| 2014-05-05 08:52:17 | BUILDING PLAN REVIW |
| | PERMIT: 14040657 |
| | ADD: 5335 N MILITARY TRL. # 40 & 65 |
| | CONT: MIKE MOORE |
| | TEL: (561) 301-9468 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 03/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY SHEET A-1; |
| | |
| | 1A) THE BUILDING DATA INDICATES THE TENANT SPACE AS A |
| | MIXED OCCUPANCY. THIS IS A DAYCARE OCCUPANCY WITH THE |
| | BUSINESS OFFICE BEING A ACCESSORY OCCUPAN Y SEE 2010 |
| | FBC-B 508.2 & 508.2.1. |
| | |
| | 1B) THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY IS |
| | BEING FIGURED AT 35 SQ FT IN THE CLASSROOMS, NOTE THIS |
| | IS A STATE REQUIREMENT. YOU WILL NEED TO MAKE A DUAL |
| | OCCUPANT LOAD UP ONE FOR THE STATE REQUIREMENTS AND ONE |
| | FOR THE 2010 FBC-B TABLE 1004.1.1 DAYCARE OCCUPANCIES |
| | AT 20 SQ./ OCCUPANT. THIS LOAD WILL INCREASE THE OVER |
| | ALL OCCUPANT LOAD AND POSSIBLE PLUMBING FIXTURE COUNT. |
| | |
| | 1C) WITH THE INCREASED OCCUPANT LOAD IN CLASSROOM # 6 |
| | AND THE MULTI-PURPOSE ROOM EACH HAVING A OCCUPANT LOAD |
| | GREATER THAN 49 WILL REQUIRE 2 EXIT DOORS SEE 2010 |
| | FBC-B TABLE 1015.1. |
| | |
| | 1D) THE 2 ROOMS REQUIRING THE 2 EGRESS EXIT DOORS WILL |
| | ALSO NEED TO COMPLY WITH THE 2 DOORS BEING 1/3RD THE |
| | DIAGONAL DISTANCE APART IN EACH ROOM SEE 2010 FBC-B |
| | 1015.2.1 EXC. 2. |
| | |
| | 1E) PLEASE PROVIDE A EXPLANATION AS TO THE TERM |
| | CLASSROOM AND WHAT WILL BE TAUGHT IN EACH AREA, SEE HOW |
| | THIS TERM AFFECTS THE OCCUPANCY AND WALL RATINGS. |
| | 2010 FBC-B 313.1 SCOPE. |
| | GROUP D OCCUPANCY IS THE USE OF A BUILDING OR |
| | STRUCTURE, OR ANY PORTION THEREOF, IN WHICH THREE OR |
| | MORE CLIENTS RECEIVE CARE, MAINTENANCE AND SUPERVISION, |
| | BY OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S), |
| | FOR LESS THAN 24 HOURS PER DAY. OCCUPANCIES THAT |
| | INCLUDE PART-DAY PRESCHOOLS, KINDERGARTENS AND OTHER |
| | SCHOOLS WHOSE PURPOSE IS PRIMARILY EDUCATIONAL EVEN |
| | THOUGH THE CHILDREN ARE OF PRESCHOOL AGE SHALL COMPLY |
| | WITH THE PROVISIONS FOR GROUP E OCCUPANCIES. |
| | |
| | 1F) CORRIDOR WIDTHS WILL NEED TO BE INCREASED TO COMPLY |
| | WITH 2010 FBC-B 1018.2 CORRIDOR WIDTH. |
| | THE MINIMUM CORRIDOR WIDTH SHALL BE AS DETERMINED IN |
| | SECTION 1005.1, BUT NOT LESS THAN 44 INCHES (1118 MM). |
| | EXC. 4. SEVENTY-TWO INCHES (1829 MM)?IN GROUP E WITH A |
| | CORRIDOR HAVING A REQUIRED CAPACITY OF 100 OR MORE. |
| | |
| | 1G) CORRIDOR WALL SECTIONS DETAILS 7/A3 & DETAIL #8/A3 |
| | BOTH INDICATE THE USE OF SMOKE PARTITIONS, PLEASE SEE |
| | THE INFORMAL BOAF INTERPRETATION ON SMOKE PARTITIONS |
| | AND DRYWALL ON ONE SIDE ONLY. |
| | DATE: MON OCT 26 2009 |
| | REPORT: 6341 |
| | CODE: BUILDING CODE YEAR: 2007 |
| | SECTION: 710 |
| | QUESTION: |
| | IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING |
| | SECTION 710.4 TO ALLOW A SMOKE PARTITION TO BE |
| | CONSTRUCTED WITH ONE LAYER OF |
| | GYPSUM WALLBOARD ON ONE SIDE (THE SMOKE SIDE) OF THE |
| | PARTITION OR MUST WALLBOARD BE INSTALLED ON BOTH SIDES, |
| | EXTENDING FROM |
| | FOUNDATION OR FLOOR TO THE UNDERSIDE OF THE FLOOR OR |
| | ROOF SHEATHING, DECK OR SLAB ABOVE? |
| | COMMENT: |
| | NONE. |
| | ANSWER: |
| | YES. ONE LAYER OF GYPSUM ON ONE SIDE IS ACCEPTABLE BUT |
| | THE OTHER SIDE CANNOT REMAIN OPEN. IT MUST BE ENCLOSED |
| | WITH MATERIAL |
| | "PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION". THE |
| | WALL MUST BE ENCLOSED FROM BOTH SIDES TO PREVENT SMOKE |
| | MIGRATION FROM |
| | EITHER SIDE. THE SPACE AROUND PENETRATING ITEMS AND IN |
| | JOINTS SHALL BE FILLED WITH AN APPROVED MATERIAL TO |
| | LIMIT THE FREE PASSAGE |
| | OF SMOKE. THE WALL MAY HAVE ELECTRICAL BOXES OR OTHER |
| | PENETRATIONS THAT CAN ALLOW SMOKE TO MIGRATE FROM THE |
| | "OPEN" SIDE. |
| | COMMENTARY: |
| | SEE ALSO SECTIONS 710.2 AND 710.6. |
| | |
| | 2A) SHEET A-3 DETAIL # 9 WALL AND CEILING OF THE |
| | LAUNDRY ROOM. THE PLANS INDICATE THE USE OF THE GYPSUM |
| | ASSOC. GA-610-02, GA FILES RC2601 & FC 5406, PLEASE |
| | PROVIDE THE DOCUMENTS SO THE INSPECTOR WILL BE ABLE TO |
| | DO THEIR INSPECTIONS. 107.2.1.3 ADDITIONAL INFORMAION |
| | REQUIRED. 707.5 CONTINUITY. |
| | |
| | 2B) THIS SAME DETAIL ALSO INDICATES THE USE OF AN |
| | ALTERNANTE HORIZONTAL ASSEMBLY AER-09038 FIG. # 7. SEE |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | |
| | 2C) 707.9 DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS |
| | IN A FIRE BARRIER BY DUCTS AND AIR TRANSFER OPENINGS |
| | SHALL COMPLY WITH SECTION 716. |
| | |
| | 3) SHEET A-2 DETAIL # 10 INDICATES NEW OPENING IN A |
| | EXTERIOR CMU WALL. SHEET A-1 DOES NOT SHOW THIS DETAIL |
| | ANYWHERE. CLASSROOM # 4 DOOR # 1 DOES SHOW POSITIVE & |
| | NEGATIVE PRESSURES, ASSUMING THIS IS THE NEW DOOR. |
| | |
| | 3A) SHEET A-2 DETAIL # 10 SHOWS A NEW LINTAL BUT DOES |
| | NOT INDICATE HOW THE VERTICAL REBARS THAT ARE BEING CUT |
| | WILL MAINTAIN THE PART OF THE MAIN WIND FORCE |
| | RESISTNING SYSTEM (MWERS)? 1609.6. |
| | |
| | 3B) SHEET A1 CLASSROOM # 4 DOOR # 1 INDICATE PRESSURES |
| | PLEASE PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B |
| | 1609.6. |
| | |
| | |
| | 3C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 3D) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |