Plan Review Details - Permit 14050102
Plan Review Stops For Permit 14050102
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-07-11 Cont ID  
Sent By jwitmer Date 2014-07-11 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-07-11 Time 11:43 Sent To  
Notes
2014-07-11 12:15:06BUILDING PLAN REVIEW
 PERMIT: 14050102
 ADD: 205 TAMARIND AVE
 CONT: TBD
 TEL: (561)494-1061
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 11/2014
 FOUNTAIN & CLOCK TOWER REVIEW
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-3.01:
 1A) THE PLANS INDICATE A PREMANUFACTURED VERTICAL WATER
 FOUNTAIN FEATURE & TROUGH. THERE IS NO DETAIL
 INFORMATION AT THIS TIME. NOTED THAT SHOP DRAWINGS ARE
 TO BE SUBMITTED AND REVIEWED BY THE DESIGNER OF RECORD
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) THE PLANS INDICATE THE VERTICAL FOUNTAIN FEATURE
 WALL TO HAVE STAINLESS STEEL CABLES IN A DIAMOND SHAPE
 PATTERN, THERE IS NO DETAIL INFORMATION AT THIS TIME.
 NOTED THAT SHOP DRAWINGS ARE TO BE SUBMITTED AND
 REVIEWED BY THE DESIGNER OF RECORD BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1C) THE PLANS INDICATE THE EXISTING FOUNTAIN EQUIPMENT
 IS TO BE REUSED/ REPAIRED AND COORDINATION WITH THE
 FOUNTAIN MANUFACTURER.
 THERE IS NO DETAIL INFORMATION AT THIS TIME. NOTED THAT
 SHOP DRAWINGS ARE TO BE SUBMITTED AND REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1D) PLEASE PROVIDE DIMENSIONS TO THE ACCESS PANEL THAT
 IS PART OF THE CLOCK TOWER, AND PROVIDES ACCESS TO THE
 FOUNTAIN PUMPS. PLEASE PROVIDE ADDITIONAL INFORMATION
 HOW COMPLIANCE WITH 2010 FBC-PUMBING 202- READY ACCESS.
 THAT WHICH ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO
 BE DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR
 MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND
 WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR
 SIMILAR DEVICE.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 10:54 Rev Time 0.00
Received By dhayes Date 2014-07-14 Time 10:54 Sent To  
Notes
2014-07-14 10:58:17DATE: 7/14/2014
 PROJECT: SEABOARD TRAIN STATION IMPROVEMENTS.
 PERMIT#: 14050102
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
  
 2) ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 3) EACH MOTOR USED IN A CONTINUOUS DUTY APPLICATION AND
 RATED MORE THAN 1 HP SHALL BE PROTECTED AGAINST
 OVERLOAD BY ONE OF THE MEANS IN 430.32(A)(1) THROUGH
 (A)(4).
  
 4) THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN THE NEC 680.2 AND 680.50
  
 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 11:23 Rev Time 0.00
Received By dhayes Date   Time 10:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-11 Cont ID  
Sent By jwitmer Date 2014-07-11 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2014-07-11 Time 11:43 Sent To  
Notes
2014-07-11 12:28:11BUILDING PLAN REVIEW
 PERMIT: 14050102
 ADD: 205 TAMARIND AVE
 CONT: TBD
 TEL: (561)494-1061
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 11/2014
 FOUNTAIN & CLOCK TOWER REVIEW
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-3.01:
 1A) THE PLANS INDICATE A PREMANUFACTURED VERTICAL WATER
 FOUNTAIN FEATURE & TROUGH. THERE IS NO DETAIL
 INFORMATION AT THIS TIME. NOTED THAT SHOP DRAWINGS ARE
 TO BE SUBMITTED AND REVIEWED BY THE DESIGNER OF RECORD
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) THE PLANS INDICATE THE VERTICAL FOUNTAIN FEATURE
 WALL TO HAVE STAINLESS STEEL CABLES IN A DIAMOND SHAPE
 PATTERN, THERE IS NO DETAIL INFORMATION AT THIS TIME.
 NOTED THAT SHOP DRAWINGS ARE TO BE SUBMITTED AND
 REVIEWED BY THE DESIGNER OF RECORD BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1C) THE PLANS INDICATE THE EXISTING FOUNTAIN EQUIPMENT
 IS TO BE REUSED/ REPAIRED AND COORDINATION WITH THE
 FOUNTAIN MANUFACTURER.
 THERE IS NO DETAIL INFORMATION AT THIS TIME. NOTED THAT
 SHOP DRAWINGS ARE TO BE SUBMITTED AND REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1D) PLEASE PROVIDE DIMENSIONS TO THE ACCESS PANEL THAT
 IS PART OF THE CLOCK TOWER, AND PROVIDES ACCESS TO THE
 FOUNTAIN PUMPS. PLEASE PROVIDE ADDITIONAL INFORMATION
 HOW COMPLIANCE WITH 2010 FBC-PUMBING 202- READY ACCESS.
 THAT WHICH ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO
 BE DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR
 MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND
 WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR
 SIMILAR DEVICE.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-14 Cont ID  
Sent By aaponte Date 2014-07-10 Time 12:09 Rev Time 0.00
Received By aaponte Date 2014-07-10 Time 12:09 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy