Plan Review Details - Permit 14040199
Plan Review Stops For Permit 14040199
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-16 Cont ID  
Sent By jgomez Date 2014-07-16 Time 16:45 Rev Time 0.00
Received By jgomez Date 2014-07-10 Time 15:43 Sent To  
Notes
2014-07-10 16:18:16ROUTED TO J GOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-25 Cont ID  
Sent By jgomez Date 2014-06-25 Time 14:15 Rev Time 0.00
Received By jgomez Date 2014-06-23 Time 14:13 Sent To  
Notes
2014-06-25 14:14:07REVISION RESUBMITTAL SENT TO JULIO'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-24 Cont ID  
Sent By jgomez Date 2014-04-24 Time 15:58 Rev Time 0.00
Received By jgomez Date 2014-04-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-11 Cont ID  
Sent By jgomez Date 2014-04-11 Time 11:50 Rev Time 0.00
Received By jgomez Date 2014-04-04 Time 09:04 Sent To  
Notes
2014-04-08 09:03:23TO JG DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2014-07-16 Cont ID  
Sent By jgomez Date 2014-07-16 Time 15:43 Rev Time 0.00
Received By jgomez Date 2014-07-16 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-06-26 Cont ID  
Sent By jgomez Date 2014-06-25 Time 14:14 Rev Time 0.00
Received By jgomez Date 2014-06-25 Time 14:14 Sent To  
Notes
2014-06-25 14:15:25MECHANICAL REVISION THIRD CHECKLIST.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
  
 A) CALCULATIONS CAN NOT BE DONE FOR WORST CASE
 SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 REVISE CALCULATIONS AS REQUIRED TO MATCH THE ACTUAL
 BUILDING ORIENTATION.
 ***NOTE: COORDINATE EQUIPMENT OF REVISED CALCULATIONS
 WITH EQUIPMENT SHOWN ON THE A/C PLAN.
  
 *****RESPONSE TO INFORMATION SUBMITTED:
 (1) EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE AGAIN
 DONE BASED ON WORST CASE SCENARIO. NEED TO USE THE
 ACTUAL BUILDING ORIENTATION. THERE IS NOT NW, NE, SE,
 SW, SE, SW ORIENTATION FOR THIS HOUSE. SEE PLANS AND
 REVISE AS REQUIRED.
 SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 (2) THERE IS NOT GARAGE IN THIS HOUSE. THEREFORE, THERE
 ARE NOT ADJACENT WALLS EITHER. SEE PLANS AND REVISE
 CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 (3) THERE ARE NOT 34 OCCUPANTS IN A SINGLE FAMILY
 RESIDENCE OF 3 BEDROOMS. SEE PLANS AND REVISE
 CALCULATIONS AS REQUIRED. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 (4) A/C EQUIPMENT SELECTED (OUTDOOR AND INDOOR) :
 PROVIDE THE MANUFACTURER'S PUBLISHED AHRI CERTIFICATE
 SHOWING THE SENSIBLE AND TOTAL COOLING CAPACITY AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
  
 B) OK. HOUSE ADDRESS WAS CORRECTED.
  
 C) COOLING AND HEATING INFORMATION SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS DON'T MATCH THE
 INFORMATION SHOWN ON THE ENERGY CALCULATIONS SUBMITTED.
 REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. ***(REPEAT COMMENT. NOT
 ADDRESSED).
  
 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C
 PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
 ***(REPEAT COMMENT. NOT ADDRESSED).
  
  
 3- ENERGY CALCULATIONS SUBMITTED:
  
 A) OK. HOUSE ADDRESS WAS CORRECTED.
  
 B) COOLING AND HEATING INFORMATION DON'T MATCH THE
 HEATING AND COOLING INFORMATION SHOWN ON THE EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 C) OK. OWNER/AGENT SIGNED BOTTOM OF FORM.
  
 4- OWES $51.50 FOR REVISON FEES RESUBMITTAL.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-04-24 Cont ID  
Sent By jgomez Date 2014-04-24 Time 15:59 Rev Time 0.00
Received By jgomez Date 2014-04-24 Time 15:58 Sent To  
Notes
2014-04-24 16:01:59MECHANICAL REVISION SECOND CHECKLIST.
 CODE: 2010 FBC.
  
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
  
 A) CALCULATIONS CAN NOT BE DONE FOR WORST CASE
 SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 REVISE CALCULATIONS AS REQUIRED TO MATCH THE ACTUAL
 BUILDING ORIENTATION.
 ***NOTE: COORDINATE EQUIPMENT OF REVISED CALCULATIONS
 WITH EQUIPMENT SHOWN ON THE A/C PLAN.
  
 B) ADDRESS SHOWN ON THE EQUIPMENT SIZING CALCULATIONS
 IS INCORRECT. THE CORRECT ADDRESS IS 210 ALHAMBRA PL,
 NOT 201 ALHAMBRA PL. REVISE AS REQUIRED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) COOLING AND HEATING INFORMATION SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS DON'T MATCH THE
 INFORMATION SHOWN ON THE ENERGY CALCULATIONS SUBMITTED.
 REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C
 PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
  
 3- ENERGY CALCULATIONS SUBMITTED:
  
 A) CORRECT ADDRESS IS 210 ALHAMBRA PL, NOT 201
 ALHAMBRA. AND COMPLETE ALL THE INFORMATION ON TOP OF
 FORM, INCLUDING THE OWNER'S NAME, BUILDER'S NAME,
 PERMITTING OFFICE, ETC. REVISE AS REQUIRED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) COOLING AND HEATING INFORMATION DON'T MATCH WITH THE
 HEATING AND COOLING INFORMATION SHOWN ON THE EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (5610805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-04-11 Cont ID  
Sent By jgomez Date 2014-04-11 Time 11:50 Rev Time 0.00
Received By jgomez Date 2014-04-11 Time 11:50 Sent To  
Notes
2014-04-11 13:10:00REVISION MECHANICAL REVIEW COMMENTS:
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION. (REQUESTED ON
 PROVISO DATED 2/7/14, BUT IT WAS NEVER SUBMITTED).
  
 ***NOTE: EQUIPMENT SHOWN ON THE CALCULATIONS TO MATCH
 EQUIPMENT SHOWN ON THE A/C PLAN.
  
  
 2- A/C CONTRACTOR RESPONSIBLE FOR THE DESIGN OF THE A/C
 PLAN SUBMITTED TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (5610805-6712