Plan Review Details - Permit 14040616
Plan Review Stops For Permit 14040616
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 09:21 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 09:07 Sent To  
Notes
2015-09-23 09:21:47BUILDING PLAN REVIEW
 W. P. B. PERMIT:14040616
 ADD: 4375 EASLEY DR.
 CONT:TBD
 TEL: ( 835-7429/ DANIEL
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 23/ 2015
 ACTION: DENIED
  
 1) NOTE THIS PERMIT IS EXPIRED, OVER 6 MONTHS WITH NO
 EXTENTIONS AND OR ACTIVITY. THE LAST REVIEW WAS
 COMPLETED ON 06/09/2014, RESUBMITTED ON 09/18/2015 OVER
 15 MONTHS OF NO ACTIVITY. PLEASE NOTE ON JUNE 30/ 2015
 THE CODE CHANGED STATWIDE TO THE 2014 FLORIDA BUILDING
 CODE, THE 5TH EDITION OF THE FLORIDA BUILDING CODE.
 PLANS WILL NEED TO BE RE-EVALUATED, THE DESIGNERS MAKE
 THE CHANGES TO THE PLANS FOR COMPLIANCE WITH THE 2014
 FBC, 5TH EDITION.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION. 105.4.1
 PERMIT INTENT. A PERMIT ISSUED SHALL BE CONSTRUED TO BE
 A LICENSE TO PROCEED WITH THE WORK AND NOT AS AUTHORITY
 TO VIOLATE, CANCEL, ALTER OR SET ASIDE ANY OF THE
 PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. EVERY PERMIT ISSUED SHALL
 BECOME INVALID UNLESS THE WORK AUTHORIZED BY SUCH
 PERMIT IS COMMENCED WITHIN 6 MONTHS AFTER ITS ISSUANCE,
 OR IF THE WORK AUTHORIZED BY SUCH PERMIT IS SUSPENDED
 OR ABANDONED FOR A PERIOD OF 6 MONTHS AFTER THE TIME
 THE WORK IS COMMENCED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-29 Cont ID  
Sent By jwitmer Date 2014-04-29 Time 17:37 Rev Time 0.00
Received By jwitmer Date 2014-04-29 Time 16:59 Sent To  
Notes
2014-04-29 17:37:26BUILDING PLAN REVIEW
 PERMIT: 14040616
 ADD: 4375 EASLEY ST
 CONT: TBD
 TEL: (561)835-7429
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 29/2014
 ACTION: DENIED
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 3) SHEET A4.1 DIVISION 9 FINISHES. INDICATES THE USE OF
 ACOUSTICAL CEILING SYSTEMS PLEASE PROVIDE COMPLIANCE
 WITH:
 808.1 ACOUSTICAL CEILING SYSTEMS.
 THE QUALITY, DESIGN, FABRICATION AND ERECTION OF METAL
 SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANEL
 CEILINGS IN BUILDINGS OR STRUCTURES SHALL CONFORM WITH
 GENERALLY ACCEPTED ENGINEERING PRACTICE, THE PROVISIONS
 OF THIS CHAPTER AND OTHER APPLICABLE REQUIREMENTS OF
 THIS CODE.
 808.1.1 MATERIALS AND INSTALLATION.
 ACOUSTICAL MATERIALS COMPLYING WITH THE INTERIOR FINISH
 REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS AND
 APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH.
 808.1.1.1 SUSPENDED ACOUSTICAL CEILINGS.
 SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND
 ASTM C 636.
  
 4) SHEET A4.1 DIVISION 9 FINISHES. PLEASE SEE USE OF
 DRYWALL IN WET AREAS, 2509.1 WET AREAS.
 SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO
 SECTIONS 1210.2 AND 1210.3.
  
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING
 BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR
 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-09 Cont ID  
Sent By dhayes Date 2014-06-09 Time 13:50 Rev Time 0.00
Received By dhayes Date 2014-06-09 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By pleduc Date 2014-04-22 Time 13:17 Rev Time 0.00
Received By pleduc Date 2014-04-22 Time 12:24 Sent To E
Notes
2014-04-22 13:17:28THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS:
  
 ON SHEET A-0.0 UNDER CODE ANALYSIS, PALM BEACH COUNTY
 FIRE DEPARTMENT IS LISTED. IT WAS HAND WRITTEN TO
 CHANGE IT WEST PALM BEACH FIRE DEPARTMENT.
  
 ON SHEET A-0.0 UNDER THE LIFE SAFETY PLAN AN EXIT PATH
 IS SHOWN TO EXIT OUT A SIDE FRONT DOOR. THERE ARE NO
 EXITS SIGN MARK THE PATH ON E-1; ADD EXIT SIGNS TO MARK
 THE PATH TO EGRESS OUT THAT DOOR.
  
 A SPRINKLER HEAD COVERAGE EVALUATION IS REQUIRED FOR
 THIS RENOVATION.
  
 ANY AND ALL WORK ON THE LIFE SAFETY SYSTEMS, FIRE ALARM
 AND SPRINKLER, SHALL BE PERMITTED THROUGH SEPARATE SHOP
 DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-23 Cont ID  
Sent By   Date 2015-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2015-09-18 Time 10:56 Sent To  
Notes
2015-09-21 10:57:08RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-09 Cont ID  
Sent By dhayes Date 2014-06-09 Time 13:58 Rev Time 0.00
Received By dhayes Date 2014-04-16 Time 09:33 Sent To  
Notes
2014-04-17 09:39:44IN C20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-14 Cont ID  
Sent By hmoser Date 2014-05-14 Time 14:45 Rev Time 0.00
Received By hmoser Date 2014-05-14 Time 14:45 Sent To  
Notes
2014-05-14 14:45:48PLAN REVIEW BY JS. PX1328

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 09:07 Sent To  
Notes
2015-09-23 09:22:07BUILDING PLAN REVIEW
 W. P. B. PERMIT:14040616
 ADD: 4375 EASLEY DR.
 CONT:TBD
 TEL: ( 835-7429/ DANIEL
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 23/ 2015
 ACTION: DENIED
  
 1) NOTE THIS PERMIT IS EXPIRED, OVER 6 MONTHS WITH NO
 EXTENTIONS AND OR ACTIVITY. THE LAST REVIEW WAS
 COMPLETED ON 06/09/2014, RESUBMITTED ON 09/18/2015 OVER
 15 MONTHS OF NO ACTIVITY. PLEASE NOTE ON JUNE 30/ 2015
 THE CODE CHANGED STATWIDE TO THE 2014 FLORIDA BUILDING
 CODE, THE 5TH EDITION OF THE FLORIDA BUILDING CODE.
 PLANS WILL NEED TO BE RE-EVALUATED, THE DESIGNERS MAKE
 THE CHANGES TO THE PLANS FOR COMPLIANCE WITH THE 2014
 FBC, 5TH EDITION.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION. 105.4.1
 PERMIT INTENT. A PERMIT ISSUED SHALL BE CONSTRUED TO BE
 A LICENSE TO PROCEED WITH THE WORK AND NOT AS AUTHORITY
 TO VIOLATE, CANCEL, ALTER OR SET ASIDE ANY OF THE
 PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. EVERY PERMIT ISSUED SHALL
 BECOME INVALID UNLESS THE WORK AUTHORIZED BY SUCH
 PERMIT IS COMMENCED WITHIN 6 MONTHS AFTER ITS ISSUANCE,
 OR IF THE WORK AUTHORIZED BY SUCH PERMIT IS SUSPENDED
 OR ABANDONED FOR A PERIOD OF 6 MONTHS AFTER THE TIME
 THE WORK IS COMMENCED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-29 Cont ID  
Sent By jwitmer Date 2014-04-29 Time 17:53 Rev Time 0.00
Received By jwitmer Date 2014-04-29 Time 17:01 Sent To  
Notes
2014-04-29 17:53:40PLUMBING PLAN REVIEW
 PERMIT: 14040616
 ADD: 4375 EASLEY ST
 CONT: TBD
 TEL: (561)835-7429
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 29/2014
 ACTION: DENIED
  
 1) SHEET A2.01 DETAIL 2 THE ACCESSIBLE RESTROOM DOES
 NOT MEET THE 2010 FL ACCESSIBILIY CODE 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2016-04-01 Cont ID  
Sent By rbrown Date 2016-04-01 Time 12:26 Rev Time 0.00
Received By rbrown Date 2016-04-01 Time 12:26 Sent To  
Notes
2016-04-01 12:30:36PERMIT APPLICATION EXTENDED TO 12/23/15

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By jroach Date 2014-06-06 Time 14:43 Rev Time 0.00
Received By jroach Date 2014-06-06 Time 14:43 Sent To  
Notes
2014-04-24 17:10:194/25/14