Plan Review Details - Permit 14040381
Plan Review Stops For Permit 14040381
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-04-22 Cont ID  
Sent By jgomez Date 2014-04-22 Time 14:26 Rev Time 0.00
Received By jgomez Date 2014-04-22 Time 14:26 Sent To  
Notes
2014-04-22 14:28:57RESIDENTIAL (R3) REROOF, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF (DCA RULE 9N-3):
 A) NOA 13-0424.14 SUBMITTED ALSO REQUIRES SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR THE NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
 PROVIDE 2 SIGNED AND SEALED RAS 117 CALCULATIONS.
  
 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT. (2 COPIES).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-21 Cont ID  
Sent By jgomez Date 2014-04-21 Time 13:43 Rev Time 0.00
Received By jgomez Date 2014-04-21 Time 13:43 Sent To  
Notes
2014-04-21 13:50:18RESIDENTIAL (R3) REROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF (DCA RULE 9N-3):
 A) NOA 13-0204.03 APPROVED ASSEMBLY SUBMITTED REQUIRES
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL. PROVIDE 2 SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
 B) NOA 13-0204.03 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. PROVIDE 2
 COPIES.
  
 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT. (2 COPIES).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By jgomez Date 2014-04-14 Time 10:03 Rev Time 0.00
Received By jgomez Date 2014-04-14 Time 09:49 Sent To  
Notes
2014-04-14 10:37:32RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF:
 A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3. NONE SUBMITTED AT THIS TIME.
  
 B) ON PRODUCT APPROVAL CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 C) IF FLAT ROOF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED AS
 REQUIRED BY THE PRODUCT APPROVAL SUBMITTED.
  
 2- SHINGLES NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT. (2 COPIES). DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-04-22 Cont ID  
Sent By jgomez Date 2014-04-22 Time 14:25 Rev Time 0.00
Received By jgomez Date 2014-04-22 Time 14:25 Sent To  
Notes
2014-04-22 14:26:12FLAT ROOF NOA 13-0424.14 SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-21 Cont ID  
Sent By jgomez Date 2014-04-21 Time 13:42 Rev Time 0.00
Received By jgomez Date 2014-04-21 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-14 Cont ID  
Sent By jgomez Date 2014-04-14 Time 09:49 Rev Time 0.00
Received By jgomez Date 2014-04-14 Time 09:49 Sent To  
Notes
***NONE***