Plan Review Details - Permit 14040266
Plan Review Stops For Permit 14040266
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 17:02 Rev Time 0.00
Received By jwitmer Date 2014-04-17 Time 16:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 13:53 Rev Time 0.00
Received By rlecky Date 2014-05-01 Time 13:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By pleduc Date 2014-04-22 Time 13:50 Rev Time 0.00
Received By pleduc Date 2014-04-22 Time 13:37 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-30 Cont ID  
Sent By jwitmer Date 2014-05-30 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2014-05-29 Time 13:21 Sent To  
Notes
2014-05-29 13:22:18INCOMING SENT TO JW DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-09 Cont ID  
Sent By skennedy Date 2014-05-09 Time 09:26 Rev Time 0.00
Received By skennedy Date 2014-04-08 Time 09:17 Sent To  
Notes
2014-05-08 16:53:53TO STEVE FOR PROCESSING.
2014-04-09 09:18:16INCOMING SENT TO C-10.JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 16:59 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 17:01 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-30 Cont ID  
Sent By jwitmer Date 2014-05-30 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2014-05-30 Time 14:07 Sent To  
Notes
2014-05-30 14:09:51ARCHITECT JIM PAINE SUBMITTED MANUFACTURER'S CUT SHEETS
 FOR A ZURN Z1170 GREASE INTERCEPTOR WILL REQUIRED A
 SEPERATE PERMIT, REVIEWED UNDER THIS MASTER PERMIT. J
 WITMER

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 17:17 Rev Time 0.00
Received By jwitmer Date 2014-04-17 Time 16:59 Sent To  
Notes
2014-04-17 17:17:51BUILDING PLAN REVIEW
 PERMIT: 14040266
 ADD: 206 CLEMATIS ST / SUBWAY KIOSK
 CONT: SOUTHERN CERTIFIED CONSTRUCTION
 TEL: (561)676-6001
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY APRIL 17/2014
 ACTION: DENIED
  
 1) PLANS INDICATE NO PLUMBING WORK WITH THE EXCEPTION
 OF HOOKING UP A HAND SINK. A VISIT TO THE SITE DID NOT
 INDICATE ANY EXISITNG SINK IN THE PROPOSED LOCATION FOR
 THE HAND SINK. PLEASE PROVIDE ADDITIONAL INFORMATION.
 FOR SANITARY AND VENT LOCATIONS, PLANS FROM 1994 DO NOT
 INDICATE ANY SINKS IN THIS LOCATION.
  
 2) PLEASE PROVIDE ADDITIONAL INFORMATION HOW HOT WATER
 WILL BE ROUTED TO THE HAND SINK LOCATION. 2010 FBC-B
 607.1.1 HAND WASHING LAVATORIES.
 IN PUBLIC FOOD SERVICE ESTABLISHMENTS, FOOD
 ESTABLISHMENTS OR WHERE OTHERWISE REQUIRED BY LAW,
 LAVATORIES INTENDED FOR THE PURPOSE OF EMPLOYEE HAND
 WASHING SHALL BE EQUIPPED WITH HOT OR TEMPERED WATER.
  
 3) THE PLANS INDICATE THE WORK AREA TO INCORPORATE THE
 3 COMPARTMENT SINK LOWER RIGHT CORNER OF A1.1. WILL
 THIS 3 COMPARTMENT SINK BE ENLARGED, IS THERE A FLOOR
 SINK OR HUB DRAIN BENEATH THE UNIT? IS THERE A GREASE
 TRAP HOOKED UP TO THE DRAIN TO CATCH FATS, OILS AND
 GREASY WASTE. 2010 FBC-P 1003.3.1 GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. A GREASE
 INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE
 REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES AND
 EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-08 Cont ID  
Sent By aaponte Date 2014-05-08 Time 16:53 Rev Time 0.00
Received By aaponte Date 2014-05-08 Time 16:53 Sent To  
Notes
2014-04-14 11:40:074/14/14