Plan Review Details - Permit 14040502
Plan Review Stops For Permit 14040502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 18:00 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 17:00 Sent To  
Notes
2014-05-02 18:00:22BUILDING PLAN REVIEW
 PERMIT: 14040502
 ADD: 3114 TUXEDO AVE.
 CONT: TBD
 TEL: (561)799-3700
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 02/ 2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE CHANGE OF
 OCCUPANCY, IT IS MORE A CHANGE OF USE AND MATERIALS.
 THE HANDLING OF THEM AND STORING THEM AS WELL.
  
 THE TYPES OF MATERIALS THAT YOUR FIRM WILL BE STORING
 AND PROCESSING IS VARIOUS METALS. FORKLIFTS WILL BE
 USED IN MOVING TTHE METALS AROUND THE SITE. WHAT TYPE
 OF FUEL DOES THE FORK LIFTS USE? IF GASOLINE WHAT TPE
 OF STORAGE CONTAINMENT IS USED TO CREATE CONTROL AREA.
 2010 FBC-B TABLE 307.1(2)
 MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF
 HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD
 WILL ALLOW 30 GALLONS OF GASOLINE TO BE STORED IN
 APPROVED CONTAINERS AND NOT BE CONSIDERED A HAZORDOUS
 OCCUPANCY.
 FOOTNOTE (B) .THE AGGREGATE QUANTITY IN USE AND STORAGE
 SHALL NOT EXCEED THE QUANTITY LISTED FOR STORAGE
 FOOTNOTE (P.) THE FOLLOWING SHALL NOT BE INCLUDED IN
 DETERMINING THE MAXIMUM ALLOWABLE QUANTITIES:
 1. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON VEHICLES.
 2. LIQUID OR GASEOUS FUEL IN FUEL TANKS ON MOTORIZED
 EQUIPMENT OPERATED IN ACCORDANCE WITH THIS CODE.
 3. GASEOUS FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES
 REGULATED BY THE FLORIDA BUILDING CODE, FUEL GAS.
 4. LIQUID FUELS IN PIPING SYSTEMS AND FIXED APPLIANCES
 REGULATED BY THE FLORIDA BUILDING CODE, MECHANICAL.
 FOOTNOTE (M) FOR GALLONS OF LIQUIDS, DIVIDE THE AMOUNT
 IN POUNDS BY 10 IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE
 FOOTNOTE (F) . MAXIMUM ALLOWABLE QUANTITIES SHALL BE
 INCREASED 100 PERCENT WHEN STORED IN APPROVED STORAGE
 CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES AS
 SPECIFIED IN THE FLORIDA FIRE PREVENTION CODE. WHERE
 NOTE E ALSO APPLIES, THE INCREASE FOR BOTH NOTES SHALL
 BE APPLIED ACCUMULATIVELY.
  
 2) WILL THERE BE CUTTING OF ALLUMINUM AND MAGNESIUM?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By albarran Date 2014-05-07 Time 15:26 Rev Time 0.00
Received By albarran Date 2014-05-07 Time 15:07 Sent To I
Notes
2014-05-07 15:25:11ELECTRICAL PLAN REVIEW COMMENTS
 PERMIT 14040502
  
 1.YOU SHALL PROVIDE A SINGLE SHEET SITE PLAN INDICATING
 THE LOCATION OF ELECTRIC UTILITIES AND THE RESPECTIVE
 ELECTRICAL SERVICE FOR EACH BLDG. THIS SHALL BE DONE
 WITH AN ELECTRICAL RISER DIAGRAM.
 2. EACH BLDG SHALL HAVE THE REQUIRED ILLUMINATION PER
 BOTH, THE FBC & THE NEC
 3. EACH BLDG. SHALL HAVE ALL THE EXITS PROPERLY
 IDENTIFIED AND ILLUMINATED.
 4. YOU SHALL SUBMIT A PANEL SCHEDULE WITH THE
 CORRESPONDING LOAD CALCS.
 5. ALL LIGHTING SHALL ADHERE TO THE REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION CODE
 6. NOTATION AS TO THE TYPE AND QUANTITIES OF ANY
 HAZARDOUS MATERIALS BEING STORED IF ANY SHALL BE
 INDICATED.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By wjolin Date 2014-04-24 Time 15:43 Rev Time 0.00
Received By wjolin Date 2014-04-24 Time 14:25 Sent To  
Notes
2014-04-24 15:42:523114 TUXEDO AVENUE
 PERMIT #14040502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL STORAGE AND STORAGE ACTIVITIES SHALL COMPLY WITH
 THE FLORIDA FIRE PREVENTION CODE 2010 EDITION.
  
 PLEASE INDICATE THE HOURS OF OPERATION FOR THE
 RECYCLING FACILITY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 BUILDING SKETCH #2 INDICATES TWO STORAGE AREAS AND A
 CLOSET; HOWEVER, THE OTHER 50% OF THE FLOOR SPACE IS
 NOT DESIGNATED WITH A USE.
  
 ALL EXISTING EXIT DOORS SHALL BE PROVIDED WITH
 ILLUMINATED EXIT SIGNS.
  
 BUILDING #5 NARRATIVE INDICATES A PROPOSED STORAGE
 HEIGHT OF LESS THAN 15 FEET. THE FIRE CODE REQUIRES
 HIGH-PILED STORAGE (12 FEET OR HIGHER) OF 2,500 SQ.FT.
 OR MORE TO BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-07 Cont ID  
Sent By albarran Date 2014-05-07 Time   Rev Time 0.00
Received By albarran Date 2014-04-14 Time 06:49 Sent To PC
Notes
2014-05-07 15:30:45FAILED ALL PREVIOUS REVIEWS. PROCESSED & EMAILED JOHN
 WITH STATUS AND ROUTED TO SMALL DENIED "R"
2014-04-15 06:49:49INCOMING SENT TO C12 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 18:00 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 18:00 Sent To  
Notes
2014-05-02 18:00:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 18:01 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 18:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 18:00 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 18:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-04-22 Cont ID  
Sent By jroach Date 2014-04-22 Time 10:09 Rev Time 0.00
Received By jroach Date 2014-04-21 Time 16:05 Sent To  
Notes
2014-04-22 10:10:36PURSUANT TO SECTION 94-444(C) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS, OUTDOOR STORAGE SHALL NOT
 BE PERMITTED UNLESS ENCLOSED ON ALL SIDES BY A WALL OF
 ADEQUATE HEIGHT CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD OR STEEL. WALL OPENINGS SHALL HAVE
 OBSCURING GATES. ALL AREAS FOR THE STORAGE AND DISPOSAL
 OF GOODS, MERCHANDISE, AND MATERIALS SHALL BE COVERED
 WITH EITHER ASPHALT OR CONCRETE PAVING, OR CRUSHED ROCK
 OF SUCH SPECIFICATION AND DESIGN AS REQUIRED BY THE
 ENGINEERING DEPARTMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT (561) 822-1448 OR VIA EMAIL AT
 [email protected]