Plan Review Details - Permit 14040803
Plan Review Stops For Permit 14040803
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-28 Cont ID  
Sent By albarran Date 2014-04-28 Time 17:10 Rev Time 0.00
Received By albarran Date 2014-04-28 Time 15:43 Sent To I
Notes
2014-04-28 17:10:38ELECTRICAL PROVISO FOR PERMIT 14040803
  
 1. FOR FINAL INSPECTION THIS SYSTEM SHALL UNDERGO A
 REACCEPTANCE TEST AS PER NFPA 72, SECTION 10.4.1.2.
 RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM LOG AS
 REQUIRED.
 2. PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM
 CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED
 AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY PROTECTED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By pleduc Date 2014-04-24 Time 16:32 Rev Time 0.00
Received By pleduc Date 2014-04-24 Time 15:27 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-28 Cont ID  
Sent By albarran Date 2014-04-28 Time 17:11 Rev Time  
Received By albarran Date   Time   Sent To PC
Notes
2014-04-28 17:12:50PROCESSED AND CONTACTED SARA. SENT TO READY "S"
2014-04-22 15:22:07ROUTED TO FIRE