Plan Review Details - Permit 14040460
Plan Review Stops For Permit 14040460
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2014-08-28 Cont ID  
Sent By skennedy Date 2014-08-28 Time 12:39 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-07-16 10:28:26NEED ADDRESS FOR BUILDING LOCATED FACING DOBBINS
 STREET. SEE RESPONSE FROM SCOTT BELOW. JG.
  
 GOOD MORNING SCOTT,
 THERE ARE TWO BUILDINGS IN THIS LOT. ONE IS FACING
 GARDEN AVE AND THE OTHER ONE IS FACING DOBBINS ST. CAN
 YOU PLEASE PROVIDE AN ADDRESS FOR THE BUILDING FACING
 DOBBINS STREET. ON THE DRAWINGS SUBMITTED UNDER PERMIT
 #14040460 THE PLANS SHOW WINDOWS REPLACEMENT FOR
 BUILDING 651 DOBBINS STREET. IS THIS A CORRECT ADDRESS.
 PAPA DOESN'T RECOGNIZE THIS ADDRESS.
 THANK YOU FOR YOUR DILIGENCE.
  
  
  
 JULIO,
 651 DOBBINS ST IS THE CORRECT AND VALID ADDRESS FOR
 THAT BUILDING AND I DID VERIFY THAT IT IS IN THE PALM
 BEACH COUNTY SYSTEM. PAPA CAN BE A BIT DECEPTIVE IN
 THAT IT DOESN'T SHOW ALL OF THE ADDRESSES FOR A PARCEL.
 ONLY THE ONE DESIGNATED AS PRIMARY IS DISPLAYED, IN
 THIS CASE 4518 GARDENS AVE.
  
 SCOTT ALEF
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 401 CLEMATIS ST., WEST PALM BEACH, FL 33401
 PHONE: 561-494-1094
 EMAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-08-28 Cont ID  
Sent By skennedy Date 2014-08-28 Time 12:39 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-08-04 Cont ID  
Sent By jgomez Date 2014-08-04 Time 08:59 Rev Time 0.00
Received By jgomez Date 2014-08-04 Time 08:59 Sent To  
Notes
2014-08-04 09:06:54RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ROBERT BROWN CALLED MIGUEL DEAVILA ON 7/28/14 TO
 EXPLAIN TO HIM WHAT WE NEED TO FINISH PROCESSING THE
 PERMIT. AFTER RESUBMITTAL ON 7/31/14 THE SAME ITEMS ARE
 NOT ADDRESSED:
  
 1- ALL DRAWINGS NEED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. FOUR TIMES)
  
 ****NOTE: THIS IS THE FOURTH TIME THIS IS BEING
 REQUESTED. ONLY A COUPLE OF DRAWINGS WERE RESUBMITTED
 WITH THE DESIGNER'S NAME AND SIGNATURE. ALL THE
 DRAWINGS NEED TO HAVE THE DESIGNERS NAME AND SIGNATURE.
 THE DRAWINGS SUBMITTED FOR THE ROOF BUILT UP ARE STILL
 MISSING THE NAME AND SIGNATURE OF THE DESIGNER.
  
 2- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING. (REPEAT COMMENT. FIVE TIMES).
  
 ****NOTE: THIS IS THE FIFTH TIME THIS IS BEING
 REQUESTED.
  
  
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-07-28 Cont ID  
Sent By jgomez Date 2014-07-28 Time 17:20 Rev Time 0.00
Received By jgomez Date 2014-07-28 Time 17:20 Sent To  
Notes
2014-07-28 17:27:39 
 7-28-14: ROBERT BROWN CALLED MR. MIGUEL DEAVILA TO
 EXPLAIN TO HIM WHAT WE NEED FROM HIM TO FINISH
 PROCESSING THE PERMIT. THE FOLLOWING ARE THE REQUIRED
 ITEMS:
  
  
 1- ALL DRAWINGS NEED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-07-15 Cont ID  
Sent By jgomez Date 2014-07-15 Time 13:32 Rev Time 0.00
Received By jgomez Date 2014-07-15 Time 13:32 Sent To  
Notes
2014-07-15 14:02:34RESIDENTIAL (R3) ALTERATIONS, BUILDING REVIEW SECOND
 CHECKLIST.
 CODE: 2010 FBC.
  
  
 1- ALL DRAWINGS NEED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 **** RESPONSE TO INFORMATION SUBMITTED.
 NOT ALL DRAWINGS HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. RESUBMIT ALL
 DRAWINGS WITH THE DESIGNER'S NAME AND SIGNATURE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED
 FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY
 REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL.
 UNABLE TO VERIFY IF IT WAS APPROVED OR NOT.
  
 ****RESPONSE TO INFORMATION SUBMITTED:
  
 REPORT NO 2031 SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER. ALL THE FLORIDA PRODUCT APPROVALS HAVE
 A NUMBER. THIS REPORT NEEDS NEEDS THE FLORIDA PRODUCT
 APPROVAL NUMBER IN ORDER TO VERIFY STATUS. PROVIDE THE
 FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO
 THIS DOOR REPORT. IF THERE IS NOT FLORIDA PRODUCT
 APPROVAL NUMBER, THEN, DOOR MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING ALL THE REQUIRED
 DOCUMENTATION TO THE LOCAL BUILDING OFFICIAL FOR
 APPROVAL.
  
 3- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING.
  
 **** RESPONSE TO INFORMATION SUBMITTED:
 THERE IS NOT INFORMATION GIVEN ON THE TYPE AND SIZE OF
 THE EXISTING BEDROOM WINDOW #2. IT ONLY GIVES THE SIZE
 AND TYPE OF THE PROPOSED WINDOW. UNABLE TO VERIFY
 COMPLIANCE WITH THE BEDROOM EGRESS REQUIREMENTS OF SEC.
 604.1 OF 2010 FBC-EXISTING BUILDING. IN ADDITION,
 CLARIFY WHY WINDOW SCHEDULE SHOWS WINDOW #1 AS "IMPACT
 EGRESS". WINDOW #1 IS LOCATED IN THE LIVING ROOM AND IS
 NOT REQUIRED TO HAVE EGRESS WINDOWS. IS THE IMPACT
 EGRESS WINDOW MEANT TO BE THE ONE IN THE BEDROOM?.
 REVISE WINDOW SCHEDULE AS REQUIRED.
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-10 Cont ID  
Sent By jgomez Date 2014-06-10 Time 17:12 Rev Time 0.00
Received By jgomez Date 2014-06-10 Time 17:11 Sent To  
Notes
2014-06-10 17:15:07 
 ****** REVISION TO THE ORIGINAL CHECKLIST DATED 5/28/14
 *****
  
  
 RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 (REVISED):
 CODE: 2010 FBC.
  
 1- ENERGY CALCULATIONS NO REQUIRED AT THIS TIME.
 ENERGY CALCULATIONS WERE REQUESTED THE FIRST TIME
 BECAUSE PLANS SUBMITTED WERE NOT CLEAR. PLANS SHOW
 FRAMING FOR A NEW ROOF THAT WAS ALREADY BUILT AND RED
 TAGGED BY THE BUILDING INSPECTOR FOR BUILDING WITHOUT
 PERMIT. DRAWINGS SUBMITTED DON'T SHOW AN EXISTING
 CONDITION AND A PROPOSED CONDITION. THIS BUILDING WAS
 BUILT IN 1952 AND ACCORDING TO CITY RECORDS THERE ARE
 NOT BUILDING PERMITS FOR THIS PROPERTY. THEREFORE, IT
 WAS MY IMPRESSION THAT ROOF WAS DAMAGED OVER THE YEARS
 AND THAT'S WHY IT WAS REPAIRED/REBUILT.
 SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 2- ROOF BUILT UP: ENGINEERING ANALYSIS NOT REQUIRED AT
 THIS TIME.
 ENGINEERING ANALYSIS WAS REQUESTED THE FIRST TIME
 BECAUSE OF THE SAME REASON EXPLAINED ON ITEM #1 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- DESIGNER TO REVISE INFORMATION ON SHEET 6.0
 A) REVISE DIMENSION "A". ACCORDING TO FOOTNOTE ON
 FIGURE R301.2(7) THE MINIMUM DIMENSION FOR "A" IS 4'-0"
 NOT 3'-0".
  
 B) REVISE THE DESIGN CRITERIA: CURRENT ASCE EDITION
 THAT CORRESPONDS TO FBC 2010 IS ASCE 7-10 NOT ASCE
 7-05. (SEE CHAPTER 43: REFERENCED STANDARDS FOR CURRENT
 EDITION).
  
 4- ALL DRAWINGS NEED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES. UPDATE THE
 VALUATION AS REQUIRED TO INCLUDE THE ROOF BUILT UP,
 REPLACEMENT OF DOOR AND WINDOWS, AND DESIGNER FEES.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. (NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR).
  
 B) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED
 FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY
 REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL.
 UNABLE TO VERIFY IF IT WAS APPROVED OR NOT.
  
 7- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING.
  
 B) SHEET 4.0: CURRENT ASCE EDITION THAT CORRESPONDS TO
 FBC-2010 IS ASCE 7-10 NOT ASCE 7-05. REVISE AS
 REQUIRED. (SEE CHAPTER 43: REFERENCED STANDARDS FOR
 CURRENT EDITION).
  
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-29 Cont ID  
Sent By JGOMEZ Date 2014-05-28 Time 17:48 Rev Time 0.00
Received By jgomez Date 2014-05-28 Time 17:01 Sent To  
Notes
2014-05-28 17:49:08RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- ROOF BUILT UP:
 PROVIDE SIGNED AND SEALED STRUCTURAL EVALUATION BY
 DESIGN PROFESSIONAL AS REQUIRED BY SEC. 506.2.2.1 OF
 2010 FBC-EXISTING BUILDING. DESIGN PROFESSIONAL TO
 PROVIDE STRUCTURAL ANALYSIS SHOWING THAT PROPOSED
 STRUCTURAL MEMBERS AND CONNECTORS SPECIFIED ON PLANS
 SUBMITTED WILL MEET THE LATERAL AND UPLIFT LOADS
 REQUIRED BY SEC. R301 OF 2010 FBC.
  
 3- DESIGN PROFESSIONAL TO REVISE INFORMATION ON SHEET
 6.0
 A) REVISE THE ROOF ZONES ON THE GABLE ROOF PLAN. THE
 WHOLE GABLE END FOR A MINIMUM DISTANCE OF 5'-0" IS
 CONSIDERED ROOF ZONE #3. SEE FIGURE R803.2.3.1 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 B) REVISE THE DESIGN CRITERIA: CURRENT ASCE EDITION
 THAT CORRESPONDS TO FBC 2010 IS ASCE 7-10 NOT ASCE
 7-05.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES. UPDATE THE
 VALUATION AS REQUIRED TO INCLUDE THE ROOF BUILT UP,
 REPLACEMENT OF DOOR AND WINDOWS, DESIGN PROFESSIONAL
 FEES.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. (NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR).
  
 B) EXTERIOR DOORS. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED
 FROM JELD WEN. DRAWINGS SUBMITTED DON'T HAVE ANY
 REFERENCE TO THE APPROVED FLORIDA PRODUCT APPROVAL.
 UNABLE TO VERIFY IF IT WAS APPROVED OR NOT.
  
 6- WINDOW AND DOOR REPLACEMENT DRAWINGS SUBMITTED:
 A) SHEET 3.0: SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOW #2 TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604.1 OF 2010 FBC-EXISTING
 BUILDING.
  
 B) SHEET 4.0: CURRENT ASCE EDITION THAT CORRESPONDS TO
 FBC-2010 IS ASCE 7-10 NOT ASCE 7-05. REVISE AS
 REQUIRED.
  
 *** PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-04-30 Cont ID  
Sent By albarran Date 2014-04-30 Time 19:17 Rev Time 0.00
Received By albarran Date 2014-04-30 Time 19:17 Sent To  
Notes
2014-04-30 19:28:05ACCORDING TO THE SCOPE OF WORK AS DESCRIBED ON THE
 PERMITS, THERE ARE NO ELECTRICAL REQUIREMENTS OTHER
 THAN FOR
 SMOKE DETECTORS AS PER
 FBC-EXISTING SECTION 704.4.3
 SHALL BE REQUIRED
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-08-04 Cont ID  
Sent By jgomez Date 2014-08-04 Time 09:25 Rev Time 0.00
Received By jgomez Date 2014-07-31 Time 08:58 Sent To  
Notes
2014-08-04 08:58:58RESUBMITTAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-28 Cont ID  
Sent By jgomez Date 2014-07-28 Time 17:19 Rev Time 0.00
Received By jgomez Date 2014-07-21 Time 17:19 Sent To  
Notes
2014-07-28 17:19:54RE-SUBMITTAL SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-15 Cont ID  
Sent By jgomez Date 2014-07-15 Time 17:06 Rev Time 0.00
Received By jgomez Date 2014-07-03 Time 10:09 Sent To  
Notes
2014-07-03 10:09:47INCOMING SENT TO J. GOMEZ . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-10 Cont ID  
Sent By jgomez Date 2014-06-10 Time 17:12 Rev Time 0.00
Received By jgomez Date 2014-06-10 Time 17:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-28 Cont ID  
Sent By jgomez Date 2014-05-28 Time 17:49 Rev Time 0.00
Received By jgomez Date 2014-04-14 Time 06:33 Sent To  
Notes
2014-04-15 06:34:17INCOMING SENT TO R07 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-15 Cont ID  
Sent By skennedy Date 2014-05-15 Time 07:23 Rev Time 0.00
Received By skennedy Date 2014-05-15 Time 07:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-05-15 Cont ID  
Sent By skennedy Date 2014-05-15 Time 07:23 Rev Time 0.00
Received By skennedy Date 2014-05-15 Time 07:23 Sent To  
Notes
2014-05-15 07:24:56ASSIGNED TO JGOMEZ TO COMPLETE

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-06-03 Cont ID  
Sent By jgomez Date 2014-05-28 Time 10:00 Rev Time 0.00
Received By jgomez Date 2014-05-28 Time 10:00 Sent To  
Notes
2014-06-03 10:01:04SHINGLES NOA 13-1104.12 SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status N Date 2014-04-22 Cont ID  
Sent By llouie Date 2014-04-22 Time 15:22 Rev Time 0.00
Received By llouie Date 2014-04-22 Time 15:22 Sent To  
Notes
2014-04-22 15:23:234/22/14 - 2014 VALUE OF CONSTRUCTION (TO DATE) DOES NOT
 EXCEED 50 PERCENT OF THE VALUE OF THE STRUCTURE. LL
  
  
2014-04-21 15:11:114/21/14