Plan Review Details - Permit 14040277
Plan Review Stops For Permit 14040277
Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-05-18 Cont ID  
Sent By mgonzale Date 2015-05-18 Time   Rev Time 0.50
Received By mgonzale Date 2015-05-18 Time   Sent To  
Notes
2015-05-18 16:23:23PROVISOS-
  
 PROVIDE AS-BUILTS AND CERTIFICATION LETTER TO PUBLIC
 WORKS.
  
 PROVIDE COPY OF CLOSED FDOT PERMIT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
2015-03-23 09:04:02REVISED DRAWINGS SUBMITTED. JG

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-12-08 Cont ID  
Sent By cranford Date 2014-12-08 Time 13:44 Rev Time 0.00
Received By cranford Date 2014-12-08 Time 13:34 Sent To M
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-05-02 Cont ID  
Sent By Mgonzale Date 2014-05-02 Time   Rev Time 1.00
Received By mgonzale Date 2014-05-02 Time   Sent To M
Notes
2014-05-02 11:07:34#1 WATERLINE ON-SITE WILL BE CONSIDERED PRIVATE. SHEET
 C-5 WILL NEED REVISION SHOWING FIRE AND DOMESTIC
 SERVICE WITH SEPARATE TAPS. FIRE LOOP WILL REQUIRE DCDA
 AT EACH CITY CONNECTION NEAR RPOERTYLINE.
  
 #2 WATERLINE EASEMENT ON-SITE WILL NOT BE REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-05-13 Cont ID  
Sent By wjolin Date 2015-05-13 Time 09:53 Rev Time 0.00
Received By wjolin Date 2015-05-13 Time 09:21 Sent To ENG
Notes
2015-03-23 09:03:53REVISED DRAWINGS SUBMITTED. JG

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-12-04 Cont ID  
Sent By hmoser Date 2014-12-15 Time 14:25 Rev Time 0.00
Received By wjolin Date 2014-12-03 Time 17:14 Sent To  
Notes
2014-12-03 17:48:372101 OKEECHOBEE BOULEVARD
 PERMIT #14040277
 MASTER #14040379
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT VALUES SHALL INCLUDE LABOR AND MATERIALS. THE
 PERMIT VALUE OF $23,000 DOES NOT INCLUDE THE 8-INCH
 BACKFLOW PREVENTER, 8-INCH AND 6-INCH PVC FIRE LINE
 (APPROXIMATELY 500 LINEAR FEET) OR THE PVC JOINT
 RESTRAINT SYSTEMS.
  
 THE PLANS INDICATE ONE WATER MAIN TAP SERVING BOTH THE
 FIRE LINE AND DOMESTIC WATER. WHAT IS THE MAXIMUM
 ANTICIPATED DEMAND OF THE 3-INCH DOMESTIC WATER LINE?
 RECOMMEND SEPARATE TAPS FOR FIRE AND DOMESTIC WATER.
  
 FIRE RESCUE UNITS WILL TRY TO AVOID STAGING ON A BUSY
 ROAD LIKE OKEECHOBEE BOULEVARD. RELOCATE THE FDC ON OR
 NEAR THE BUILDING'S FIRE LANE.
  
 PROVIDE LOCKING KNOX CAPS ON THE FDC.
  
 SUBMIT PRODUCT CUTSHEET FOR BACKFLOW PREVENTION DEVICE
 TO BE USED IN THE FIRE SERVICE MAIN. DEVICE SHALL BE
 LISTED FOR FIRE PROTECTION USE.
  
 SUPERVISE THE BACKFLOW PREVENTER WITH TAMPER SWITCHES
 AND CHAIN WITH LOCK.
  
 SUBMIT PRODUCT CUTSHEETS FOR JOINT RESTRAINING METHODS.
 DATA SHEETS SHALL CLEARLY INDICATE THE PROPER TORQUE
 WRENCH SETTING IF USING MECHANICAL RESTRAINTS.
 CORROSION RESISTANCE: AFTER INSTALLATION, RODS, NUTS,
 BOLTS, WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES
 SHALL BE CLEANED AND THOROUGHLY COATED WITH A
 BITUMINOUS OR OTHER ACCEPTABLE CORROSION-RETARDING
 MATERIAL.
  
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING
 PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT
 PRESSURE +/-5 PSI FOR 2 HOURS.
  
 THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR
 PERFORMING ALL REQUIRED ACCEPTANCE TESTS AND COMPLETING
 AND SIGNING THE CONTRACTOR'S MATERIAL AND TEST
 CERTIFICATE(S) FOUND IN NFPA 24.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By pleduc Date 2014-04-21 Time 11:04 Rev Time 0.00
Received By pleduc Date 2014-04-21 Time 10:14 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-20 Cont ID  
Sent By hmoser Date 2015-05-20 Time 07:02 Rev Time 0.00
Received By hmoser Date 2015-03-18 Time 08:57 Sent To  
Notes
2015-03-23 08:59:03RE-SUBMITTAL (NEW DRAWINGS) SENT TO FIRE SHELF FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-15 Cont ID  
Sent By hmoser Date 2014-12-15 Time 14:25 Rev Time 0.00
Received By hmoser Date 2014-06-20 Time 15:55 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-14 Cont ID  
Sent By hmoser Date 2014-05-14 Time 11:43 Rev Time 0.00
Received By hmoser Date 2014-04-08 Time 16:35 Sent To  
Notes
2014-05-07 15:45:255/7 TO MECHANICAL
 (WAS IN SK OFFICE)
  
2014-04-08 16:35:54INCOMING SENT TO FIRE BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2015-05-20 Cont ID  
Sent By hmoser Date 2015-05-20 Time 07:01 Rev Time 0.00
Received By hmoser Date 2015-05-20 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-12-15 Cont ID  
Sent By hmoser Date 2014-12-15 Time 14:25 Rev Time 0.00
Received By hmoser Date 2014-12-15 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-14 Cont ID  
Sent By hmoser Date 2014-05-14 Time 11:43 Rev Time 0.00
Received By hmoser Date 2014-05-14 Time 11:17 Sent To  
Notes
***NONE***