Plan Review Details - Permit 14040884
Plan Review Stops For Permit 14040884
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-21 Cont ID  
Sent By jwitmer Date 2014-05-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2014-05-21 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 06:04 Sent To  
Notes
2014-05-02 06:57:38BUILDING/ PLUMBING PLAN REVIEW
 REVISION: 14040884
 PERMIT: 13120972
 ADD: 5802 S DIXIE HWY.
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI.
 ACTION: DENIED
  
 1) THIS IS A EXSPANSION OF A INTERIOR- DEMO PERMIT TO
 INCLUDE THE REBUILDING OF A RESTROOM. PLEASE PROVIDE
 TYPE OF OCCUPANCY THIS UNIT IS TO BE CONSIDERED. NOTE
 APPROXIMATELY 1386 SQ FT.
 BUSSINESS 1386 SQ FT/ 100= 14 OCCUPANT LOAD
 MERCANTILE 1386 SQ FT / 30 = 47 OCCUPANT LOAD
 RESTARAUNT 1386 SQ FT/ 15= 93 OCCUPANT LOAD
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
  
 2A) THE PLANS INDICATE THE NEW RESTROOM PLUMBING GOING
 INTO A EXISTING FIRE WALL, THE TYPE OF OCCUPANCY NEEDS
 TO BE DECLARED TO KNOW WHAT RATING THE FIRE WALL NEEDS
 TO BE RATED. PLEASE CONFIRM IF THIS IS A PARTYWALL
 SHARED BY BOTH TENANTS OR IF THERE ARE TO TENANT
 SEPERATION WALLS BACK TO BACK. IF THIS IS A SHARED
 PARTYWALL THE PLUMBING WILL NOT BE ABLE TO BE PUT INTHE
 PARTY WALL. FOR A TENANT SEPERATION WALL PLEASE SEE
 2010 FBC-B TABLES 602 EXTERIOR WALLS FIRE SEPERATION
 DISTANCE AND TABLE 706.4 FIRE WALL RATINGS DETERMINED
 BY OCCUPANCY GROUP. NOTE IF THE PLUMBING IS INSET INTO
 THE FIRE WALL, WHAT TYPE OF MATERIAL IS GOING TO BE
 USED TO BE INSTALLED TO COVER THE PIPES AND HAVE THE
 SAME RATING AS THE FIRE WALL.
  
 2B) 2010 FBC-B 706.8 FIREWALL OPENINGS.
 EACH OPENING THROUGH A FIRE WALL SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 715.4 AND SHALL NOT EXCEED 156
 SQUARE FEET (15 M2). THE AGGREGATE WIDTH OF OPENINGS AT
 ANY FLOOR LEVEL SHALL NOT EXCEED 25 PERCENT OF THE
 LENGTH OF THE WALL.
 EXCEPTIONS:
 1. OPENINGS ARE NOT PERMITTED IN PARTY WALLS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 706.1.1.
 2. OPENINGS SHALL NOT BE LIMITED TO 156 SQUARE FEET (15
 M2) WHERE BOTH BUILDINGS ARE EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1.
  
 2C) 706.9 FIREWALL PENETRATIONS. PENETRATIONS OF FIRE
 WALLS SHALL COMPLY WITH SECTION 713.
  
 2D) 2010 FBC-B 706.5.1 REQUIRES THERE TO BE NO
 PENETRATIONS OF THE ROOF WITHIN THE TOTAL LENGTH OF THE
 FIRE WALL, THE VENT WILL BE REQUIRED TO BE OFFSET. IN
 NEW CONSTRUCTION THE ROOF DECK WOULD HAVE BEEN EITHER
 FIRE RETARDANT TREATED PLYWOOD OR 5/8 INCH TYPE X
 DRYWALL BELOW THE ROOF DECK.
  
 2E) PLEASE PROVIDE WHAT TYPE OF FIRE RESISTANCE RATED
 ASSEMBLY WILL BE INSTALLED WHERE THE PIPES PENETRATE
 THE FIRE RATED WALL.
 2010 FBC-B 713.3.1.1.
  
 3) PLEASE SEE ACCESSIBILITY DETAIL FLOOR PLAN INDICATES
 THE WATER CLOSET A MINIMUM OF 12 INCHES FROM WALL LINE.
 2010 FL ACCESSIBILITY CODE 604.2 LOCATION. THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES
 (455 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION,
 EXCEPT THAT THE WATER CLOSET SHALL BE 17 INCHES (430
 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION IN THE AMBULATORY ACCESSIBLE
 TOILET COMPARTMENT SPECIFIED IN 604.8.2. WATER CLOSETS
 SHALL BE ARRANGED FOR A LEFT-HAND OR RIGHT-HAND
 APPROACH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-22 Cont ID  
Sent By dhayes Date 2014-05-22 Time 07:51 Rev Time 0.00
Received By dhayes Date 2014-05-22 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By pleduc Date 2014-05-13 Time 16:38 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 10:36 Sent To  
Notes
2014-05-12 11:27:10ROUTE TO DENIED DRAWER "M"

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-13 Cont ID  
Sent By pleduc Date 2014-05-13 Time   Rev Time 0.00
Received By pleduc Date 2014-04-29 Time 15:54 Sent To B
Notes
2014-04-29 16:13:16THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENT.
  
 THE WALLS OF THE SPACE INDICATED AS "FUTURE A/C" SHALL
 HAVE A 1 HOUR RATING AND INDICATED AS SUCH ON THE PLAN.
  
 PER SECTION 8.7, ANY AREA HAVING A DEGREE OF HAZARD
 GREATER THAN NORMAL TO THE GENERAL OCCUPANCY OF THE
 BUILDING, SHALL BE PROVIDED WITH A 1-HOUR FIRE-RATED
 BARRIER OR BE PROTECTED WITH AN AUTOMATIC SPRINKLER
 SYSTEM.
  
 DENIED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-22 Cont ID  
Sent By dhayes Date 2014-05-22 Time 07:52 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 17:28 Sent To  
Notes
2014-05-17 16:37:165/17 TO JW DESK
  
2014-05-12 17:29:00SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 11:17 Rev Time 0.00
Received By dhayes Date 2014-04-24 Time 18:15 Sent To  
Notes
2014-04-24 18:15:36SENT TO B10 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-02 Cont ID  
Sent By hmoser Date 2014-05-02 Time 13:17 Rev Time 0.00
Received By hmoser Date 2014-05-02 Time 13:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-21 Cont ID  
Sent By jwitmer Date 2014-05-21 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2014-05-21 Time 11:20 Sent To  
Notes
2014-05-21 12:03:49PLUMBING PLAN REVIEW
 REVISION: 14040884
 PERMIT: 13120972
 ADD: 5802 S DIXIE HWY.
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WEDNESDAY MAY 21/2014
 ACTION: PROVISO
  
 1) THIS IS A EXPANSION OF A INTERIOR- DEMO PERMIT TO
 INCLUDE THE REBUILDING OF A RESTROOM, THIS TENANT SPACE
 IS TO BE CONSIDERED A SHELL OR VANILLA BOX .PLEASE NOTE
 THE REQUIREMENTS FOR THE FOLLOWING OCCUPANCIES FOR A
 FUTURE TENANT BUILD OUT:
 . NOTE TENANT SPACE IS APPROXIMATELY 1386 SQ FT.
 BUSINESS 1386 SQ FT/ 100= 14 OCCUPANT LOAD 2010 FBC-P
 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX
  
 MERCANTILE 1386 SQ FT / 30 = 47 OCCUPANT LOAD 2010
 FBC-P 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX & HI-LOW
 DRINKING FOUNTAIN.
  
 MERCANTILE (RESTUARANT , 50 OCC) 1386 SQ FT / 30 = 47
 OCCUPANT LOAD 2010 FBC-P 403.2 EXC 3 ALLOWS FOR A
 SINGLE UNISEX, SERVICE SINK & GREASE INTERCEPTOR SIZED
 FOR FLOW RATE
  
 RESTAURANT 1386 SQ FT/ 15= 93 OCCUPANT LOAD REQUIRING 2
 RESTROOMS, SERVICE SINK & GREASE INTERCEPTORSIZED FOR
 FLOW RATE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 06:15 Sent To  
Notes
2014-05-02 07:01:09PLUMBING PLAN REVIEW
 REVISION: 14040884
 PERMIT: 13120972
 ADD: 5802 S DIXIE HWY.
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI.
 ACTION: DENIED
  
 1) THIS IS A EXSPANSION OF A INTERIOR- DEMO PERMIT TO
 INCLUDE THE REBUILDING OF A RESTROOM. PLEASE PROVIDE
 TYPE OF OCCUPANCY THIS UNIT IS TO BE CONSIDERED. NOTE
 APPROXIMATELY 1386 SQ FT.
 BUSSINESS 1386 SQ FT/ 100= 14 OCCUPANT LOAD 2010 FBC-P
 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX
 MERCANTILE 1386 SQ FT / 30 = 47 OCCUPANT LOAD 2010
 FBC-P 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX
 RESTARAUNT 1386 SQ FT/ 15= 93 OCCUPANT LOAD
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
  
 2A) THE PLANS INDICATE THE NEW RESTROOM PLUMBING GOING
 INTO A EXISTING FIRE WALL, THE TYPE OF OCCUPANCY NEEDS
 TO BE DECLARED TO KNOW WHAT RATING THE FIRE WALL NEEDS
 TO BE RATED. PLEASE CONFIRM IF THIS IS A PARTYWALL
 SHARED BY BOTH TENANTS OR IF THERE ARE TO TENANT
 SEPERATION WALLS BACK TO BACK. IF THIS IS A SHARED
 PARTYWALL THE PLUMBING WILL NOT BE ABLE TO BE PUT INTHE
 PARTY WALL. FOR A TENANT SEPERATION WALL PLEASE SEE
 2010 FBC-B TABLES 602 EXTERIOR WALLS FIRE SEPERATION
 DISTANCE AND TABLE 706.4 FIRE WALL RATINGS DETERMINED
 BY OCCUPANCY GROUP. NOTE IF THE PLUMBING IS INSET INTO
 THE FIRE WALL, WHAT TYPE OF MATERIAL IS GOING TO BE
 USED TO BE INSTALLED TO COVER THE PIPES AND HAVE THE
 SAME RATING AS THE FIRE WALL.
  
 2B) 2010 FBC-B 706.8 FIREWALL OPENINGS.
 EACH OPENING THROUGH A FIRE WALL SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 715.4 AND SHALL NOT EXCEED 156
 SQUARE FEET (15 M2). THE AGGREGATE WIDTH OF OPENINGS AT
 ANY FLOOR LEVEL SHALL NOT EXCEED 25 PERCENT OF THE
 LENGTH OF THE WALL.
 EXCEPTIONS:
 1. OPENINGS ARE NOT PERMITTED IN PARTY WALLS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 706.1.1.
 2. OPENINGS SHALL NOT BE LIMITED TO 156 SQUARE FEET (15
 M2) WHERE BOTH BUILDINGS ARE EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1.
  
 2C) 706.9 FIREWALL PENETRATIONS. PENETRATIONS OF FIRE
 WALLS SHALL COMPLY WITH SECTION 713.
  
 2D) 2010 FBC-B 706.5.1 REQUIRES THERE TO BE NO
 PENETRATIONS OF THE ROOF WITHIN THE TOTAL LENGTH OF THE
 FIRE WALL, THE VENT WILL BE REQUIRED TO BE OFFSET. IN
 NEW CONSTRUCTION THE ROOF DECK WOULD HAVE BEEN EITHER
 FIRE RETARDANT TREATED PLYWOOD OR 5/8 INCH TYPE X
 DRYWALL BELOW THE ROOF DECK.
  
 2E) PLEASE PROVIDE WHAT TYPE OF FIRE RESISTANCE RATED
 ASSEMBLY WILL BE INSTALLED WHERE THE PIPES PENETRATE
 THE FIRE RATED WALL.
 2010 FBC-B 713.3.1.1.
  
 3) PLEASE SEE ACCESSIBILITY DETAIL FLOOR PLAN INDICATES
 THE WATER CLOSET A MINIMUM OF 12 INCHES FROM WALL LINE.
 2010 FL ACCESSIBILITY CODE 604.2 LOCATION. THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES
 (455 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION,
 EXCEPT THAT THE WATER CLOSET SHALL BE 17 INCHES (430
 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION IN THE AMBULATORY ACCESSIBLE
 TOILET COMPARTMENT SPECIFIED IN 604.8.2. WATER CLOSETS
 SHALL BE ARRANGED FOR A LEFT-HAND OR RIGHT-HAND
 APPROACH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  