| 2014-04-24 09:58:06 | ADDRESS: 1750 N. CONGRESS WPB |
| | PERMIT#: 14040245 |
| | 1ST ELECTRICAL REVIEW |
| | ACTION: DENIED. |
| | CODE: 2008 NEC AND 2010 FBC |
| | |
| | DEFICIENCIES |
| | |
| | 907.1.2 FIRE ALARM SHOP DRAWINGS. [F] |
| | SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED |
| | FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION, |
| | AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE |
| | FOLLOWING: |
| | 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. |
| | 2) LOCATIONS OF ALARM-INITIATING DEVICES. |
| | 3) LOCATIONS OF ALARM NOTIFICATION APPLIANCES, |
| | INCLUDING CANDELA RATINGS FOR VISIBLE ALARM |
| | NOTIFICATION APPLIANCES. |
| | 4) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS |
| | AND NOTIFICATION POWER SUPPLIES. |
| | 5) ANNUNCIATORS. |
| | 6) POWER CONNECTION. |
| | 7) BATTERY CALCULATIONS. |
| | 8) CONDUCTOR TYPE AND SIZES. |
| | 9) VOLTAGE DROP CALCULATIONS. |
| | 10) MANUFACTURERS' DATA SHEETS INDICATING MODEL NUMBERS |
| | AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND |
| | MATERIALS. |
| | 11) DETAILS OF CEILING HEIGHT AND CONSTRUCTION. |
| | 12) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. |
| | 13) CLASSIFICATION OF THE SUPERVISING STATION. |
| | |
| | THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED: |
| | 1) A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS. |
| | 2) LOCATIONS OF ALARM NOTIFICATION APPLIANCES, |
| | INCLUDING CANDELA RATINGS FOR VISIBLE ALARM |
| | NOTIFICATION APPLIANCES. |
| | 3) LOCATION OF FIRE ALARM CONTROL UNIT, TRANSPONDERS |
| | AND NOTIFICATION POWER SUPPLIES. |
| | 4) CONDUCTOR TYPE AND SIZES. |
| | 5) DETAILS OF CEILING HEIGHT AND CONSTRUCTION. |
| | 6) THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. |
| | 7) CLASSIFICATION OF THE SUPERVISING STATION. |
| | |
| | ADDITIONALLY |
| | FBC |
| | [F] 907.2.18.1 SMOKE DETECTORS. A MINIMUM OF ONE SMOKE |
| | DETECTOR LISTED FOR THE INTENDED PURPOSE SHALL BE |
| | INSTALLED IN THE FOLLOWING AREAS: |
| | 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| | TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS. |
| | 2) ELEVATOR LOBBIES. |
| | 3) THE MAIN RETURN AND EXHAUST AIR PLENUM OF EACH |
| | AIR-CONDITIONING SYSTEM SERVING MORE THAN ONE STORY AND |
| | LOCATED IN A SERVICEABLE AREA DOWNSTREAM OF THE LAST |
| | DUCT INLET |
| | 4) EACH CONNECTION TO A VERTICAL DUCT OR RISER SERVING |
| | TWO OR MORE FLOORS FROM AIR RETURN AIR DUCTS OR PLENUMS |
| | OF HEATING, VENTILATING SYSTEM, EXCEPT THAT IN GROUP R |
| | OCCUPANCIES, A LISTED SMOKE DETECTOR IS ALLOWED TO BE |
| | USED IN EACH AIR RISER CARRYING NOT MORE THAN 5000 CFM |
| | (2.4 M3/S) AND SERVING NOT MORE THAN 10 AIR INLET |
| | OPENINGS. |
| | |
| | THEREFORE, THE FOLLOWING DEFICIENCIES ARE NOTED: |
| | 1) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| | TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS, |
| | A LISTED SMOKE DETECTOR SHALL BE INSTALLED. |
| | 2) THE ELECTRICAL ROOM IS NOTED BUT NO SMOKE DETECTOR |
| | IS SHOWN. |
| | . |
| | |
| | FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN |
| | REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS |
| | EXAMINER, PX3421. I CAN BE AT 561-805-6717 OR AT |
| | [email protected] |
| | |