Plan Review Details - Permit 14040535
Plan Review Stops For Permit 14040535
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-19 Cont ID  
Sent By JWITMER Date 2014-04-19 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2014-04-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By rlecky Date 2014-04-21 Time 11:30 Rev Time 0.00
Received By rlecky Date 2014-04-21 Time 10:13 Sent To  
Notes
2014-04-21 11:31:4014040535
 854 CONNISTON RD.
 CHURCH REMODEL REVISION TO MASTER PERMIT #12090675)
  
 THE FOLLOWING NOTES WERE PLACED ON THE PLAN.
  
 PROVIDE SAFETY LABELING FOR FLASH PROTECTION. NEC
 110.22, 110.16
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
 PROVIDE AN ENGINEERING DETAIL FOR THE LIGHT POLES AND
 FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH
 WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE
 FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE
 SYSTEMS, FIRE ALARM SYSTEMS AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-05-04 Cont ID  
Sent By MGONZALE Date 2014-05-04 Time   Rev Time 1.00
Received By mgonzale Date 2014-05-04 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By pleduc Date 2014-04-24 Time 13:13 Rev Time 0.00
Received By pleduc Date 2014-04-24 Time 12:16 Sent To M
Notes
2014-04-24 13:12:57THIS PLAN WAS REVIEWED BY PETER LEDUC,FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 THE FIRE ALARM AND SPRINKLER SYSTEM SHALL BE PERMITTED
 THROUGH SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 AN ADDITIONAL EXIT SIGN IS REQUIRED IN FOYER 2 AT THE
 TURN IN THE HALLWAY INDICATING THE DIRECTION TO EGRESS
  
 IF NOT ALREADY EXISTING,EMERGENCY LIGHTING IS REQUIRED
 IN THE STAIRWAYS.
  
 FIRE INSPECTOR IS TO VERIFY EXITING/NON-EXISTING EXITS
 SIGNS IN AREAS NOT INDICATING ON THE PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By mgonzale Date 2014-05-04 Time 22:00 Rev Time 0.00
Received By jgomez Date 2014-04-15 Time 14:01 Sent To  
Notes
2014-04-15 14:07:22REVISION SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-04-28 Cont ID  
Sent By hmoser Date 2014-04-28 Time 11:38 Rev Time 0.00
Received By hmoser Date 2014-04-24 Time 14:29 Sent To  
Notes
2014-04-28 11:38:00PASS PROVISO
 1) REFER TO TABLE 401.5 SCREENS PROTECTING
 AIR INTAKE OPENING. 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-19 Cont ID  
Sent By jwitmer Date 2014-04-19 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2014-04-19 Time 12:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By eschneid Date 2014-04-22 Time 09:38 Rev Time 1.00
Received By eschneid Date 2014-04-22 Time 09:38 Sent To  
Notes
2014-04-22 09:41:35PASSED
  
 1) ALL PROVISOS FROM MAIN PERMIT (12090675) STILL
 APPLY.
  
 2) THE SITE PLAN SHOWS FEATURES THAT DO NOT COMPLY WITH
 CODE AND WILL BE REVIEWED AS PART OF THEIR RESPECTIVE
 PERMIT. EXAMPLY - DUMPSTER ENCLOSURE LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-04-21 11:43:194/21/14