Plan Review Details - Permit 14041074
Plan Review Stops For Permit 14041074
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-10 Cont ID  
Sent By shill Date 2014-07-10 Time 17:22 Rev Time 0.00
Received By shill Date 2014-07-10 Time 17:22 Sent To  
Notes
2014-07-10 17:25:02****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 NON IMPACT DOOR OK PER RB
  
 INSPECTOR TO VERIFY THAT EXISTING SHUTTERS INSTALLED
 UNDER PERMIT #98090486 ARE IN OPERABLE CONDITION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-10 Cont ID  
Sent By shill Date 2014-06-10 Time 08:21 Rev Time 0.00
Received By shill Date 2014-06-10 Time 08:21 Sent To  
Notes
2014-06-10 08:29:53****CORRECTIONS****
 ****COURTESY PLAN REVIEW (SUBMITTED VIA EMAIL)****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT PROTECTION REQUIRED, FBC 1609.1.4.
  
 EXITS CANNOT BE BLOCKED BY IMPACT PROTECTION
 (SHUTTERS), SEE FBC 1003.6, MEANS OF EGRESS CONTINUITY.
  
 2ND REVIEW, RESPONSE IS THAT CUSTOMER HAS EXISTING
 SHUTTERS. PROVIDE A LIFE SAFETY PLAN TO SHOW EXIT DOORS
 BEING BLOCKED BY SHUTTERS AND PROVIDE A PERMIT NUMBER
 FOR THE SHUTTERS. THERE IS NO PROVISION IN THE FBC FOR
 SHUTTERS OVER MEANS OF EGRESS DOORS. THIS IS CONSIDERED
 BY THE BUILDING OFFICIAL ON A CASE BY CASE BASIS.
  
 2. ON THE PRODUCT APPROVAL, INDICATE OPTIONS PROPOSED.
 THIS APPEARS TO BE AN ENTRY/EXIT DOOR, SO AN ACCESSIBLE
 THRESHOLD IS REQUIRED FBC 2010 ACCESSIBILITY 404.2.5.
  
 2ND REVIEW, RESUB SHEET NOTED WHERE THIS INFORMATION
 CAN BE FOUND. PLEASE CIRCLE ON THE PRODUCT APPROVAL AS
 REQUESTED FOR BOTH PLAN REVIEW AND INSPECTION PURPOSES.
  
 3. EITHER INDICATE ON THE PRODUCT APPROVAL WHERE PANIC
 OR FIRE EXIT HARDWARE IS PROPOSED OR PROVIDE A LIFE
 SAFETY PLAN WHICH SHOWS WHY THIS WOULD NOT BE REQUIRED,
 FBC 1008.1.10.
  
 RESUBMITTAL FORM STATES THAT PANIC DEVICES ARE NOT
 NEEDED AS DOORS REMAIN OPEN. PROVIDE A LIFE SAFETY PLAN
 AS REQUESTED. THERE IS AN EXCEPTION IN THE CODE TO THE
 PANIC DEVICES, BUT THE EXCEPTION HAS REQUIREMENTS WHICH
 NEED TO BE SHOWN.
  
 NEW COMMENT:
  
 PLEASE RESUBMIT THROUGH THE FRONT COUNTER. AN EMAIL WAS
 SENT TO TWO DIFFERENT PEOPLE, NEITHER OF WHOM WERE THE
 PLAN REVIEWER WHO FAILED THE PLAN. NEW OR ADDITIONAL
 DOCUMENTS ARE REQUIRED. AT TIMES, SOME ITEMS MAY BE
 SUBMITTED VIA EMAIL UPON REQUEST UNDER CERTAIN
 CIRCUMSTANCES.
  
 IT IS SUGGESTED THAT YOU MAKE A RECORDS RESEARCH
 REQUEST FOR THE FLOOR PLAN OF THIS SPACE, PREFERABLY
 THE LIFE SAFETY PLAN. ON THIS PLAN, INDICATE LOCATION
 OF PROPOSED WORK. THIS PORTION MAY BE SENT VIA EMAIL TO
 ME FOR PRELIMINARY REVIEW.
  
 YOU CAN MAKE A PUBLIC RECORDS RESEARCH REQUEST TO:
 [email protected] OR [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-17 Time 14:24 Rev Time 0.00
Received By shill Date 2014-05-15 Time 15:21 Sent To  
Notes
2014-05-01 17:50:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT PROTECTION REQUIRED, FBC 1609.1.4.
  
 EXITS CANNOT BE BLOCKED BY IMPACT PROTECTION
 (SHUTTERS), SEE FBC 1003.6, MEANS OF EGRESS CONTINUITY.
  
 2. ON THE PRODUCT APPROVAL, INDICATE OPTIONS PROPOSED.
 THIS APPEARS TO BE AN ENTRY/EXIT DOOR, SO AN ACCESSIBLE
 THRESHOLD IS REQUIRED FBC 2010 ACCESSIBILITY 404.2.5.
  
 3. EITHER INDICATE ON THE PRODUCT APPROVAL WHERE PANIC
 OR FIRE EXIT HARDWARE IS PROPOSED OR PROVIDE A LIFE
 SAFETY PLAN WHICH SHOWS WHY THIS WOULD NOT BE REQUIRED,
 FBC 1008.1.10.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-16 Cont ID  
Sent By pleduc Date 2014-05-16 Time   Rev Time 0.00
Received By pleduc Date 2014-05-16 Time 14:40 Sent To B
Notes
2014-05-16 14:51:27THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 THE DOOR LOCK SHALL BE SELF-INDICATING, OPEN/LOCKED.
  
 INSTALL PANIC HARDWARE IF APPLICABLE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-10 Cont ID  
Sent By shill Date 2014-06-10 Time 08:30 Rev Time 0.00
Received By shill Date 2014-06-10 Time 08:20 Sent To  
Notes
2014-06-10 08:20:46RESUB VIA FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-17 Cont ID  
Sent By shill Date 2014-05-17 Time 14:24 Rev Time 0.00
Received By shill Date 2014-05-15 Time   Sent To B
Notes
2014-05-17 14:24:48THIS WAS SUBMITTED IN RESPONSE TO A PLAN REVIEW WHICH
 WAS ENTERED IN ERROR. DISCUSSED WITH CONTRACTOR.
  
2014-05-16 09:25:51ROUTED TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-30 Cont ID  
Sent By shill Date 2014-05-30 Time 10:23 Rev Time 0.00
Received By skennedy Date 2014-04-30 Time 12:55 Sent To  
Notes
2014-05-30 09:38:10F- FILED UNDER SMALL "S"
 APPLICANT CONTACTED BY E-MAIL 5/30/14
2014-05-17 14:24:065/17 TO ZONING
  
2014-05-15 15:49:455/15 TO FIRE
  
2014-04-30 12:56:09MISC 1
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-30 Cont ID  
Sent By aaponte Date 2014-05-30 Time 09:36 Rev Time 0.00
Received By aaponte Date 2014-05-30 Time 09:36 Sent To  
Notes
2014-05-30 09:36:57EXISTING DOOR SET BACK FROM ROW LINE, AND MINIMUM
 SETBACK REQUIREMENT.
2014-05-19 15:54:085/19/14 ZONING RECEIVED, SENT TO AA. SG