Plan Review Details - Permit 14040733
Plan Review Stops For Permit 14040733
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2014-09-09 Cont ID  
Sent By skennedy Date 2014-09-09 Time 16:28 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-09-09 16:31:23SEE EMAIL TO JOHN CAIRNES DATED 9/9/14.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 12:58 Rev Time 0.00
Received By jwitmer Date 2014-04-25 Time 12:58 Sent To  
Notes
2014-04-25 12:59:03ADDRESSING NOTIFIED, CLOSED STOP FOR AUDITING PURPOSES.
 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-08 Cont ID  
Sent By skennedy Date 2014-09-08 Time 11:34 Rev Time 0.00
Received By skennedy Date 2014-09-08 Time 11:34 Sent To  
Notes
2014-08-15 15:08:57NEW SHEETS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2014-04-25 Time 12:05 Sent To  
Notes
2014-04-25 12:38:52PROVISO:SLAB PAD WORK SHOULD SHOW SLOPE AWAY FROM WELL
 TO KEEP TOXINS FROM SEEPING INTO THE WELL AND AQUAFIER.
 A SEPARATE PERMIT WILL BE REQUIRED FOR ALL FENCING FOR
 THE PROTECTION OF WELL HEAD AND ELECTRICAL EQUIPMENT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 14:03 Rev Time 0.00
Received By rlecky Date 2014-09-09 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By albarran Date 2014-04-24 Time 08:22 Rev Time 0.00
Received By albarran Date 2014-04-23 Time 17:24 Sent To P
Notes
2014-04-24 08:35:56THE FOLLOWING ITEMS SHALL BE ADDRESSED FOR APPROVAL OF
 THIS PERMIT:
 1. INDICATE THE SOURCE OF THE 120 VOLT CIRCUIT ALONG
 WITH THE METERING AND CONNECTIONS.
 2. INCLUDE THE NEC 110.16 FLASH PROTECTION WARNING
 3. MAKE CERTAIN THAT ALL SERVICE EQUIPMENT IS WELL
 CLEAR OF THE ELECTRICAL DATUM PLANE AS PER NEC 682.10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-09 Cont ID  
Sent By rlecky Date 2014-09-09 Time 14:03 Rev Time 0.00
Received By rlecky Date 2014-08-15 Time 15:45 Sent To  
Notes
2014-08-15 15:46:24RE-SUBMITTAL SENT TO C25 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 12:58 Rev Time 0.00
Received By jwitmer Date 2014-04-21 Time 16:43 Sent To  
Notes
2014-04-21 16:35:18EXPEDITED PLANS SENT TO B4 SHELF FOR REVIEW. JG.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2014-09-08 Cont ID  
Sent By sgraham Date 2014-09-08 Time 11:24 Rev Time 0.00
Received By sgraham Date 2014-09-08 Time 11:24 Sent To  
Notes
2014-08-15 15:10:44LANDSCAPE PLANS SUBMITTED L1-1 AND L1-2. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-08 Cont ID  
Sent By skennedy Date 2014-09-08 Time 10:36 Rev Time 0.00
Received By skennedy Date 2014-09-08 Time 11:33 Sent To  
Notes
2014-09-08 11:33:47IRRIGATION ONLY.
2014-08-15 15:08:10NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 12:38 Rev Time 0.00
Received By jwitmer Date 2014-04-25 Time 12:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-08 Cont ID  
Sent By sgraham Date 2014-09-08 Time 11:23 Rev Time 0.00
Received By sgraham Date 2014-09-08 Time 11:23 Sent To  
Notes
2014-09-08 11:34:11FOR FENCE PERMITS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved