| 2014-04-22 15:22:31 | 114 SOUTH OLIVE AVENUE |
| | PERMIT #14040237 |
| | MASTER #13060638 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE FIRE PROTECTION ENGINEERING CONSTRUCTION DOCUMENTS |
| | ESTABLISH "J.F. SHANNON" AS THE ENGINEER OF RECORD; |
| | THEREFORE, THE FIRE SPRINKLER SHOP DRAWINGS SHALL NOT |
| | BE SEALED BY ANOTHER ENGINEER UNLESS MR. LAWRENCE |
| | BORAIKO (ENGINEER) IS DESIGNATED AS THE "DELEGATED |
| | ENGINEER" BY THE ENGINEER OF RECORD. |
| | |
| | PER FLORIDA BUILDING CODE SECTION 905.3.1 A CLASS I |
| | STANDPIPE SYSTEM IS REQUIRED THROUGHOUT BUILDINGS WHERE |
| | THE FLOOR LEVEL OF THE HIGHEST STORY IS LOCATED MORE |
| | THAN 30 FEET ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| | VEHICLE ACCESS. |
| | |
| | BACKFLOW PREVENTER LOCATION ISSUE: PER NFPA 24 SECTION |
| | 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| | FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN |
| | BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | ***NOTE: A SEPARATE PERMIT IS NEEDED FOR THE |
| | UNDERGROUND FIRE LINE TAP*** |
| | |