Plan Review Details - Permit 14040680
| Plan Review Stops For Permit 14040680 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-29 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-29 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2014-04-29 08:12:41 | BUILDING PROVISO: | | | 1) BEFORE THE INSTALLATION OF FLOOR INSULATION SUBMIT | | | MANUFACTURERS TEST FOR COMPLIANCE WITH: | | | 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING | | | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF | | | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING | | | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX | | | OF NOT MORE THAN 100. | | | | | | | | | | | | FBC-B 2010 | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-04-21 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-04-21 |
Time |
12:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-29 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-18 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2014-04-18 16:56:38 | INCOMING SENT TO B23 BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-29 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-29 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2014-04-29 08:51:36 | MECHANICAL PROVISO; | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | COMMERCIAL BUILDINGS: | | | MECHANICAL | | | BATHROOM VENTILATION IT APPEARS THE CEILING FAN IS | | | BEING REMOVED. | | | ENVIRONMENTAL AIR. AIR THAT IS CONVEYED TO OR FROM | | | OCCUPIED AREAS THROUGH DUCTS WHICH ARE NOT PART OF THE | | | HEATING OR AIR-CONDITIONING SYSTEM, SUCH AS VENTILATION | | | FOR HUMAN USAGE, DOMESTIC KITCHEN RANGE EXHAUST, | | | BATHROOM EXHAUST AND DOMESTIC CLOTHES DRYER EXHAUST. | | | | | | 2010 FBC-MECHANICAL TABLE 403.3 EXHAUST AIRFLOW 50 CFM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-29 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-29 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2014-04-29 08:22:44 | PLUMBING PROVISO; | | | SHOWER LINER TEST REQUIRED. | | | 312.9 SHOWER LINER TEST. | | | WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER-TIGHT | | | BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION | | | 417.5.2, THE COMPLETED LINER INSTALLATION SHALL BE | | | TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED | | | WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA | | | SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT | | | LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD. | | | WHERE A THRESHOLD OF AT LEAST 2 INCHES (51 MM) HIGH | | | DOES NOT EXIST, A TEMPORARY THRESHOLD SHALL BE | | | CONSTRUCTED TO RETAIN THE TEST WATER IN THE LINED FLOOR | | | OR RECEPTOR AREA TO A LEVEL NOT LESS THAN 2 INCHES (51 | | | MM) DEEP MEASURED AT THE THRESHOLD. THE WATER SHALL BE | | | RETAINED FOR A TEST PERIOD OF NOT LESS THAN 15 MINUTES, | | | AND THERE SHALL NOT BE EVIDENCE OF LEAKAGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2014-04-21 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2014-04-21 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
|