Plan Review Details - Permit 14041087
Plan Review Stops For Permit 14041087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By jwitmer Date 2014-06-20 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 16:23 Sent To  
Notes
2014-05-05 16:32:59 
 BUILDING PLAN REVIEW
 PERMIT: 14041087
 ADD: 1200 S FLAGLER DR # 501
 CONT: LOWES HOME CENTER
 TEL: (561)721-5611
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 5/2014
 ACTION: DENIED
  
 1) PLANS INDICATE A FLOOR REPLACEMENT BUT DO NOT
 PROVIDE THE TYPE OF MATERIALS TO BE INSTALLED NOR THE
 TYPE OF FLOOR INSULATION TO BE INSTALLED..
  
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 1C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 -------------------------------------------------------
 --------------------
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-24 Cont ID  
Sent By dhayes Date 2014-06-24 Time 15:45 Rev Time 0.00
Received By dhayes Date 2014-06-24 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-20 Cont ID  
Sent By albarran Date 2014-05-20 Time 14:07 Rev Time 0.00
Received By albarran Date 2014-05-20 Time 13:18 Sent To  
Notes
2014-05-20 14:09:18ELECTRICAL DEFICIENCIES FOR PERMIT 14041087
  
 1. MINIMUM OUTLET PLACEMENT TO COMPLY WITH NEC 210.52
 IS AS MARKED ON SUBMITTED PLANS
 2. AS PER NEC 210.8, ALL KITCHEN OUTLETS SHALL BE GFCI
 PROTECTED.
 3. ALL NEW OUTLET BOXES SHALL COMPLY WITH MINIMUM DEPTH
 REQUIREMENTS OF NEC 314.21.
 4. ALL NEW OUTLETS SHALL COMPLY W/NEC 406.11,
 TAMPER-RESISTANT.
 5. ALL NEW CIRCUITS SHALL COMPLY W/NEC 210.12,
 ARC-FAULT.
 6. PROVIDE A PANEL SCHEDULE
 7. SUBMIT AN ELECTRICAL RISER DIAGRAM W/LOAD CALCS.
 8. IF SERVICE IS BEING UPGRADED, PROVIDE A SITE PLAN
 INDICATING WHERE THE METER AND MAIN DISCONNECT ARE.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-24 Cont ID  
Sent By dhayes Date 2014-06-24 Time 15:45 Rev Time 0.00
Received By dhayes Date 2014-06-18 Time 19:07 Sent To  
Notes
2014-06-18 19:07:44INCOMING SENT TO JW. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-20 Cont ID  
Sent By albarran Date 2014-05-20 Time 14:09 Rev Time 0.00
Received By albarran Date 2014-05-01 Time 05:49 Sent To  
Notes
2014-05-20 14:11:24SMALL DENIED BIN "L"
2014-05-01 05:51:38INCOMING B04. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By jwitmer Date 2014-06-20 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 15:45 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 16:23 Sent To  
Notes
2014-05-05 16:40:43PLUMBING PLAN REVIEW
 PERMIT: 14041087
 ADD: 1200 S FLAGLER DR # 501
 CONT: LOWES HOME CENTER
 TEL: (561)721-5611
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 5/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIW CRITERIA FOR BUILDINGS.
 FLOOR PLAN SHOWING THE SINK LOCATION, EXISSTING AND NEW
 LOCATION, LOCATION OF EXISTING STACK, SIZE OF TRAP AND
 DISTANCE FROM FIXTURE TRAP TO VENT, 2010 FBC-P TABLE
 906.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  