| Plan Review Stops For Permit 14040899 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-04-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-25 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-25 |
Time |
08:29 |
Sent To |
I |
|
| Notes |
| 2014-04-25 08:57:14 | HAVING NOT INDICATED THE LOCATION OF THE AIR HANDLING | | | UNIT, I MADE MENTION OF THE FOLLOWING REQUIREMENTS: | | | HVAC EQUIPMENT INSTALLED IN ATTICS ARE SUBJECT TO | | | SPECIFIC NEC | | | REQUIREMENTS: | | | NEC 110.33(B) REQUIRES A PERMANENT LADDER TO THE ATTIC | | | NEC 210.63 REQUIRES A SERVICE OUTLET INSIDE THE ATTIC | | | NEC 210.70 REQUIRES THAT THERE BE A LIGHT INSIDE THE | | | ATTIC & | | | NEC 410.11 REQUIRES THAT THE LIGHT HAVE A GUARD AROUND | | | THE LAMP | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-04-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-25 |
Time |
08:57 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
PC |
|
| Notes |
| 2014-04-25 09:06:08 | PRINTED PINK CARD AND CALLED RAY. SENT TO OUT RACK "D" | | 2014-04-25 08:20:28 | ROUTED TO ELECTRICAL LESS THAN $5000 |
|
|
|