| 2014-04-08 19:01:49 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND |
| | SPEED WITH EXPOSURE CATEGORY C. THE MAXIMUM DESIGN |
| | PRESSURE FOR THE CERTAIN TEED MODIFIED ROOFING OVER |
| | WOOD DECKS IS -52.5 PSF. THIS WILL NOT MEET THE |
| | REQUIRED PRESSURES. SUBMIT SIGNED AND SEALED RAS 117 |
| | CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 OF NOA |
| | NO.13-0204.03. FBC 1609.1 |
| | |
| | 2) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING. FBC |
| | 1609.1 |
| | |
| | 3) A FLORIDA COVER SHEET FOR FL# 2533-R8 WAS ATTACHED |
| | TO NOA NO.13-0204.04 FOR THE CERTAIN-TEED MODIFIED |
| | ROOFING OVER CONCRETE DECKS. THE NOA IS NOT THE |
| | INSTALLATION INSTRUCTIONS FOR THIS FLORIDA PRODUCT |
| | APPROVAL. THEY ARE TWO SEPARATE PRODUCT APPROVALS. IF |
| | YOU WANT TO USE THE FLORIDA PRODUCT APPROVAL SUBMIT THE |
| | CURRENT REVISION OF IT (R-10) WITH THE PROPER |
| | INSTALLATION INSTRUCTIONS. THE MIAMI-DADE NOA IS |
| | ACCEPTABLE AS IT IS WITHOUT THE FL COVERSHEET. PLEASE |
| | CLARIFY. DCA RULE 9N-3 AND CITY AMENDMENTS 107.2.1 |
| | |
| | |
| | 4) A FLORIDA PRODUCT APPROVAL ( FL16709 ) FOR |
| | CERTAIN-TEED MODIFIED ROOFING WAS SUBMITTED. IF YOU |
| | WISH TO USE THIS PRODUCT APPROVAL, YOU ARE REQUIRED TO |
| | MARK THE SYSTEM THAT YOU WILL USE AND ALL THE |
| | APPROPRIATE FASTENING OPTIONS ON THE INSTALLATION |
| | INSTRUCTIONS. SUBMIT TWO COPIES OF A ROOF DIAGRAM THAT |
| | WILL CLARIFY WHERE THIS WILL BE INSTALLED AND WHERE THE |
| | OTHER SYSTEMS WILL BE INSTALLED. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |