THE CITYPLACE DRI,
 ALL ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.
  
 7) THE DETAIL TAG FOR THE POOL GATE D1 LS509 (NORTHERN
 GATE) LEADS TO THE DETAIL ON SHEET LS509 WHICH DOES NOT
 MATCH THE GATE IN PLAN VIEW ON SHEET LS103.
  
 8) ADD THE NOTE TO THE EAST ELEVATION REFERENCING THAT
 THERE WILL BE ART LOCATED IN THE NICHES, PER THE PLANS
 APPROVED BY RESOLUTION NO. 329-13.
  
 9) LIGHTING SHALL BE PROVIDED FOR THE ART NICHES.
  
 10) CHANGE ALL REFERENCE TO THE CORNER SIGN (RELOCATED
 MONUMENT SIGN) TO STATE THE APPROVED SIZE FROM
 RESOLUTION NO. 329-11, AS STATED BELOW:
  
 A. THE CORNER SIGN SHALL CONTAIN A MAXIMUM TOTAL OF 240
 SQUARE FEET IN AREA (120 SQUARE FEET MAXIMUM PER FACE).
  
 B. THE CORNER SIGN SHALL BE NO GREATER THAN TWELVE (12)
 FEET IN HEIGHT AND TEN (10) FEET IN WIDTH.
  
 11) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 RESUBMITTAL AND THE FULL ZONING REVIEW OF THE PLANS
 SUBMITTED WITH THE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  