Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:43 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 06:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-13 Cont ID  
Sent By skennedy Date 2014-05-13 Time 07:37 Rev Time 0.00
Received By skennedy Date 2014-05-13 Time 07:22 Sent To  
Notes
2014-05-13 07:45:041ST REVIEW:
  
 PROVIDE DESIGN WIND LOAD REQUIREMENTS USING ASCE-7
 STANDARD AS OUTLINED IN STEP 1 ON SHEET 3 OF 10 IN NOA
 13-1021.07.
  
 PROVIDE A SITE SPECIFIC DRAWING WITH DIMENSIONS TO
 DETERMINE THE HEIGHT, WIDTH, AND MULLION SPACING FOR
 THE SYSTEM.
  
 THE PHOTOGRAPH PROVIDED INDICATE MULLION SPACING OF
 39". THE HIGHLIGHTED OR SLECTED DESIGN IS BASED ON 32"
 NOMINAL WIDTH.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:43 Rev Time 0.00
Received By skennedy Date 2014-05-29 Time 12:38 Sent To  
Notes
2014-05-30 12:38:55RESUBMITTAL SENT TO STEVE KENNEDY'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-13 Cont ID  
Sent By skennedy Date 2014-05-13 Time 07:45 Rev Time 0.00
Received By skennedy Date 2014-04-30 Time 09:56 Sent To  
Notes
2014-04-30 09:56:39ROUTED TO BLDG $5000 & UNDER