| Plan Review Stops For Permit 14041097 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
JGOMEZ |
Date |
2014-05-29 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2014-06-09 09:51:35 | ROOFING UNDER PERMIT #14050271. JG. | | 2014-05-20 15:45:52 | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-05-20 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-20 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-20 |
Time |
14:35 |
Sent To |
M |
|
| Notes |
| 2014-05-20 15:46:42 | ELECTRICAL PROVISOS FOR PERMIT 14041097 | | | 1. AS PER NEC300.5(B), THE INTERIOR OF AN UNDERGROUND | | | (OR IN CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET | | | LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE | | | LISTED ACCORDINGLY. | | | 2. AS PER NEC 314.27, BOXES IN THE CEILING FOR HANGING | | | LUMINARIES SHALL BE DESIGNED TO SUPPORT MINIMUM 50#. | | | 3. NEC 210.52, HAS SPECIFIC OUTLET SPACING | | | REQUIREMENTS. | | | 4. SEE SUGGESTED 3WAY SWITCHING AS MARKED ON PLANS | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-08 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-03 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2014-07-03 10:11:18 | INCOMING SENT TO J. GOMEZ . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-04-30 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2014-05-01 07:15:23 | INCOMING R13 . JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-07-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-08 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-08 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2014-06-09 10:44:37 | RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- BALANCED RETURN AIR IN MASTER BEDROOM: REVISE SIZE | | | OF TRANSFER GRILL TO COMPLY WITH EXCEPTION #2 OF SEC. | | | M1602.4. "THE TRANSFER GRILL SHALL USE 50 SQUARE INCHES | | | (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR)". ALL THE | | | SUPPLY AIR INTO THE MASTER SUITE SHALL BE INCLUDED. | | | ACCORDING TO PLAN ON SHEET A3 ALL THE SUPPLY AIR TO THE | | | MASTER BEDROOM IS 377 CFM. THEREFORE, NEED A TRANSFER | | | GRILL WITH AT LEAST 188.5 SQUARE INCHES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-29 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
jsaez |
Date |
2014-05-29 |
Time |
12:48 |
Sent To |
B |
|
| Notes |
| 2014-05-29 12:56:19 | FAILED MECHANICAL REVIEW AS FOLLOWS: | | | 1. PROVIDE SEPARATE A/C PLANS | | | 2. DETAIL OF AHU & CU & EXHAUST FANS | | | 3. SUBMIT LOAD CALCULATIONS | | | | | | THESE PLANS WERE REVIEWED BY JOEY SAEZ, MECHANICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | | | | FEEL FREE TO CONTACT ME DIRECTLY AT: [email protected] | | | | | | | | | RETURNED TO BIN R13 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2014-06-09 12:54:15 | ROOFING UNDER PERMIT #14050271. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-05-23 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2014-05-23 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-05-23 |
Time |
14:59 |
Sent To |
B |
|
| Notes |
| 2014-05-23 15:40:28 | PROVISO | | | | | | 1. PRIOR TO FINAL INSPECTION, SEPARATE LANDSCAPE AND | | | IRRIGATION PERMIT APPLICATIONS SHALL BE SUBMITTED AND | | | APPROVED. LANDSCAPING SHALL CONFORM TO THE MINIMUM | | | REQUIREMENTS OF ARTICLE XIV OF THE CITY?S ZONING AND | | | LAND DEVELOPMENT REGULATIONS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT [email protected] OR (561) 822-1448. | | 2014-05-06 14:40:39 | 5/6/14 |
|
|