Plan Review Details - Permit 14040298
Plan Review Stops For Permit 14040298
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-27 Cont ID  
Sent By shill Date 2014-08-27 Time 18:08 Rev Time 0.00
Received By shill Date 2014-08-27 Time 18:08 Sent To  
Notes
2014-08-27 18:11:16***PROVISO***
  
 SEPARATE PERMIT REQUIRED FOR ROOF. SUBMIT PRODUCT
 APPROVALS, SELECT ASSEMBLY PROPOSED, AND ENGINEERING
 FOR ENHANCED FASTENING.
  
 ASSEMBLY SELECTED AND SUBMITTED FOR REVIEW HAD A
 LIMITATION OF -52.5. ZONE 1 REQUIREMENT IS 59.38. SEE
 RAS 117 8.1, DESIGN PRESSURE FOR THE SELECTED ASSEMBLY
 IS TO APPLY TO ZONE 1.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 13:58 Rev Time 0.00
Received By shill Date 2014-04-26 Time 13:58 Sent To  
Notes
2014-04-26 14:26:22****CORRECTIONS****
 ****REVISED 6/14 TO REMOVE REFERENCE TO FBC 2010
 RESIDENTIAL 301.2.1.1 AND CHANGE CODE REFERENCE TO
 301.1.****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107.2.1, ALL INFORMATINO, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2. SHEET 2.0, PAVER WORK PROPOSED WHICH IS NOT LOCATED
 WITHIN THE BOUNDARIES OF THE PROPERTY FOR THIS PERMIT
 APPLICATION. WORK ON ANOTHER PARCEL WILL REQUIRE A
 SEPARATE PERMIT.
  
 3. DRIVEWAY/PAVER WORK PROPOSED REQUIRES A SEPARATE
 PERMIT, FBC 107. PERMIT #14040299 FOR PAVERS WAS
 SUBMITTED. IT IS SUGGESTED THAT, WHEN RESUBMITTING,
 PLANS RELATING TO THE PAVER WORK BE RESUBMITTED
 SEPARATELY FROM THE PATIO/PORCH PERMIT. THIS WILL HELP
 TO EXPEDITE BOTH PERMITS.
  
 4. COVER SHEET STATES THIS IS A LEVEL 2 ALTERATION; SEE
 FBC 2010 EXISTING BUILDING 202 AND REVISE.
  
 5. FBC 2010 RESIDENTIAL 301.1, PLAN STATES THAT THIS
 DESIGN IS IN ACCORDANCE WITH ASCE7-10. IF PLANS ARE NOT
 PREPARED BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS
 FOR STRUCTURAL ELEMENTS (CONNECTORS, FOOTING SIZES,
 COLUMN SIZES, SPANS, ETC).
  
 6. ZONING HAS REDLINED SHEETS 2.0, 5.0, 9.0, AND OTHER
 SHEETS. PLEASE INCORPORATE THE CHANGES INTO THE PLAN,
 ALL SHEETS, AS THERE IS A REDUCTION IN SIZE AND AFFECTS
 OTHER SHEETS, FBC 107.
  
 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE SHINGLE ROOF, FBC 2010 RESIDENTIAL 301, FAC9N-3.
  
 8. FOR THE FLAT ROOF, PROVIDE A CURRENT PRODUCT
 APPROVAL. THE NOA SUBMITTED HAS BEEN SUPERSEDED. THE
 CURRENT VERSION OF THIS APPROVAL IS AVAILABLE AT WWW.MI
 AMIDADE.GOV/BUILDING/LIBRARY/PRODUCTCONTROL/NOA/1207161
 8.PDF. PROVIDE TWO SETS.
  
 9. FOR THE FLAT ROOF, INDICATE WHICH APPROVED ASSEMBLY
 IS PROPOSED.
  
 10. FOR THE FLAT ROOF, PROVIDE ENGINEERING FOR THE
 ENHANCED FASTENING REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 13:02 Rev Time 0.00
Received By dhayes Date 2014-09-04 Time 12:35 Sent To  
Notes
2014-09-04 13:04:43DATE: 9/4/2014
 PROJECT: COVERED PATIO
 PERMIT#: 14040298
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By albarran Date 2014-05-07 Time 17:31 Rev Time 0.00
Received By albarran Date 2014-05-07 Time 16:26 Sent To  
Notes
2014-05-07 17:37:58FAILED ELECTRICAL REVIEW 5/7/14
  
 1 APPLICABLE ELECTRICAL CODE IN FORCE IS THE 2008
 EDITION OF THE NEC
 2. ARC-FAULT REQUIREMENTS AS PER THE CURRENT CODE DO
 NOT MATCH THE NOTES AS SUBMITTED.
 3. NEED BETTER DETAIL ON THE ELECTRICAL PAGE TO SHOW
 WHAT AREA WILL BE ENCLOSED AND WHAT WILL BE OPEN.
 4. ALL EXTERIOR OUTLETS SHALL BE GFCI PROTECTED.
 5. THE DISCONNECT FOR THE CONDENSING UNIT SHALL BE
 WITHIN SIGHT OF EQUIPMENT.
 6. THE SERVICED OUTLET REQUIRED BY 210.63 SHALL NOT BE
 BEHIND THE UNIT.
 7. MAKE MENTION OF THE NEC 314.27(A) REQUIREMENT FOR
 THE CEILING BOXES.
  
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-04 Cont ID  
Sent By dhayes Date 2014-09-04 Time 13:04 Rev Time 0.00
Received By dhayes Date 2014-06-30 Time 18:15 Sent To  
Notes
2014-06-30 18:15:22R09
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 12:20 Rev Time 0.00
Received By skennedy Date 2014-04-09 Time 10:03 Sent To  
Notes
2014-04-26 14:28:46R08
  
2014-04-09 20:10:134/9 TO MISC 2
  
2014-04-09 10:04:13SENT TO ZONING. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-30 Cont ID  
Sent By tklarge Date 2014-08-30 Time 09:29 Rev Time 0.00
Received By tklarge Date 2014-08-30 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 12:20 Rev Time 0.00
Received By skennedy Date 2014-05-17 Time 12:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2014-08-27 Cont ID  
Sent By shill Date 2014-08-27 Time 18:11 Rev Time 0.00
Received By shill Date 2014-08-27 Time 18:11 Sent To  
Notes
2014-08-27 18:17:00SEPARATE PERMIT REQUIRED FOR ROOF
 ASSEMBLY SELECTED HAD A LIMITATION OF -52.5. ZONE 1
 REQUIREMENT IS 59.38. SEE RAS 117 8.1, DESIGN PRESSURE
 FOR THE SELECTED ASSEMBLY IS TO APPLY TO ZONE 1.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-08 Cont ID  
Sent By sgraham Date 2014-07-08 Time 14:47 Rev Time 0.00
Received By sgraham Date 2014-07-08 Time 14:47 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-09 Cont ID  
Sent By sgraham Date 2014-04-09 Time 14:31 Rev Time 0.00
Received By sgraham Date 2014-04-09 Time 14:31 Sent To B
Notes
***NONE***