Plan Review Details - Permit 14040354
Plan Review Stops For Permit 14040354
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-29 Cont ID  
Sent By dhayes Date 2014-04-25 Time 16:24 Rev Time 0.00
Received By dhayes Date 2014-04-25 Time 16:24 Sent To Z
Notes
2014-04-25 14:28:32PASSED WITH THE FOLLOWING PROVISO:
  
 ALL ELECTRICAL APPARATUS, WIRING METHODS, AND MATERIALS
 SHALL COMPLY WITH THE 2008 EDITION OF THE NEC ARTICLES
 501 AND 682.
  
 DAVID HAYES. PLANS EXAMINER. 561-805-6717,
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-18 Cont ID  
Sent By pleduc Date 2014-04-18 Time 12:46 Rev Time 0.00
Received By pleduc Date 2014-04-18 Time 11:58 Sent To E
Notes
2014-04-18 12:45:58THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 INSTALL A SIGN "CAUTION - UNDERGROUND DIESEL TANK".
  
 INSTALL TRAFFIC BOLLARDS TO PROTECT TANK FROM VEHICLES
 WHERE REQUIRED.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By skennedy Date 2014-06-11 Time 14:31 Rev Time 0.00
Received By skennedy Date 2014-06-11 Time 14:31 Sent To  
Notes
2014-06-11 14:31:48DERM APPROVED 3/27/14.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-07 Cont ID  
Sent By hmoser Date 2014-05-07 Time 15:51 Rev Time 0.00
Received By hmoser Date 2014-04-09 Time 15:54 Sent To  
Notes
2014-04-11 15:54:23SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-07 Cont ID  
Sent By hmoser Date 2014-05-07 Time 15:50 Rev Time 0.00
Received By hmoser Date 2014-05-07 Time 13:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-26 Cont ID  
Sent By eschneid Date 2014-06-26 Time 16:21 Rev Time 0.50
Received By eschneid Date 2014-06-26 Time 16:20 Sent To PC
Notes
2014-06-26 16:30:22PASSED
  
 1) THE ABOVEGROUND FEATURES RELATED TO THE STORAGE TANK
 SHALL BE SCREENED WITH AN OPAQUE FENCE/WALL FOR THE
 FULL HEIGHT OF THE ABOVE GROUND FEATURES. A FENCE
 PERMIT IS REQUIRED. THE FENCE SHALL BE INSTALLED AND
 PASS INSPECTION PRIOR TO THE FINAL (104) INSPECTION FOR
 THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-06 Cont ID  
Sent By ESchneid Date 2014-05-06 Time 16:56 Rev Time 0.25
Received By eschneid Date 2014-05-06 Time 16:56 Sent To M
Notes
2014-05-06 16:58:57FAILED
  
 1) THE PLACEMENT OF THE ABOVE GROUND FEATURES FOR THE
 NEW UNDERGROUND FUEL TANK IS A MODIFICATION TO THE
 APPROVED SITE AND LANDSCAPE PLANS AND REQUIRES A MINOR
 PLANNED DEVELOPMENT AMENDMENT.
  
 2) PLEASE BE AWARE THAT THIS IS A POSSIBLE LOCATION FOR
 THE RELOCATION OF THE PACE BUS PARKING ONCE TRADITIONS
 PHASE II IS CONSTRUCTED. STAFF RECOMMENDS TAKING INTO
 ACCOUNT THE FUTURE PARKING RELOCATION WHEN PLANNING ANY
 NEW SITE FACILITIES.
  
 3)) THE ABOVE GROUND FEATURES FOR THE NEW UNDERGROUND
 FUEL TANK SHALL BE SCREENED WITH AN OPAQUE FENCE/WALL
 TO THE HEIGHT OF THE EQUIPMENT. A FENCE PERMIT IS
 REQUIRED. THE EXTERIOR OF THE FENCE SHALL BE SCREENED
 WITH LANDSCAPE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
2014-04-30 16:07:104/30/14 ZONING RECEIVED, SENT TO ES. SG