| Plan Review Stops For Permit 14040385 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-26 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-26 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-05-15 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-15 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-15 |
Time |
09:48 |
Sent To |
M |
|
| Notes |
| 2014-05-15 11:28:06 | ELECTRICAL PROVISOS FOR PERMIT #14040385 | | | 1. THOUGH ENERGY CODE COMPLIANCE MAY BE WAIVED DUE TO | | | THE TEMPORARY NATURE OF THE PROJECT, PROPER EMERGENCY & | | | EXIT LIGHTING REQUIREMENTS CAN?T BE WAIVED AND WILL BE | | | EXPECTED FOR FINAL INSPECTIONS. | | | 2. AS PER NEC 210.8(B), ALL 125 V 15 & 20 AMP | | | SINGLE-PHASE RECEPTACLES IN KITCHENS SHALL BE GFCI | | | PROTECTED. | | | 3. PANEL SHALL BE LABELED AS PER NEC 110.16. | | | 4. MAKE SURE THAT THE SERVICE OUTLET OR THE DISCONNECT | | | FOR THE CONDENSING UNITS ARE NOT BLOCKED AS PER NEC | | | 110.26(A) | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY TO SEE | | | IF THERE ARE ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-04-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-11 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-11 |
Time |
10:21 |
Sent To |
B |
|
| Notes |
| 2014-04-11 11:59:31 | IN ADDITION TO THE SUBMITTED DRAWINGS, A LIGHTING SHEET | | | COMPLIANT WITH FBC-E SECTION 505 SHALL BE PROVIDED FOR | | | APPROVAL | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-04-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-04-24 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-21 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2014-04-21 13:16:14 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | | WITH THE FOLLOWING COMMENT. | | | | | | THE FIRE SUPPRESSION SYSTEM WORK SHALL BE SUBMITTED | | | UNDER SEPARATE SHOP DRAWINGS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2014-05-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-17 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-17 |
Time |
06:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-05-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-26 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-04-26 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2014-05-17 06:24:36 | REVIEW BY JWITMER | | 2014-04-26 07:08:14 | FUEL GAS PLAN REVIEW | | | PERMIT: 14040385 | | | ADD: 8225 IBIS | | | CONT: TBD | | | TEL: (561)723-2623/ LARRY ZUBIK | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SAT. APRIL 26/2014 | | | ACTION: DENIED | | | | | | GAS PERMIT APPLICATION REQUIREMENTS | | | LACKING INFORMATION TO BE ABLE TO DO A GAS PLAN REVIEW. | | | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2010 FUEL GAS. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2010 FUEL GAS CODE SEC. 304 | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2010 FUEL GAS SEC. 402.2 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-05-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-17 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-15 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2014-05-16 09:01:18 | ****EXPEDITED**** | | | ON HM DESK | | | | | 2014-05-15 09:21:02 | ****EXPEDITED**** | | | ROUTED TO MA DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-07 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-04-09 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2014-04-10 13:36:55 | SENT TO B5 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-05-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-16 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-05-16 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2014-05-16 15:06:13 | PASS PROVISO | | | REFER TO SECTION 306.5.1 SLOPED ROOFS. | | | FIRE SUPPRESSION REQUIRES SEPARATE | | | APPLICATION AND PLANS. | | | PLAN REVIEW BY JS. PX1328 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-07 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-05-07 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2014-05-07 09:32:22 | PLAN DENIED | | | 1) REFER TO SECTION 306.5.1 SLOPED ROOFS. 2010 FBC (M) | | | 2) REFER TO SECTION 506.3.12.1 TERMINATION ABOVE THE | | | ROOF | | | 2010 FBC (M) | | | 3) SEPARATE APPLICATION PLAN AND PERMIT REQUIRED FOR | | | FIRE SUPPRESSION. PER SECTION 107 FBC 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-05-22 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-05-22 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2014-05-22 15:27:27 | PLUMBING PASSED DELETION OF A STEAM GENERAOR. JW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-26 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-26 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2014-04-26 07:23:19 | PLUMBING PLAN REVIEW | | | PERMIT: 14040385 | | | ADD: 8225 IBIS | | | CONT: TBD | | | TEL: (561)723-2623/ LARRY ZUBIK | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SAT. APRIL 26/2014 | | | ACTION: DENIED | | | | | | 1) THE PLANS DO NOT INDICATE THE AADDITION, DELETIONOF | | | ANY PLUMBING FIXTURES, SHEET PL201 DOES HAVE A DETAIL | | | OF STEAM GENERATOR, PLEASE PROVIDE IF THIS UNIT IS GAS | | | OR ELECTRIC? WHAT THIS UNIT IS TO BE USED FOR? CLEANING | | | OF GREASY WASTE FROM KITCHEN APPLIANCES OR FOR A DISH | | | OR GLASS WASHER? 107.2.1.3. ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | IF THIS STEAM GENERATOR IS TO BE USED IN CLEANING WITH | | | A COMMERCIAL DISH OR GLASS WASHER ONE CONCERN WILL BE | | | COMPLIANCE WITH 2010 FBC-PLUMBING 701.7 CONNECTIONS. | | | DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP | | | PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE | | | SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING | | | DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER | | | THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST, | | | APPROVED COOLING METHODS SHALL BE PROVIDED. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-04-17 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2014-04-17 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2014-04-17 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2014-04-14 11:31:53 | 4/14/14 |
|
|