Plan Review Details - Permit 14040681
Plan Review Stops For Permit 14040681
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 19:12 Rev Time 0.00
Received By shill Date 2014-06-20 Time 19:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-01 Time 15:35 Rev Time 0.00
Received By shill Date 2014-05-01 Time 15:35 Sent To  
Notes
2014-05-01 15:40:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 3202.3.1, REVISE SITE PLAN TO INCLUDE SIDEWALK
 WIDTH.
  
 DIMENSIONS ARE DIFFICULT TO READ AS THE HATCHING OF THE
 AWNING PARTIALLY OBSCURES SOME DIMENSIONS. HOWEVER, IT
 APPEARS THAT THE AWNING ENCROACHES MORE THAN THE 2/3
 ALLOWED BY FBC 3202.3.1 AND 3105.1.1.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 19:12 Rev Time 0.00
Received By shill Date 2014-06-05 Time 09:25 Sent To  
Notes
2014-06-20 13:38:23TO MISC BOX.
2014-06-05 09:26:14INCOMING SENT TO ZONING . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-01 Time 15:40 Rev Time 0.00
Received By shill Date 2014-04-18 Time 16:50 Sent To  
Notes
2014-05-01 09:28:07TO MISC 2 BOX.
2014-04-18 16:50:32INCOMING SENT TO ZONING BOX. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By aaponte Date 2014-06-20 Time 13:26 Rev Time 0.00
Received By aaponte Date 2014-06-20 Time 13:26 Sent To  
Notes
2014-06-20 13:37:57PROVISO: SIGN ON AWNING CANNOT BE WIDER THAN 60% OF
 STOREFRONT WIDTH ( NO MORE THAN 15.6' IN TOTAL WIDTH).
2014-06-05 11:40:496/5/14 ZONING SENT TO AA. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By AAponte Date 2014-05-01 Time 09:20 Rev Time 0.00
Received By aaponte Date 2014-05-01 Time 09:20 Sent To  
Notes
2014-05-01 09:27:471. PROPOSED AWNING IS NOT CONSISTENT WITH THE DESIGN
 CHARACTER OF THE BUILDING. EXISTING CONCRETE CANOPY
 SHALL BE RESPECTED. PLEASE EXPLORE A HORIZONTAL ELEMENT
 THAT COMPLEMENTS AND WORKS WITH THE EXISTING CONCRETE
 CANOPY.
 2. MAXIMUM HORIZONTAL PROJECTION FOR AWNINGS IS 8 FEET.
 PROPOSED AWNING IS 11'-8". IF THE AWNING IS REPLACED
 FOR A CANOPY, THE 11'8" PROJECTION IS PERMITTED.
 3. PLEASE INDICATE VERTICAL CLEARANCE. MINIMUM 8'
 REQUIRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
2014-04-21 14:55:074/21/14 ZONING RECEIVED, SENT TO AA. SG