| 2014-04-30 13:42:26 | PLUMBING PLAN REVIEW |
| | PERMIT: 14040925 |
| | ADD: 4158 LAKE TAHOE CIR |
| | CONT: LSCI, INC. |
| | TEL: (727)571-4141 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 30/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE DETAIL SHEET FOR THE WATER HEATER IS MISSING THE |
| | INFORMATION ON THE REQUIREMENTS FOR DISCHARGE PIPING. |
| | 2010 FBC-P 504.6 REQUIREMENTS FOR DISCHARGE PIPING. |
| | THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE, |
| | TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL: |
| | |
| | 1. NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM. |
| | |
| | 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| | ROOM AS THE WATER HEATER. |
| | |
| | 3. NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF |
| | THE VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE |
| | AIR GAP. |
| | |
| | 4. SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT |
| | TO PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT. |
| | |
| | 5. DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER |
| | HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE |
| | OUT-DOORS. |
| | |
| | 6. DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL |
| | INJURY OR STRUCTURAL DAMAGE. |
| | |
| | 7. DISCHARGE TO A TERMINATION POINT THAT IS READILY |
| | OBSERVABLE BY THE BUILDING OCCUPANTS. |
| | |
| | 8. NOT BE TRAPPED. |
| | |
| | 9. BE INSTALLED SO AS TO FLOW BY GRAVITY. |
| | |
| | 10. NOT TERMINATE MORE THAN 6 INCHES (152 MM) ABOVE THE |
| | FLOOR OR WASTE RECEPTOR. |
| | |
| | 11. NOT HAVE A THREADED CONNECTION AT THE END OF SUCH |
| | PIPING. |
| | |
| | 12. NOT HAVE VALVES OR TEE FITTINGS. |
| | |
| | 13. BE CONSTRUCTED OF THOSE MATERIALS LISTED IN SECTION |
| | 605.4 OR MATERIALS TESTED, RATED AND APPROVED FOR SUCH |
| | USE IN ACCORDANCE WITH ASME A112.4.1. |
| | |
| | SECTION 612 |
| | SOLAR SYSTEMS |
| | |
| | 2) 2010 FBC-R M612.1 SOLAR SYSTEMS. |
| | THE CONSTRUCTION, INSTALLATION, ALTERATIONS AND REPAIR |
| | OF SYSTEMS, EQUIPMENT AND APPLIANCES INTENDED TO |
| | UTILIZE SOLAR ENERGY FOR SPACE HEATING OR COOLING, |
| | DOMESTIC HOT WATER HEATING, SWIMMING POOL HEATING OR |
| | PROCESS HEATING SHALL BE IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL . |
| | M2301.5 BACKFLOW PROTECTION. |
| | CONNECTIONS FROM THE POTABLE WATER SUPPLY TO SOLAR |
| | SYSTEMS SHALL COMPLY WITH SECTION P2902.5.5. |
| | P2902.5.5 SOLAR SYSTEMS. |
| | THE POTABLE WATER SUPPLY TO A SOLAR SYSTEM SHALL BE |
| | EQUIPPED WITH A BACKFLOW PREVENTER WITH INTERMEDIATE |
| | ATMOSPHERIC VENT COMPLYING WITH ASSE 1012 OR A REDUCED |
| | PRESSURE PRINCIPLE BACKFLOW PREVENTER COMPLYING WITH |
| | ASSE 1013. WHERE CHEMICALS ARE USED, THE POTABLE WATER |
| | SUPPLY SHALL BE PROTECTED BY A REDUCED PRESSURE |
| | PRINCIPLE BACKFLOW PREVENTER. |
| | |
| | EXCEPTION: WHERE ALL SOLAR SYSTEM PIPING IS A PART OF |
| | THE POTABLE WATER DISTRIBUTION SYSTEM, IN ACCORDANCE |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | PLUMBING, AND ALL COMPONENTS OF THE PIPING SYSTEM ARE |
| | LISTED FOR POTABLE WATER USE, CROSS-CONNECTION |
| | PROTECTION MEASURES SHALL NOT BE REQUIRED. |