Plan Review Details - Permit 14050005
Plan Review Stops For Permit 14050005
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2014-07-18 Cont ID  
Sent By dhayes Date 2014-07-18 Time 08:19 Rev Time 0.00
Received By dhayes Date 2014-07-17 Time 06:50 Sent To  
Notes
2014-07-18 08:20:24SEE REVISION #14070608 FOR REVIEW NOTES. DAH
2014-07-18 06:51:16INCOMING SENT TO D.HAYES'S DESK. JW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 15:58 Rev Time 0.00
Received By dhayes Date 2014-06-03 Time 15:58 Sent To  
Notes
2014-06-03 16:25:05ELECTRICAL PROVISO
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) LIGHTING CONTROLS MANDATORY. LIGHTING SYSTEMS SHALL
 BE PROVIDED WITH CONTROLS AS REQUIRED IN. OCCUPANCY
 SENSORS REQUIRED IN ACCORDANCE WITH FBC-ENERGY CODE
 SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. PROVIDE
 AUTOMATIC LIGHTING SHUTOFF.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By dhayes Date 2014-05-01 Time 07:57 Rev Time 0.00
Received By dhayes Date 2014-05-01 Time 16:57 Sent To  
Notes
2014-05-01 16:59:07PROVISO: 2010 FBC 505.2.2 COMPLIANCE REQUIRED.
  
 DAVID HAYES ELECTRICAL PLANS EXAMINER. 561-805-6717,
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By pleduc Date 2014-05-28 Time   Rev Time 0.00
Received By pleduc Date 2014-05-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-06-24 Cont ID  
Sent By jwitmer Date 2014-06-24 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2014-06-24 Time 16:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 15:49 Sent To  
Notes
2014-05-05 16:17:46FUEL GAS/ PLUMBING PLAN REVIEW
 PERMIT: 14050005
 ADD: 1741 PALM BEACH LAKES F05
 CONT: TBD
 TEL: (561) 401-1349
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 05/2014
 ACTION: DENIED
  
 1) THE P3 SHEET INDICATES LP GAS TO THE FOOD COURT
 AREA, PLEASE SEE ONLY NATURAL GAS IS BEING SUPPLIED TO
 THE FOOD COURT. THE ONLY PLACE LP GAS IS ON SITE IS TO
 THE GENERATORS. PLEASE CORRECT PLANS AND TABLES FOR
 NATURAL GAS. 2010 FBC-FUEL GAS TABLE 402.4 (1-22),
 NATURAL GAS.
  
 2) THIS SHEET UNDER THE HEADING OF NOTES INDICATES THE
 USE OF POLYEHTYLENE PIPE OF SCHEDULE 40 GALVANIZED
 METAL PIPE. THE PLAN ALSO INDICATES 12 FEET TO BE RUN
 IN THE WALL. PLEASE SEE 2010 FUEL GAS SECTION 404.3
 PIPING IN CONCEALED LOCATIONS. PORTIONS OF A PIPING
 SYSTEM INSTALLED IN CONCEALED LOCATIONS SHALL NOT HAVE
 UNIONS, TUBING FITTINGS, RIGHT AND LEFT COUPLINGS,
 BUSHINGS, COMPRESSION COUPLINGS AND SWING JOINTS MADE
 BY COMBINATIONS OF FITTINGS.
 EXCEPTIONS:
 1. TUBING JOINED BY BRAZING.
 2. FITTINGS LISTED FOR USE IN CONCEALED LOCATIONS.
  
 3) THE P3 NOTE 2 INDICATES SCHEDULE 40 METAL PIPE OR
 POLYEHTYLENE PLASTIC PIPE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" ORITS EQUIVALENT
 BE USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 4
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-24 Cont ID  
Sent By jwitmer Date 2014-06-24 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2014-06-19 Time 11:13 Sent To  
Notes
2014-06-23 11:13:34RESUBMITTAL SENT TO JIM WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-05-28 Time 15:48 Rev Time 0.00
Received By dhayes Date 2014-05-01 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-13 Cont ID  
Sent By hmoser Date 2014-05-13 Time 15:15 Rev Time 0.00
Received By hmoser Date 2014-05-13 Time 14:50 Sent To  
Notes
2014-05-13 15:15:10 
  
  
 1) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PROVIDE SIZE AND TYPE ANCHOR USED TO TIE DOWN CONDENSER
 STAND TO ROOF. ( BY ENGINEER ) AT FIRST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-24 Cont ID  
Sent By jwitmer Date 2014-06-24 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2014-06-24 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 12:00 Sent To  
Notes
2014-05-05 15:49:41PLUMBING PLAN REVIEW
 PERMIT: 14050005
 ADD: 1741 PALM BEACH LAKES F05
 CONT: TBD
 TEL: (561) 401-1349
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 05/2014
 ACTION: DENIED
  
 1) SHEET P1.0 THE FLOOR DRAINS INDICATE WITH RESEAL BUT
 DO NOT INDICATE THE RESEAL IS A TRAP PRIMER.
 2010 FBC-P 1002.2 DESIGN OF TRAPS.
 FIXTURE TRAPS SHALL BE SELF-SCOURING. FIXTURE TRAPS
 SHALL NOT HAVE INTERIOR PARTITIONS, EXCEPT WHERE SUCH
 TRAPS ARE INTEGRAL WITH THE FIXTURE OR WHERE SUCH TRAPS
 ARE CONSTRUCTED OF AN APPROVED MATERIAL THAT IS
 RESISTANT TO CORROSION AND DEGRADATION. SLIP JOINTS
 SHALL BE MADE WITH AN APPROVED ELASTOMERIC GASKET AND
 SHALL BE INSTALLED ONLY ON THE TRAP INLET, TRAP OUTLET
 AND WITHIN THE TRAP SEAL.
 2010 FBC-P 1002.3 PROHIBITED TRAPS.
 THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS
 THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEA.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop POLICE POLICE
Rev No 1 Status N Date 2014-05-14 Cont ID  
Sent By eschneid Date 2014-05-14 Time 13:29 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2014-05-14 13:30:52CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY'S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: "THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS."
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A 'SAFE' CLIMATE
 WITHIN A BUILT ENVIRONMENT" RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS "QUALITY OF LIFE." A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER'S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
  
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-14 Cont ID  
Sent By eschneid Date 2014-05-14 Time 14:35 Rev Time 0.25
Received By eschneid Date 2014-05-14 Time 11:54 Sent To  
Notes
2014-05-06 14:42:025/6/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved