Plan Review Details - Permit 14041097
Plan Review Stops For Permit 14041097
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-06-09 Cont ID  
Sent By JGOMEZ Date 2014-05-29 Time 14:44 Rev Time 0.00
Received By jgomez Date 2014-06-09 Time 08:39 Sent To  
Notes
2014-06-09 09:51:35ROOFING UNDER PERMIT #14050271. JG.
2014-05-20 15:45:52 
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By albarran Date 2014-05-20 Time 15:46 Rev Time 0.00
Received By albarran Date 2014-05-20 Time 14:35 Sent To M
Notes
2014-05-20 15:46:42ELECTRICAL PROVISOS FOR PERMIT 14041097
 1. AS PER NEC300.5(B), THE INTERIOR OF AN UNDERGROUND
 (OR IN CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET
 LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE
 LISTED ACCORDINGLY.
 2. AS PER NEC 314.27, BOXES IN THE CEILING FOR HANGING
 LUMINARIES SHALL BE DESIGNED TO SUPPORT MINIMUM 50#.
 3. NEC 210.52, HAS SPECIFIC OUTLET SPACING
 REQUIREMENTS.
 4. SEE SUGGESTED 3WAY SWITCHING AS MARKED ON PLANS
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-08 Cont ID  
Sent By jgomez Date 2014-07-08 Time 14:31 Rev Time 0.00
Received By jgomez Date 2014-07-03 Time 10:10 Sent To  
Notes
2014-07-03 10:11:18INCOMING SENT TO J. GOMEZ . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-09 Cont ID  
Sent By jgomez Date 2014-06-09 Time 09:52 Rev Time 0.00
Received By jgomez Date 2014-04-30 Time 07:13 Sent To  
Notes
2014-05-01 07:15:23INCOMING R13 . JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-07-08 Cont ID  
Sent By jgomez Date 2014-07-08 Time 14:02 Rev Time 0.00
Received By jgomez Date 2014-07-08 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-06-09 Cont ID  
Sent By jgomez Date 2014-06-09 Time 10:31 Rev Time 0.00
Received By jgomez Date 2014-06-09 Time 10:31 Sent To  
Notes
2014-06-09 10:44:37RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- BALANCED RETURN AIR IN MASTER BEDROOM: REVISE SIZE
 OF TRANSFER GRILL TO COMPLY WITH EXCEPTION #2 OF SEC.
 M1602.4. "THE TRANSFER GRILL SHALL USE 50 SQUARE INCHES
 (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR)". ALL THE
 SUPPLY AIR INTO THE MASTER SUITE SHALL BE INCLUDED.
 ACCORDING TO PLAN ON SHEET A3 ALL THE SUPPLY AIR TO THE
 MASTER BEDROOM IS 377 CFM. THEREFORE, NEED A TRANSFER
 GRILL WITH AT LEAST 188.5 SQUARE INCHES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-29 Cont ID  
Sent By albarran Date 2014-05-29 Time 12:48 Rev Time 0.00
Received By jsaez Date 2014-05-29 Time 12:48 Sent To B
Notes
2014-05-29 12:56:19FAILED MECHANICAL REVIEW AS FOLLOWS:
 1. PROVIDE SEPARATE A/C PLANS
 2. DETAIL OF AHU & CU & EXHAUST FANS
 3. SUBMIT LOAD CALCULATIONS
  
 THESE PLANS WERE REVIEWED BY JOEY SAEZ, MECHANICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
  
 FEEL FREE TO CONTACT ME DIRECTLY AT: [email protected]
  
  
 RETURNED TO BIN R13

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-09 Cont ID  
Sent By jgomez Date 2014-06-09 Time 09:51 Rev Time 0.00
Received By jgomez Date 2014-06-09 Time 09:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-06-09 Cont ID  
Sent By jgomez Date 2014-06-09 Time 12:53 Rev Time 0.00
Received By jgomez Date 2014-06-09 Time 12:53 Sent To  
Notes
2014-06-09 12:54:15ROOFING UNDER PERMIT #14050271. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-23 Cont ID  
Sent By llouie Date 2014-05-23 Time 14:59 Rev Time 0.00
Received By jroach Date 2014-05-23 Time 14:59 Sent To B
Notes
2014-05-23 15:40:28PROVISO
  
 1. PRIOR TO FINAL INSPECTION, SEPARATE LANDSCAPE AND
 IRRIGATION PERMIT APPLICATIONS SHALL BE SUBMITTED AND
 APPROVED. LANDSCAPING SHALL CONFORM TO THE MINIMUM
 REQUIREMENTS OF ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
2014-05-06 14:40:395/6/14