| Plan Review Stops For Permit 14041100 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2014-05-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-17 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-05-17 10:21:57 | SCOTT ALEF ADDED ADDRESS. | | 2014-04-30 17:35:19 | SENT E-MAIL TO SCOTT ALEF REQUESTING ADDRESS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2016-01-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-01-22 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-22 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-03-12 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-03-12 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2015-02-25 17:41:34 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-05-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-05-24 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-05-24 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-05-15 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-15 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-15 |
Time |
14:05 |
Sent To |
AD |
|
| Notes |
| 2014-05-15 16:22:54 | APPROVED THE ELECTRICAL REVIEW AND RETURNED TO BIN C5 | | | FOR ADDRESS REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-02-02 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-02-02 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-05-05 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2016-02-02 16:24:35 | THIS WAS APPROVED BY ELECTRIC BACK ON MAY 5TH, 2015 BUT | | | THE RESULTS WERE INADVERTENTLY ENTERED IN THE B | | | SLOT.THIS WAS BROUGHT TO MY ATTENTION TODAY BY STEVE | | | AND THUS CORRECTED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2016-02-17 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-02-17 |
Time |
|
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
2016-02-17 |
Time |
|
Sent To |
I |
|
| Notes |
| 2016-02-17 16:56:57 | PRE-CONSTRUCTION MEETING REQUIRED WITH CITY OF WPB | | | ENGINEERING CONSTRUCTION COORDINATOR/ ROW DEPARTMENT | | | WITH 72 HOUR NOTICE. | | | | | | CALL 811 BEFORE DIG. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2015-03-16 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-03-16 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-03-16 |
Time |
11:23 |
Sent To |
Z |
|
| Notes |
| 2015-03-16 13:21:32 | PUBLIC WORKS / ENGINEERING | | | | | | 1. PLEASE PROVIDE A SIGNED AND SEALED STATEMENT FROM | | | THE LANDSCAPE ARCHITECT VERIFYING THAT THE PLANTING OF | | | FAKAHATCHEE GRASS ON TOP OF THE EXFILTRATION TRENCH | | | WILL NOT RESULT IN INCREASED MAINTENANCE COSTS | | | RESULTING FROM ROOTS EXTENDING INTO THE TRENCH BEDDING | | | AND PIPE. | | | | | | 2. PLEASE PROVIDE A SIGNED AND SEALED STATEMENT FROM | | | THE ENGINEER OF RECORD THAT THE PLACEMENT OF | | | FAKAHATCHEE GRASS ON WITHIN THE PROPOSED SWALE WILL NOT | | | DIMINISH THE CAPACITY OF THE PROPOSED SWALE. ACCORDING | | | TO IFAS: FLORIDA TRIPSACUM (FAKAHATCHEE GRASS) FORMS A | | | DENSE, UPRIGHT CLUMP OF 3-FOOTLONG LEAVES . THIS GRASS | | | ATTAINS A HEIGHT OF ABOUT 2 TO 3 FEET AND SPREADS TO | | | FORM A CLUMP UP TO 6-FEETWIDE. | | | | | | 3. PLEASE PROVIDE A SIGNED AND SEALED STATEMENT FROM | | | THE LANDSCAPE ARCHITECT VERIFYING THAT THE PLACEMENT OF | | | A CABBAGE PALM DIRECTLY ON TOP OF THE EXISTING 18-INCH | | | WILL NOT RESULT IN INCREASED MAINTENANCE COSTS | | | RESULTING FROM THE ROOTS EXTENDING INTO THE PIPE. | | | | | | KELLY CRANFORD, PE | | | CITY LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1098 (OFFICE) | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2014-07-25 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2014-07-25 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2014-07-25 |
Time |
16:02 |
Sent To |
I |
|
| Notes |
| 2014-07-25 16:03:48 | ENGINEERING DEPARTMENT COMMENTS | | | ONLY THE PROPOSED IMPROVEMENTS ON CITY PROPERTY HAVE | | | BEEN REVIEWED. IMPROVEMENTS WITHIN CONGRESS AVENUE | | | RIGHT-OF-WAY WILL NEED TO BE APPROVED BY PALM BEACH | | | COUNTY. | | | | | | 1. THE SUBMITTED PLANS WERE NOT SIGNED OR SEALED. | | | PLEASE SUBMIT SIGNED AND SEALED PLANS FOR FINAL | | | APPROVAL. | | | | | | 2. PLEASE DEMONSTRATE THAT THE PROJECT WILL PROVIDE | | | ADEQUATE DRAINAGE AND STORMWATER MANAGEMENT. COMPLIANCE | | | WITH CHAPTER 40E-4 WILL DEMONSTRATE COMPLIANCE WITH | | | THIS PROVISION [SECTIONS 90-201, 94-35(C )(11), AND | | | 94-307]. | | | | | | 3. PLEASE PROVIDE DETAILS FOR THE DUMPSTER ENCLOSURE | | | SHOWN ON SHEET C3-1. ALSO INDICATE HOW THE CITY | | | SANITATION TRUCKS WILL ACCESS THE DUMPSTERS. | | | | | | 4. PLEASE REVISE THE LANDSCAPE PLANS TO THEY DO NOT | | | CONFLICT WITH THE SITE DRAINAGE. LANDSCAPING IS | | | PROPOSED ON TOP OF THE PROPOSED SWALE, ON TOP OF THE | | | EXFILTRATION TRENCH, AND SURROUNDING ONE OF THE CATCH | | | BASINS. UTILIZE ROOT BARRIERS AS APPROPRIATE TO ENSURE | | | THE LANDSCAPE PLANTING?S ROOTS WILL NOT ENTER THE | | | STORMWATER TRENCH. | | | | | | 5. PLEASE PROVIDE SIZING CALCULATIONS FOR THE RIP-RAP. | | | | | | 6. PLEASE CLARIFY WHETHER THE EXFILTRATION TRENCH ALONG | | | THE WEST SIDE OF CONGRESS WILL BE REPLACED OR RESTORED. | | | CONFLICTING NOTES ARE ON SHEETS C3-1, C1-12, AND C5-6. | | | | | | 7. PLEASE SHOW THE CONGRESS AVENUE RIGHT-OF-WAY LINE ON | | | THE LANDSCAPE PLANS. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | ENGINEERING & PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561)484-1098 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-01-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-01-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-01-27 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-03-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-03-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-03-02 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2015-03-03 10:26:06 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | NFPA 10, CHAPTER 6 | | | | | | 6.4.1 FIRE EXTINGUISHERS WITH CLASS C RATINGS SHALL BE | | | REQUIRED WHERE ENERGIZED ELECTRICAL EQUIPMENT CAN BE | | | ENCOUNTERED. | | | | | | 6.4.2 THE REQUIREMENTS IN 6.4.1 SHALL INCLUDE SITUATION | | | WHERE FIRE EITHER DIRECTLY INVOLVES OR SURROUNDS | | | ELECTRICAL EQUIPMENT. | | | | | | TWO CLASS C EXTINGUISHERS ARE REQUIRED TO BE INSTALLED | | | AT THIS LOCATION IN AN EASILY IDENTIFIABLE AND VISIBLE | | | LOCATION. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-02-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-02-18 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-12-29 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-03-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-12-29 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-03-27 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2015-02-25 17:41:16 | RE-SUBMITTAL SENT TO C5 BIN FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-07-28 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-05-01 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2014-05-01 06:32:30 | INCOMING C05 . JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2016-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-01-25 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-01-25 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-23 |
Time |
05:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-23 |
Time |
04:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-03-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-03-14 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-03-14 |
Time |
06:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-01-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-01-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-01-27 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-12-29 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-03-27 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-05-14 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-05-06 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2014-05-14 09:44:53 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.14.2014 | | | PERMIT NO.: 14041100 | | | ADDRESS: 1009 BANYAN BOULEVARD ? LOCATION OF WORK IS ON | | | CONGRESS AVENUE, NORTH OF EMBASSY DRIVE | | | CONTRACTOR/CONTACT: JOHN CAIRNES | | | TELEPHONE NO.: 561.371.5695 | | | SCOPE OF REVIEW: SURFACE WATER PUMP STATION. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. APPROVAL FOR RELOCATION OF THE BUS SHELTER / STOP | | | SHALL BE OBTAINED FROM PALM TRAN PRIOR TO ANY | | | REMOVAL/RELOCATION. | | | | | | 2. A TREE ALTERATION PERMIT SHALL BE OBTAINED FROM THE | | | CITY?S DEVELOPMENT SERVICES DEPARTMENT ? PLANNING | | | DIVISION, PRIOR TO THE REMOVAL OR RELOCATION OF ANY | | | EXISTING TREES. | | | | | | 3. A SIDEWALK CONNECTION SHOULD BE PROVIDED FROM THE | | | BUS SHELTER / STOP TO THE ADJACENT WALKWAY. | | | | | | 4. NO PLAN WAS SHOWN FOR THE STRIPING OF CONGRESS | | | AVENUE UPON COMPLETION OF THE MILLING AND RESURFACING. | | | | | | 5. A SEPARATE APPLICATION SHALL BE SUBMITTED FOR A | | | LANDSCAPE PERMIT. THE PERMIT SHALL BE ACCOMPANIED BY | | | TWO (2) SETS OF SIGNED/SEALED LANDSCAPE PLANS, AS WELL | | | AS A CERTIFIED COST ESTIMATE FOR MATERIALS AND LABOR. | | | THE LANDSCAPE PLANS INCLUDED IN THE PLANS SUBMITTED | | | WERE NOT SIGNED/SEALED. | | | | | | 6. ALL LANDSCAPING SHALL BE IRRIGATED WITH A PERMANENT | | | IRRIGATION SYSTEM. A SEPARATE PERMIT SHALL BE OBTAINED. | | | | | | 7. SHEET L1-1 INDICATES THAT THE PLANT LIST IS ON L1-3; | | | THE PLANT LIST IS ACTUALLY ON L1-1 ITSELF. | | | | | | 8. PLEASE PROVIDE A LARGER SPECIFICATION FOR THE SILVER | | | BUTTONWOOD HEDGE SO AS TO CREATE A MORE IMMEDIATE | | | IMPACT ON SCREENING OF THE FACILITY. | | | | | | 9. WHY USE OF RED MULCH? IS THIS A CITY SPECIFIED | | | MATERIAL? IS IT CONSISTENT WITH OTHER PLANTINGS IN THE | | | AREA? | | | | | | 10. IS THERE A WAY TO CONSIDER NARROWING THE DRIVEWAYS | | | INTO AND OUT OF THE FENCED AREA? IF THE OPENINGS WERE | | | NARROWER, THE OPENING IN THE LANDSCAPING WOULD BE | | | REDUCED AND ADDITIONAL PLANTINGS COULD BE INSTALLED TO | | | BETTER SCREEN THE COMPOUND. | | | | | | 11. IS THERE A WAY TO DROP THE ELEVATION OF THE | | | DISCHARGE PIPE BETWEEN THE FENCE AND THE RIGHT-OF-WAY | | | LINE SO AS TO ALLOW FOR THE PLANTING OF ADDITIONAL | | | PALMS/TREES IN FRONT OF THE FENCE. ADDITIONAL PLANTING | | | WOULD HELP TO SCREEN THE TRASH RAKES THAT EXTEND | | | UPWARD. | | | | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|