Plan Review Details - Permit 14040925
Plan Review Stops For Permit 14040925
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-12 Cont ID  
Sent By jwitmer Date 2014-06-12 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2014-06-12 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-30 Cont ID  
Sent By jwitmer Date 2014-04-30 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2014-04-30 Time 12:00 Sent To  
Notes
2014-04-30 12:25:57BUILDING PLAN REVIEW
 PERMIT: 14040925
 ADD: 4158 LAKE TAHOE CIR
 CONT: LSCI, INC.
 TEL: (727)571-4141
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 30/ 2014
 ACTION: DENIED
  
 1) THE PLANS SHEET A.1.3-10 HAVE A GENERIC ROOF DETAIL
 THAR INDICATES THAT IT SHOULD NOT BE INSTALLED IN A
 ROOF ZONE 3. PLEASE PROVIDE A ROOFING PLAN TO SCALE TO
 SHOW THE SIZE OF THE ROOF AND WHERE THE INSTALATION OF
 THE SOLAR COLECTOR WILL BE LOCATED. PLEASE IDENTIFY THE
 ROOF ZONES 1, 2 & 3.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL...
  
 2) THROUGHOUT THE PLAN IT MAKES REFERANCE TO OPTIONS
 FROM THE TYPE OF FASTENER, TO THE FRAMING DETAILS, TO
 THE TYPE OF MOUNTING BRAKETS TO THE TILT KIT DECK
 ANCHOR. THE PLANS NEED TO BE SPECIFIC IN NATURE AS TO
 THE INSTALATION, CIRCLE OR IDENTIFY EACH TYPE OF OPTION
 SO THEY PLAN WILL BE SPECIFIC TO THIS INSTALATION.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) THE WEBSITE LISTED ON THE PLANS FOR VERIFICATION OF
 THE WIND LOAD CALCULATIONS WOULD NOT OPEN, CALCULATIONS
 COULD NOT BE VERIFIED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-12 Cont ID  
Sent By jwitmer Date 2014-06-12 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2014-06-12 Time 11:58 Sent To  
Notes
2014-06-12 11:58:39SENT TO J.W. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-30 Cont ID  
Sent By jwitmer Date 2014-04-30 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2014-04-25 Time 18:06 Sent To  
Notes
2014-04-28 18:06:28SENT TO PLUMBING SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-12 Cont ID  
Sent By jwitmer Date 2014-06-12 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2014-06-12 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-30 Cont ID  
Sent By jwitmer Date 2014-04-30 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2014-04-30 Time 12:00 Sent To  
Notes
2014-04-30 13:42:26PLUMBING PLAN REVIEW
 PERMIT: 14040925
 ADD: 4158 LAKE TAHOE CIR
 CONT: LSCI, INC.
 TEL: (727)571-4141
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 30/ 2014
 ACTION: DENIED
  
 1) THE DETAIL SHEET FOR THE WATER HEATER IS MISSING THE
 INFORMATION ON THE REQUIREMENTS FOR DISCHARGE PIPING.
 2010 FBC-P 504.6 REQUIREMENTS FOR DISCHARGE PIPING.
 THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL:
  
 1. NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM.
  
 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER.
  
 3. NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF
 THE VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE
 AIR GAP.
  
 4. SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT
 TO PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT.
  
 5. DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUT-DOORS.
  
 6. DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY OR STRUCTURAL DAMAGE.
  
 7. DISCHARGE TO A TERMINATION POINT THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS.
  
 8. NOT BE TRAPPED.
  
 9. BE INSTALLED SO AS TO FLOW BY GRAVITY.
  
 10. NOT TERMINATE MORE THAN 6 INCHES (152 MM) ABOVE THE
 FLOOR OR WASTE RECEPTOR.
  
 11. NOT HAVE A THREADED CONNECTION AT THE END OF SUCH
 PIPING.
  
 12. NOT HAVE VALVES OR TEE FITTINGS.
  
 13. BE CONSTRUCTED OF THOSE MATERIALS LISTED IN SECTION
 605.4 OR MATERIALS TESTED, RATED AND APPROVED FOR SUCH
 USE IN ACCORDANCE WITH ASME A112.4.1.
  
 SECTION 612
 SOLAR SYSTEMS
  
 2) 2010 FBC-R M612.1 SOLAR SYSTEMS.
 THE CONSTRUCTION, INSTALLATION, ALTERATIONS AND REPAIR
 OF SYSTEMS, EQUIPMENT AND APPLIANCES INTENDED TO
 UTILIZE SOLAR ENERGY FOR SPACE HEATING OR COOLING,
 DOMESTIC HOT WATER HEATING, SWIMMING POOL HEATING OR
 PROCESS HEATING SHALL BE IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL .
 M2301.5 BACKFLOW PROTECTION.
 CONNECTIONS FROM THE POTABLE WATER SUPPLY TO SOLAR
 SYSTEMS SHALL COMPLY WITH SECTION P2902.5.5.
 P2902.5.5 SOLAR SYSTEMS.
 THE POTABLE WATER SUPPLY TO A SOLAR SYSTEM SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH INTERMEDIATE
 ATMOSPHERIC VENT COMPLYING WITH ASSE 1012 OR A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTER COMPLYING WITH
 ASSE 1013. WHERE CHEMICALS ARE USED, THE POTABLE WATER
 SUPPLY SHALL BE PROTECTED BY A REDUCED PRESSURE
 PRINCIPLE BACKFLOW PREVENTER.
  
 EXCEPTION: WHERE ALL SOLAR SYSTEM PIPING IS A PART OF
 THE POTABLE WATER DISTRIBUTION SYSTEM, IN ACCORDANCE
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 PLUMBING, AND ALL COMPONENTS OF THE PIPING SYSTEM ARE
 LISTED FOR POTABLE WATER USE, CROSS-CONNECTION
 PROTECTION MEASURES SHALL NOT BE REQUIRED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  