Plan Review Details - Permit 14040876
Plan Review Stops For Permit 14040876
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-09 Cont ID  
Sent By dhayes Date 2014-07-09 Time 15:29 Rev Time 0.00
Received By dhayes Date 2014-07-09 Time 14:56 Sent To  
Notes
2014-07-09 15:28:40DATE: 7/9/2014
 PROJECT: SEABOARD TRAIN STATION.
 PERMIT#: 14040876
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 2) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
 ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 3) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF
 THIS CODE. NEC 110.3(A)(1 THRU 8)
  
 4)THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN 680.2. NEC 680.50
 THE LIGHTING AND SUBMERSIBLE PUMP CIRCUITS SHALL BE
 GFCI PROTECTED UNLESS THEY OPERATE AT UNDER 15 VAC. NEC
 680.51
  
 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By albarran Date 2014-05-07 Time 20:12 Rev Time 0.00
Received By albarran Date 2014-05-07 Time 19:31 Sent To I
Notes
2014-05-07 20:14:03FIRST ELECTRICAL REVIEW FAILED AS BELOW INDICATED:
  
 1. MISSING A SECOND SET OF PLANS FOR APPROVAL
  
 2. MISSING THE WIND LOAD CALCS FOR THE POLES WITH THE
 RESPECTIVE FIXTURE HEADS. THESE WIND LOAD CALCS SHALL
 COMPLY WITH THE "LIGHT POLE NOTES" OF PAGE E1.03
  
 3 AS PER NEC 680.51, THE LIGHTING AND SUBMERSIBLE PUMP
 CIRCUITS SHALL BE GFCI PROTECTED UNLESS THEY OPERATE AT
 UNDER 15 VAC.
  
 4. AS PER NEC 406.8(B) THE "WP" RECEPTACLE ADJACENT TO
 THE FOUNTAIN SHALL BE LISTED "WR" WEATHER-RESISTANT
 TYPE IN ADDITION TO THE WEATHER-PROOF COVERS.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-07-10 Cont ID  
Sent By fmittner Date 2014-07-10 Time 16:21 Rev Time 0.00
Received By fmittner Date 2014-07-10 Time 16:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By fmittner Date 2014-05-06 Time 10:57 Rev Time 0.00
Received By fmittner Date 2014-05-06 Time 10:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-09 Cont ID  
Sent By dhayes Date 2014-07-09 Time 15:28 Rev Time 0.00
Received By dhayes Date 2014-07-09 Time 13:00 Sent To  
Notes
2014-07-09 13:00:35SENT TO ELECTRICAL BOX