Plan Review Details - Permit 14040712
Plan Review Stops For Permit 14040712
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By jwitmer Date 2014-04-21 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-04-21 Time 07:00 Sent To  
Notes
2014-04-21 07:29:23BUILDING PROVISO:
 1) 2010 FBC-B SECTION 603
 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION
 (2). THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 100.
  
 2) 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS
 FIBER-MAT REINFORCED CEMENT SUBSTRATE SHEETS IN
 COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 AND
 INSTALLED IN ACCORDANCE
 WITH MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND
 CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840 AND
 MANUFACTURER RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD
 IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM
 BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By jwitmer Date 2014-04-21 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 07:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By jwitmer Date 2014-04-21 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-04-21 Time 07:29 Sent To  
Notes
***NONE***