Plan Review Details - Permit 14040467
Plan Review Stops For Permit 14040467
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2014-04-17 Time 15:36 Sent To  
Notes
2014-04-17 15:53:26BUILDING PLAN REVIEW
 PERMIT: 14040467
 ADD: 1715 PALM BEACH LAKES/ TEMP OFICE MANUFACTURED
 BLDG
 CONT: DEERFIELD CONSTRUCTION
 TEL: (13)984-4096
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY APRIL 17/2014
 ACTION: DENIED
  
 1) MANUFACTURED BUILDINGS (553.37(2)(D), FLORIDA
 STATUTES, REQUIRES THE DEPARTMENT OF COMMUNITY AFFAIRS)
 ARE UNDER THE STATE MODULAR PROGRAM STATE APPROVED
 PLANS FOR THE BUILDING ARE REQUIRED (2) COPIES THEY DO
 NOT NEED TO BE SIGNED AND SEALED., ONLY THE APPROVAL
 STAMP. THE TIE DOWN IS SITE SPECIFIC AND WILL NEED TO
 BE SIGNED AND SEALED 2 SETS OF PLANS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 13:04 Rev Time 0.00
Received By rlecky Date 2014-05-01 Time 13:03 Sent To  
Notes
2014-05-01 13:05:2714040467
 1715 PALM BEACH LAKES BLVD.
 TEMPORARY OFFICE TRAILER
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRIC PERMIT WITH PLANS FOR THE
 ELECTRICAL SERVICE CONNECTION OF THE TRAILER. NEC 215.5
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-04-21 Cont ID  
Sent By scaldero Date 2014-04-21 Time 15:10 Rev Time 0.00
Received By scaldero Date 2014-04-21 Time 15:10 Sent To  
Notes
2014-04-21 15:14:04PERMIT # 14040467
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***INDICATE DISTANCE FROM RED ROBIN STRUCTURE AND ANY
 OTHER RELEVANT STRUCTURES.***
  
 PER NFPA 241 ? STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2
 TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM
 ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET.
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET.
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET.
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET.
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 60 FEET.
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 *SEE ALSO BUILDING DEPT. COMMENTS.***
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 09:14 Rev Time 0.00
Received By eschneid Date 2014-04-14 Time 06:45 Sent To  
Notes
2014-04-15 06:46:57INCOMING SENT TO C15 BOX. JW

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 09:57 Sent To  
Notes
2014-05-02 09:57:44PLUMBING PLAN REVIEW
 PERMIT: 14040467
 ADD: 1715 PALM BEACH LAKES/ TEMP OFICE MANUFACTURED
 BLDG
 CONT: DEERFIELD CONSTRUCTION
 TEL: (13)984-4096
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY APRIL 17/2014
 ACTION: DENIED
  
 1) MANUFACTURED BUILDINGS (553.37(2)(D), FLORIDA
 STATUTES, REQUIRES THE DEPARTMENT OF COMMUNITY AFFAIRS)
 ARE UNDER THE STATE MODULAR PROGRAM STATE APPROVED
 PLANS FOR THE BUILDING ARE REQUIRED (2) COPIES THEY DO
 NOT NEED TO BE SIGNED AND SEALED., ONLY THE APPROVAL
 STAMP. THE TIE DOWN IS SITE SPECIFIC AND WILL NEED TO
 BE SIGNED AND SEALED 2 SETS OF PLANS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 09:13 Rev Time 0.25
Received By eschneid Date 2014-05-06 Time 09:13 Sent To  
Notes
2014-04-21 15:09:254/21/14