Plan Review Details - Permit 14040385
Plan Review Stops For Permit 14040385
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 06:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-15 Cont ID  
Sent By albarran Date 2014-05-15 Time 11:10 Rev Time 0.00
Received By albarran Date 2014-05-15 Time 09:48 Sent To M
Notes
2014-05-15 11:28:06ELECTRICAL PROVISOS FOR PERMIT #14040385
 1. THOUGH ENERGY CODE COMPLIANCE MAY BE WAIVED DUE TO
 THE TEMPORARY NATURE OF THE PROJECT, PROPER EMERGENCY &
 EXIT LIGHTING REQUIREMENTS CAN?T BE WAIVED AND WILL BE
 EXPECTED FOR FINAL INSPECTIONS.
 2. AS PER NEC 210.8(B), ALL 125 V 15 & 20 AMP
 SINGLE-PHASE RECEPTACLES IN KITCHENS SHALL BE GFCI
 PROTECTED.
 3. PANEL SHALL BE LABELED AS PER NEC 110.16.
 4. MAKE SURE THAT THE SERVICE OUTLET OR THE DISCONNECT
 FOR THE CONDENSING UNITS ARE NOT BLOCKED AS PER NEC
 110.26(A)
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY TO SEE
 IF THERE ARE ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-11 Cont ID  
Sent By albarran Date 2014-04-11 Time 11:56 Rev Time 0.00
Received By albarran Date 2014-04-11 Time 10:21 Sent To B
Notes
2014-04-11 11:59:31IN ADDITION TO THE SUBMITTED DRAWINGS, A LIGHTING SHEET
 COMPLIANT WITH FBC-E SECTION 505 SHALL BE PROVIDED FOR
 APPROVAL
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By wjolin Date 2014-04-24 Time 12:43 Rev Time 0.00
Received By wjolin Date 2014-04-21 Time 13:13 Sent To  
Notes
2014-04-21 13:16:14THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENT.
  
 THE FIRE SUPPRESSION SYSTEM WORK SHALL BE SUBMITTED
 UNDER SEPARATE SHOP DRAWINGS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 06:24 Rev Time 0.00
Received By skennedy Date 2014-05-17 Time 06:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-05-17 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 07:09 Rev Time 0.00
Received By skennedy Date 2014-04-26 Time 06:34 Sent To  
Notes
2014-05-17 06:24:36REVIEW BY JWITMER
2014-04-26 07:08:14FUEL GAS PLAN REVIEW
 PERMIT: 14040385
 ADD: 8225 IBIS
 CONT: TBD
 TEL: (561)723-2623/ LARRY ZUBIK
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. APRIL 26/2014
 ACTION: DENIED
  
 GAS PERMIT APPLICATION REQUIREMENTS
 LACKING INFORMATION TO BE ABLE TO DO A GAS PLAN REVIEW.
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 06:24 Rev Time 0.00
Received By skennedy Date 2014-05-15 Time 09:20 Sent To  
Notes
2014-05-16 09:01:18****EXPEDITED****
 ON HM DESK
  
2014-05-15 09:21:02****EXPEDITED****
 ROUTED TO MA DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-07 Cont ID  
Sent By hmoser Date 2014-05-07 Time 09:33 Rev Time 0.00
Received By hmoser Date 2014-04-09 Time 13:36 Sent To  
Notes
2014-04-10 13:36:55SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-05-16 Cont ID  
Sent By hmoser Date 2014-05-16 Time 14:50 Rev Time 0.00
Received By hmoser Date 2014-05-16 Time 14:10 Sent To  
Notes
2014-05-16 15:06:13PASS PROVISO
 REFER TO SECTION 306.5.1 SLOPED ROOFS.
 FIRE SUPPRESSION REQUIRES SEPARATE
 APPLICATION AND PLANS.
 PLAN REVIEW BY JS. PX1328

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By hmoser Date 2014-05-07 Time 09:15 Rev Time 0.00
Received By hmoser Date 2014-05-07 Time 09:15 Sent To  
Notes
2014-05-07 09:32:22PLAN DENIED
 1) REFER TO SECTION 306.5.1 SLOPED ROOFS. 2010 FBC (M)
 2) REFER TO SECTION 506.3.12.1 TERMINATION ABOVE THE
 ROOF
 2010 FBC (M)
 3) SEPARATE APPLICATION PLAN AND PERMIT REQUIRED FOR
 FIRE SUPPRESSION. PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-22 Cont ID  
Sent By jwitmer Date 2014-05-22 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2014-05-22 Time 15:26 Sent To  
Notes
2014-05-22 15:27:27PLUMBING PASSED DELETION OF A STEAM GENERAOR. JW

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 07:23 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 06:46 Sent To  
Notes
2014-04-26 07:23:19PLUMBING PLAN REVIEW
 PERMIT: 14040385
 ADD: 8225 IBIS
 CONT: TBD
 TEL: (561)723-2623/ LARRY ZUBIK
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. APRIL 26/2014
 ACTION: DENIED
  
 1) THE PLANS DO NOT INDICATE THE AADDITION, DELETIONOF
 ANY PLUMBING FIXTURES, SHEET PL201 DOES HAVE A DETAIL
 OF STEAM GENERATOR, PLEASE PROVIDE IF THIS UNIT IS GAS
 OR ELECTRIC? WHAT THIS UNIT IS TO BE USED FOR? CLEANING
 OF GREASY WASTE FROM KITCHEN APPLIANCES OR FOR A DISH
 OR GLASS WASHER? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 IF THIS STEAM GENERATOR IS TO BE USED IN CLEANING WITH
 A COMMERCIAL DISH OR GLASS WASHER ONE CONCERN WILL BE
 COMPLIANCE WITH 2010 FBC-PLUMBING 701.7 CONNECTIONS.
 DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP
 PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE
 SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING
 DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER
 THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST,
 APPROVED COOLING METHODS SHALL BE PROVIDED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-17 Cont ID  
Sent By avann Date 2014-04-17 Time 13:44 Rev Time 0.00
Received By ajones Date 2014-04-17 Time 13:44 Sent To  
Notes
2014-04-14 11:31:534/14/14