Plan Review Details - Permit 14040208
Plan Review Stops For Permit 14040208
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 13:30 Sent To  
Notes
2014-04-18 14:28:59 
  
  
 BUILDING PROVISO:
 708.14.1 ELEVATOR LOBBY.
 THE REQUIREMENTS IN SECTION 709 FOR FIRE PARTITIONS,
 DOORS PROTECTING OPENINGS IN
 THE ELEVATOR LOBBY ENCLOSURE WALLS SHALL ALSO COMPLY
 WITH SECTION 715.4.3 AS
 REQUIRED FOR CORRIDOR WALLS AND PENETRATIONS OF THE
 ELEVATOR LOBBY ENCLOSURE.
  
 715.4.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF
 20 MINUTES (TABLE 715.4) WHERE LOCATED IN CORRIDOR
 WALLS OR SMOKE BARRIER WALLS
 HAVING A FIRE-RESISTANCE RATING IN ACCORDANCE WITH
 TABLE 715.4 SHALL BE TESTED IN
 ACCORDANCE WITH NFPA 252 OR UL 10C WITHOUT THE HOSE
 STREAM TEST.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-01 Cont ID  
Sent By dhayes Date 2014-05-01 Time 14:37 Rev Time 0.00
Received By dhayes Date 2014-05-01 Time 14:12 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By pleduc Date 2014-04-21 Time 12:25 Rev Time 0.00
Received By pleduc Date 2014-04-21 Time 11:18 Sent To E
Notes
2014-04-21 12:14:51THE PLAN REVIEW WAS COMPLETED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LOBBY DOORS SHALL NOT BE LOCKED AGAINST EGRESS.
  
 THE FIRE ALARM AND SPRINKLER SYSTEM SHALL REMAIN FULLY
 FUNCTIONAL DURING CONSTRUCTION.
  
 ALL WORK ON THE LIFE SAFETY SYSTEMS, FIRE ALARM AND
 SPRINKLER, SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS
 AND BY A CERTIFIED LIFE SAFETY CONTRACTOR.
  
 ANY SYSTEM DOWN FOR MORE THAN 4 HOURS IS REQUIRED TO BE
 UNDER FIRE WATCH.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-01 Cont ID  
Sent By hmoser Date 2014-05-01 Time 16:27 Rev Time 0.00
Received By hmoser Date 2014-04-07 Time 12:14 Sent To  
Notes
2014-04-07 12:15:08B09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-01 Cont ID  
Sent By hmoser Date 2014-05-01 Time 16:27 Rev Time 0.00
Received By hmoser Date 2014-05-01 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 14:39 Sent To  
Notes
2014-04-18 15:32:36PLUMBING PROVISO:
 2010 FL EXST BLDG CODE LEVEL II ALTERATIONS: 706.1
 GENERAL. A BUILDING, FACILITY, OR
 ELEMENT THAT IS ALTERED SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
 2010C FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2010 FL ACCESSIBILITY CODE 211 DRINKING FOUNTAINS: ONE
 HIGH/ LOW REQUIRED
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  