| Plan Review Stops For Permit 14040803 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-04-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-28 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-28 |
Time |
15:43 |
Sent To |
I |
|
| Notes |
| 2014-04-28 17:10:38 | ELECTRICAL PROVISO FOR PERMIT 14040803 | | | | | | 1. FOR FINAL INSPECTION THIS SYSTEM SHALL UNDERGO A | | | REACCEPTANCE TEST AS PER NFPA 72, SECTION 10.4.1.2. | | | RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM LOG AS | | | REQUIRED. | | | 2. PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM | | | CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED | | | AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY PROTECTED. | | | |
|
|