| Plan Review Stops For Permit 14040187 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-04-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-14 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-14 |
Time |
12:50 |
Sent To |
I |
|
| Notes |
| 2014-04-14 13:40:58 | AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND | | | RACEWAY SHALL BE CONSIDERED A WET LOCATION; ALL | | | CONDUCTORS WITHIN THE RACEWAY SHALL BE LISTED | | | ACCORDINGLY. | | | ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION. | | | NO SITE TUBES WILL BE ACCEPTED. | | | AS PER NEC 300.5(D)(3) A WARNING RIBBON SHALL BE | | | PLACED NO MORE THAN 12" ABOVE RACEWAY INSIDE | | | TRENCH | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-04-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-14 |
Time |
13:41 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
PC |
|
| Notes |
| 2014-04-14 13:41:55 | SORTED AND GIVEN TO ALLISON | | 2014-04-04 13:45:34 | ROUTED TO ELECTRICAL $5000 & UNDER |
|
|
|