Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-29 Cont ID  
Sent By jwitmer Date 2014-05-29 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2014-05-29 Time 15:42 Sent To  
Notes
2014-05-29 15:47:50IMPACT FEES ARE NOT REQUIRED, I SPOKE WITH MICHELLE AT
 THE P B COUNTY IMPACT FEE OFFICE NO FEES ARE REQUIRED
 FOR A CHANGE OF OCCUPANCY FOR DAYCARE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2014-05-05 Time 08:43 Sent To  
Notes
2014-05-05 08:52:17BUILDING PLAN REVIW
 PERMIT: 14040657
 ADD: 5335 N MILITARY TRL. # 40 & 65
 CONT: MIKE MOORE
 TEL: (561) 301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 03/ 2014
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET A-1;
  
 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A
 MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE
 BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010
 FBC-B 508.2 & 508.2.1.
  
 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS
 BEING FIGURED AT 35 SQ FT IN THE CLASSROOMS, NOTE THIS
 IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL
 OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE
 FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES
 AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER
 ALL OCCUPANT LOAD AND POSSIBLE PLUMBING FIXTURE COUNT.
  
 1C) WITH THE INCREASED OCCUPANT LOAD IN CLASSROOM # 6
 AND THE MULTI-PURPOSE ROOM EACH HAVING A OCCUPANT LOAD
 GREATER THAN 49 WILL REQUIRE 2 EXIT DOORS SEE 2010
 FBC-B TABLE 1015.1.
  
 1D) THE 2 ROOMS REQUIRING THE 2 EGRESS EXIT DOORS WILL
 ALSO NEED TO COMPLY WITH THE 2 DOORS BEING 1/3RD THE
 DIAGONAL DISTANCE APART IN EACH ROOM SEE 2010 FBC-B
 1015.2.1 EXC. 2.
  
 1E) PLEASE PROVIDE A EXPLANATION AS TO THE TERM
 CLASSROOM AND WHAT WILL BE TAUGHT IN EACH AREA, SEE HOW
 THIS TERM AFFECTS THE OCCUPANCY AND WALL RATINGS.
 2010 FBC-B 313.1 SCOPE.
 GROUP D OCCUPANCY IS THE USE OF A BUILDING OR
 STRUCTURE, OR ANY PORTION THEREOF, IN WHICH THREE OR
 MORE CLIENTS RECEIVE CARE, MAINTENANCE AND SUPERVISION,
 BY OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S),
 FOR LESS THAN 24 HOURS PER DAY. OCCUPANCIES THAT
 INCLUDE PART-DAY PRESCHOOLS, KINDERGARTENS AND OTHER
 SCHOOLS WHOSE PURPOSE IS PRIMARILY EDUCATIONAL EVEN
 THOUGH THE CHILDREN ARE OF PRESCHOOL AGE SHALL COMPLY
 WITH THE PROVISIONS FOR GROUP E OCCUPANCIES.
  
 1F) CORRIDOR WIDTHS WILL NEED TO BE INCREASED TO COMPLY
 WITH 2010 FBC-B 1018.2 CORRIDOR WIDTH.
 THE MINIMUM CORRIDOR WIDTH SHALL BE AS DETERMINED IN
 SECTION 1005.1, BUT NOT LESS THAN 44 INCHES (1118 MM).
 EXC. 4. SEVENTY-TWO INCHES (1829 MM)?IN GROUP E WITH A
 CORRIDOR HAVING A REQUIRED CAPACITY OF 100 OR MORE.
  
 1G) CORRIDOR WALL SECTIONS DETAILS 7/A3 & DETAIL #8/A3
 BOTH INDICATE THE USE OF SMOKE PARTITIONS, PLEASE SEE
 THE INFORMAL BOAF INTERPRETATION ON SMOKE PARTITIONS
 AND DRYWALL ON ONE SIDE ONLY.
 DATE: MON OCT 26 2009
 REPORT: 6341
 CODE: BUILDING CODE YEAR: 2007
 SECTION: 710
 QUESTION:
 IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING
 SECTION 710.4 TO ALLOW A SMOKE PARTITION TO BE
 CONSTRUCTED WITH ONE LAYER OF
 GYPSUM WALLBOARD ON ONE SIDE (THE SMOKE SIDE) OF THE
 PARTITION OR MUST WALLBOARD BE INSTALLED ON BOTH SIDES,
 EXTENDING FROM
 FOUNDATION OR FLOOR TO THE UNDERSIDE OF THE FLOOR OR
 ROOF SHEATHING, DECK OR SLAB ABOVE?
 COMMENT:
 NONE.
 ANSWER:
 YES. ONE LAYER OF GYPSUM ON ONE SIDE IS ACCEPTABLE BUT
 THE OTHER SIDE CANNOT REMAIN OPEN. IT MUST BE ENCLOSED
 WITH MATERIAL
 "PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION". THE
 WALL MUST BE ENCLOSED FROM BOTH SIDES TO PREVENT SMOKE
 MIGRATION FROM
 EITHER SIDE. THE SPACE AROUND PENETRATING ITEMS AND IN
 JOINTS SHALL BE FILLED WITH AN APPROVED MATERIAL TO
 LIMIT THE FREE PASSAGE
 OF SMOKE. THE WALL MAY HAVE ELECTRICAL BOXES OR OTHER
 PENETRATIONS THAT CAN ALLOW SMOKE TO MIGRATE FROM THE
 "OPEN" SIDE.
 COMMENTARY:
 SEE ALSO SECTIONS 710.2 AND 710.6.
  
 2A) SHEET A-3 DETAIL # 9 WALL AND CEILING OF THE
 LAUNDRY ROOM. THE PLANS INDICATE THE USE OF THE GYPSUM
 ASSOC. GA-610-02, GA FILES RC2601 & FC 5406, PLEASE
 PROVIDE THE DOCUMENTS SO THE INSPECTOR WILL BE ABLE TO
 DO THEIR INSPECTIONS. 107.2.1.3 ADDITIONAL INFORMAION
 REQUIRED. 707.5 CONTINUITY.
  
 2B) THIS SAME DETAIL ALSO INDICATES THE USE OF AN
 ALTERNANTE HORIZONTAL ASSEMBLY AER-09038 FIG. # 7. SEE
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 2C) 707.9 DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS
 IN A FIRE BARRIER BY DUCTS AND AIR TRANSFER OPENINGS
 SHALL COMPLY WITH SECTION 716.
  
 3) SHEET A-2 DETAIL # 10 INDICATES NEW OPENING IN A
 EXTERIOR CMU WALL. SHEET A-1 DOES NOT SHOW THIS DETAIL
 ANYWHERE. CLASSROOM # 4 DOOR # 1 DOES SHOW POSITIVE &
 NEGATIVE PRESSURES, ASSUMING THIS IS THE NEW DOOR.
  
 3A) SHEET A-2 DETAIL # 10 SHOWS A NEW LINTAL BUT DOES
 NOT INDICATE HOW THE VERTICAL REBARS THAT ARE BEING CUT
 WILL MAINTAIN THE PART OF THE MAIN WIND FORCE
 RESISTNING SYSTEM (MWERS)? 1609.6.
  
 3B) SHEET A1 CLASSROOM # 4 DOOR # 1 INDICATE PRESSURES
 PLEASE PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B
 1609.6.
  
  
 3C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3D) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-06-04 Cont ID  
Sent By dhayes Date 2014-06-04 Time 14:07 Rev Time 0.00
Received By dhayes Date 2014-06-04 Time 14:07 Sent To  
Notes
2014-06-04 14:44:22PROJECT: 5335 N. MILITARY TR. #40 AND 65
 PERMIT# 14040657
 3RD ELECTRICAL REVIEW
 ACTION: PROVISIONAL APPROVAL
 CODE: 2008 NEC AND 2010 FBC
  
 CORRECTIONS REQUIRED ON REVISION:
  
 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. NEC 230.2 (NUMBER OF SERVICES)
 THE RISER AND FLOOR PLAN AS CURRENTLY SHOWN ON SHEET
 E-1 INDICATES THIS EXACT CONDITION PROHIBITED BY THE
 CODE NOTED ABOVE. PLEASE MAKE CORRECTION TO THIS
 CONDITION AND RE-SUBMIT.
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE
 701.11(G) OF THE 2008 EDITION OF THE NEC.
  
 3) CHILD CARE FACILITIES SHALL COMPLY WITH THE 2010
 EDITION OF THE FBC SECTION 436 SEE SECTION BELOW:
 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM SHALL BE
 BY MANUAL MEANS AND BY OPERATION OF ANY REQUIRED SMOKE
 DETECTORS AND REQUIRED SPRINKLER SYSTEMS. FBC 436.7.1
  
 4) OCCUPANT NOTIFICATION SIGNALS SHALL BE AUDIBLE AND
 VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 AND THE
 FBC-ACCESSIBILITY. THE GENERAL EVACUATION ALARM SIGNAL
 SHALL OPERATE THROUGHOUT THE ENTIRE BUILDING. FBC
 436.7.1.1
  
 5) A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO STAIRS AND IN THE
 CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAYCARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY. 436.7.2
  
 6) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW
 VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE
 ALARM, DATA/COM, AND ACCESS CONTROL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 14:54 Rev Time 0.00
Received By dhayes Date 2014-06-03 Time 14:54 Sent To  
Notes
2014-06-03 14:30:215335 N. MILITARY TR. #40 AND 65
  
 NOTE: ALTHOUGH THE 2ND ELECTRICAL REVIEW CONFLICTS WITH
 THE 1ST REVIEW IT SHALL OVERIDE AND DEEM THE 1ST REVIEW
 NULL AND VOID.
  
 2ND ELECTRICAL REVIEW:
  
 ACTION: DENIED.
  
 CODE REFFRENCE: 2008 NEC AND 2010 FBC
  
 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. NEC 230.2 (NUMBER OF SERVICES)
 THE RISER AND FLOOR PLAN AS CURRENTLY SHOWN ON SHEET
 E-1 INDICATES THIS EXACT CONDITION PROHIBITED BY THE
 CODE NOTED ABOVE. PLEASE MAKE CORRECTION TO THIS
 CONDITION AND RE-SUBMIT.
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE
 701.11(G) OF THE 2008 EDITION OF THE NEC.
  
 3) CHILD CARE FACILITIES SHALL COMPLY WITH THE 2010
 EDITION OF THE FBC SECTION 436 SEE SECTION BELOW:
 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM SHALL BE
 BY MANUAL MEANS AND BY OPERATION OF ANY REQUIRED SMOKE
 DETECTORS AND REQUIRED SPRINKLER SYSTEMS. FBC 436.7.1
  
 4) OCCUPANT NOTIFICATION SIGNALS SHALL BE AUDIBLE AND
 VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 AND THE
 FBC-ACCESSIBILITY. THE GENERAL EVACUATION ALARM SIGNAL
 SHALL OPERATE THROUGHOUT THE ENTIRE BUILDING. FBC
 436.7.1.1
  
 5) A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO STAIRS AND IN THE
 CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAYCARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY. 436.7.2
  
 6) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW
 VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE
 ALARM, DATA/COM, AND ACCESS CONTROL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
2014-05-14 17:58:11NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 13:03 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 11:29 Sent To  
Notes
2014-05-12 13:15:40ELECTRICAL PROVISO:
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE
 701.11(G) OF THE 2008 EDITION OF THE NEC.
  
 3) CONDUCTORS SHALL BE PERMITTED TO BE TAPPED WITHOUT
 OVERCURRENT PROTECTION AT THE TAP TO A FEEDER AS
 SPECIFIED IN 240.21(B)(1) THROUGH B(5) SEE ARTICLE
 240.21(B) OF THE 2008 EDITION OF THE NEC. THE RISER
 DIAGRAM AS SHOWN ON PLANS DOES NOT APPEAR TO BE IN
 COMPLIANCE. VERIFY EXISTING CONDITION IN THE FIELD.
  
 4) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW
 VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE
 ALARM, DATA/COM, AND ACCESS CONTROL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-05-19 Cont ID  
Sent By pleduc Date 2014-05-19 Time   Rev Time 0.00
Received By pleduc Date 2014-05-19 Time 09:48 Sent To  
Notes
2014-05-14 17:58:36NEW SHEETS SUBMITTED.. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By pleduc Date 2014-04-22 Time 14:46 Rev Time 0.00
Received By pleduc Date 2014-04-22 Time 14:13 Sent To E
Notes
2014-04-22 14:46:16THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMNETS.
  
 ON SHEETS LS-1 AND E-2, PLEASE ADD AN "EM" LIGHT IN
 REAR HALLWAY WHERE INDICATED AND MOVE THE "EM" LIGHT
 FROM LEFT SIDE OF HALLWAY TO THE RIGHT SIDE.
  
 ON SHEET E-1 AT THE FRONT LOBBY AND RECEPTION AREA IT
 INDICATES "BUZZER RELEASE". THE EXIT DOORS IN THAT AREA
 CAN'T BE LOCKED AGAINST EGRESS. PLEASE REFER TO THE
 DELAYED EGRESS CODE IN CHAPTER 7 OF THE FLORIDA FIRE
 PREVENTION CODE FOR GUIDENCE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 14:55 Rev Time 0.00
Received By dhayes Date 2014-05-14 Time 08:54 Sent To  
Notes
2014-05-15 08:55:09RESUBMITTAL SENT TO B21 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 14:24 Rev Time 0.00
Received By dhayes Date 2014-04-17 Time 09:51 Sent To  
Notes
2014-04-21 09:54:28C22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-09 Cont ID  
Sent By hmoser Date 2014-05-09 Time 15:17 Rev Time 0.00
Received By hmoser Date 2014-05-09 Time 15:17 Sent To  
Notes
2014-05-09 15:18:46NO MECHANICAL PLAN SUBMITTED
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-29 Cont ID  
Sent By jwitmer Date 2014-05-29 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2014-05-29 Time 15:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By jwitmer Date 2014-05-05 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2014-05-03 Time 13:02 Sent To  
Notes
2014-05-03 13:27:53PERMIT: 14040657
 ADD: 5335 N MILITARY TRL. # 40 & 65
 CONT: MIKE MOORE
 TEL: (561) 301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 03/ 2014
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET A-1;
  
 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A
 MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE
 BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010
 FBC-B 508.2 & 508.2.1.
  
 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS
 BEING FIGURED AT 35 SQ FT INTHE CLASSROOMS, NOTE THIS
 IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL
 OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE
 FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES
 AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER
 ALL OCCUPANTLOAD AND POSSIBLE PLUMBING FIXTURE COUNT.
 PLEASE PROVIDE A FIXTURE COUNT PER 2010 FBC-PLUMBING
 TABLE 403.1.
  
 1C) THE EXISTING RESTROOMS LOCATED BY THE LAUNDRY ROOM
 ARE NOT ACCESSIBLE PLEASE SHOW COMPLIANCE WITH 2010
 FBC-P 213 TOILET FACILITIES AND BATHING FACILITIES
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603. EXC. 4. WHERE
 MULTIPLE SINGLE USER TOILET ROOMS ARE CLUSTERED AT A
 SINGLE LOCATION, NO MORE THAN 50 PERCENT OF THE SINGLE
 USER TOILET ROOMS FOR EACH USE AT EACH CLUSTER SHALL BE
 REQUIRED TO COMPLY WITH 603.
  
 1D) SHEET A-2 PROVIDES HANDICAPPED DETAILS FOR ADULTS
 BUT DOES NOT ADDRESS THE FOLLOWING ACCESSIBILITY
 REQUIEMENTS:
 2010 FBC- ACCESSIBILITY CODE;
 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9. SEE AGES 3 & 4, AGES 5-8 &
 9-12.
 604.9.1 LOCATION.
 THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM
 AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR
 RIGHT-HAND APPROACH TO THE WATER CLOSET.
  
 604.9.2 CLEARANCE.
 CLEARANCE AROUND A WATER CLOSET SHALL COMPLY WITH
 604.3.
  
 604.9.3 HEIGHT.
 THE HEIGHT OF WATER CLOSETS SHALL BE 11 INCHES (280 MM)
 MINIMUM AND 17 INCHES (430 MM) MAXIMUM MEASURED TO THE
 TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION.
  
 604.9.4 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 604.5.
  
 604.9.5 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.2
 AND 309.4 AND SHALL BE INSTALLED 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR. FLUSH CONTROLS SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN
 AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH
 604.8.2.
  
 604.9.6 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 14 INCHES (355 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM ABOVE THE FINISH FLOOR. THERE
 SHALL BE A CLEARANCE OF 11/2 INCHES (38 MM) MINIMUM
 BELOW THE GRAB BAR. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 2) SHEET A2 VENT SIZES ARE NOT PROVIDED ON THE DETAIL
 INACCORDANCE WITH 2010 FBC-P 907.1 & 908.1.
  
 3) THE PLANS DO NOT SHOW POTABLE WATER: 602.2 POTABLE
 WATER REQUIRED.
 ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING
 FIXTURES THAT PROVIDE WATER FOR DRINKING, BATHING OR
 CULINARY PURPOSES, OR FOR THE PROCESSING OF FOOD,
 MEDICAL OR PHARMACEUTICAL PRODUCTS. UNLESS OTHERWISE
 PROVIDED IN THIS CODE, POTABLE WATER SHALL BE SUPPLIED
 TO ALL PLUMBING FIXTURE
  
 4) HOT WATER REQUIRED. 607.1 WHERE REQUIRED.
 IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO
 ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE.
  
 EXCEPTION: IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR
 TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND
 WASHING PURPOSES. THE DELIVERY OF COLD WATER ONLY SHALL
 BE PERMITTED TO BE DELIVERED FROM ALL HAND WASHING
 FACILITIES EXCEPT WHERE HOT WATER IS REQUIRED BY LAW.
  
 607.1.1 HAND WASHING LAVATORIES.
 IN PUBLIC FOOD SERVICE ESTABLISHMENTS, FOOD
 ESTABLISHMENTS OR WHERE OTHERWISE REQUIRED BY LAW,
 LAVATORIES INTENDED FOR THE PURPOSE OF EMPLOYEE HAND
 WASHING SHALL BE EQUIPPED WITH HOT OR TEMPERED WATER.
  
 5) THE FOOD PREP AREA DOES NOT INDICATE COMPLIANCE WITH
 2010 FBC-PLUMBING 1003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By ajones Date 2014-04-24 Time 17:13 Rev Time 0.00
Received By ajones Date 2014-04-24 Time 17:13 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved