Plan Review Details - Permit 14040877
Plan Review Stops For Permit 14040877
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-02 Cont ID  
Sent By shill Date 2014-05-02 Time 12:27 Rev Time 0.00
Received By shill Date 2014-05-02 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 10:00 Rev Time 0.00
Received By shill Date 2014-04-26 Time 10:00 Sent To  
Notes
2014-04-26 10:03:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 **REVISED 5/2** - ITEMS #1&2 (COPIES OF SOUND TEST)
 WAIVED AS UNIT IS OVER THE GARAGE AREA
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 THE TEST PROVIDED IS INCOMPLETE. PRODUCT PROPOSED
 APPEARS TO BE "FLOOR MUFFLER." THE NAME OF THE PRODUCT
 TESTED APPEARS TO BE "GREEN FLOOR MUFFLER FLOOR
 UNDERLAYMENT" BUT IS PARTIALLY OBSCURED. PROVIDE A TEST
 REPORT WHICH CLEARLY SHOWS THE PRODUT NAME, WHICH
 SHOULD BE CONSISTENT WITH THE PRODUCT PROPOSED AND THE
 TWO SOUND TESTS.
  
 4. TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 10:03 Rev Time 0.00
Received By shill Date 2014-04-24 Time 13:21 Sent To  
Notes
2014-04-24 13:22:29<5000 BLDG