Plan Review Details - Permit 14040174
Plan Review Stops For Permit 14040174
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-05-20 Cont ID  
Sent By skennedy Date 2015-05-20 Time 09:37 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-04-30 Cont ID  
Sent By shill Date 2015-04-30 Time 07:38 Rev Time 0.00
Received By shill Date 2015-04-30 Time 07:38 Sent To  
Notes
2015-04-30 07:38:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS 471.
  
 2. WHEN RESUBMITTING, PLEASE PROVIDE ACCURATE
 INFORMATION ON THE "RESUBMITTAL" FORM. THE CONTRACTOR
 FOR THIS JOB IS "LIN R ROGERS." AS DOCUMENTS ARE FILED
 BY CONTRACTOR NAME, PROVIDING A NAME OTHER THAN
 CONTRACTOR IN THE "CONTRACTOR" LINE MAY RESULT IN THE
 PLANS BEING MISFILED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-12-04 Cont ID  
Sent By shill Date 2014-12-04 Time 09:29 Rev Time 0.00
Received By shill Date 2014-12-04 Time 09:29 Sent To  
Notes
2014-12-04 09:29:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE
 VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND
 IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED.
  
 12/4/14 ENGINEERING FOR CALCS ARE NOW WITH THE NEW,
 MOST RECENT SET OF PLANS. ENGINEER TO CONFIRM THAT THIS
 IS THE POLE PROPOSED.
  
 ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING,
 SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A
 REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP
 DRAWING REVIEW STAMP, OR BY LETTER.
  
 2. OK
  
 3. PLEASE NOTE THAT THE POLE ENGINEERING WAS APPROVED
 WITH PROVISO. FIXTURE CALCS WERE TO BE SUBMITTED AS A
 REVISION SUBJECT TO FIELD INSPECTOR'S DISCRETION. THIS
 MAY BE SUBMITTED AT THIS TIME (BUT IS NOT REQUIRED).
  
 4. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS FOR PERMIT ISSUANCE. IF THE PREVIOUSLY REVIEWED
 POLE CALCS ARE TO BE A PART OF THE ISSUED PERMIT,
 PLEASE INCLUDE WITH THE NEW SETS. PLEASE DO NOT REMOVE
 ANY OLD SHEETS FROM THE PACKAGE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 09:53 Rev Time 0.00
Received By shill Date 2014-12-01 Time 09:53 Sent To  
Notes
2014-12-01 09:58:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE
 VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND
 IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED.
  
 ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING,
 SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A
 REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP
 DRAWING REVIEW STAMP, OR BY LETTER.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. VALUE
 IS TO INCLUDE LABOR, MATERIALS, ENGINEERING, OVERHEAD
 AND PROFIT FBC 109.
  
 3. PLEASE NOTE THAT THE POLE ENGINEERING WAS APPROVED
 WITH PROVISO. FIXTURE CALCS WERE TO BE SUBMITTED AS A
 REVISION SUBJECT TO FIELD INSPECTOR'S DISCRETION. THIS
 MAY BE SUBMITTED AT THIS TIME (BUT IS NOT REQUIRED).
  
 4. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS FOR PERMIT ISSUANCE. IF THE PREVIOUSLY REVIEWED
 POLE CALCS ARE TO BE A PART OF THE ISSUED PERMIT,
 PLEASE INCLUDE WITH THE NEW SETS. PLEASE DO NOT REMOVE
 ANY OLD SHEETS FROM THE PACKAGE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-03 Cont ID  
Sent By eschneid Date 2014-07-07 Time 10:21 Rev Time 0.00
Received By shill Date 2014-07-03 Time 15:50 Sent To  
Notes
2014-07-03 15:50:49PROVISO - SUBMIT FIXTURE CALCS AS A REVISION SUBJECT TO
 FIELD INSPECTOR'S DISCRETION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 18:47 Rev Time 0.00
Received By shill Date 2014-06-20 Time 18:47 Sent To  
Notes
2014-06-20 18:48:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, PROVIDE STRUCTURAL DRAWINGS FOR THE LIGHT
 POLE AS PREVIOUSLY REQUESTED BY THE ELECTRICAL
 REVIEWER. INCLUDE WIND DESIGN CRITERIA.
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2015-04-01 Cont ID  
Sent By sgraham Date 2015-04-01 Time 16:06 Rev Time 0.00
Received By dhayes Date 2015-04-01 Time 16:05 Sent To Z
Notes
2015-04-01 16:06:074/1/2015 APPROVED WITH EXCEPTION.
 COMPLY WITH ALL THE REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION REQUIREMENTS FOR EXTERIOR LIGHTING. FBC-E
 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 13:47 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 13:47 Sent To  
Notes
2014-11-21 13:48:18ROUTE TO MISC. 1
  
 11/21/14 APPROVED WITH EXCEPTION.
 THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED
 DOCUMENTATION:
 1.PROVIDE SPEC SHEETS FOR THE POLES AS WELL AS FOR THE
 PROPOSED HEADS.
 2. PROVIDE ENGINEERED WIND LOAD CALCULATIONS OF THE
 POLES WITH THE RESPECTIVE HEADS ATTACHED. FBC-1609
 3. COMPLY WITH ALL THE REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION REQUIREMENTS FOR EXTERIOR LIGHTING. FBC-E
 505.2.4
 4. VERIFY EXISTING WIRING COMPLIES WITH NEC 300.5(B).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT DAVID HAYES (561) 805-6717

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 10:03 Rev Time 0.00
Received By dhayes Date 2014-09-15 Time 10:03 Sent To Z
Notes
2014-09-15 10:05:48DATE: 09/15/2014
 PROJECT: WELLS FARGO
 PERMIT#: 14040174
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 11:03 Rev Time 0.00
Received By dhayes Date 2014-07-08 Time 11:02 Sent To  
Notes
2014-07-08 11:03:41DATE: 7/8/2014
 PROJECT: WELLS FARGO
 PERMIT#: 14040174
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-06-13 Cont ID  
Sent By albarran Date 2014-06-13 Time 12:03 Rev Time 0.00
Received By albarran Date 2014-06-13 Time 11:47 Sent To B
Notes
2014-06-13 12:05:03FAILED TO ADDRESS THE ISSUES RAISED ON THE PREVIOUS
 REVIEW. SINCE THIS INVOLVES THE PLACEMENT OF NEW POLES,
 A "B" STOP WAS CREATED AND THUS ROUTED THERE FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By albarran Date 2014-04-14 Time 15:46 Rev Time 0.00
Received By albarran Date 2014-04-14 Time 15:35 Sent To I
Notes
2014-04-14 15:45:18THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED
 DOCUMENTATION AND NOTES AS MENTIONED BELOW:
 1. YOU SHALL PROVIDE SPEC SHEETS FOR THE POLES AS WELL
 AS FOR THE PROPOSED HEADS.
 2. YOU SHALL PROVIDE ENGINEERED WIND LOAD CALCULATIONS
 OF THE POLES WITH THE RESPECTIVE HEADS ATTACHED.
 3. YOU SHALL COMPLY WITH ALL THE REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION REQUIREMENTS FOR EXTERIOR
 LIGHTING.
 4. IF YOU WILL BE USING EXISTING WIRING, YOU MUST
 VERIFY THAT IT COMPLIES WITH NEC 300.5(B).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT MIKE ALBARRAN (561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2015-05-20 Cont ID  
Sent By skennedy Date 2015-05-20 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-05-11 Time   Sent To  
Notes
2015-05-12 09:37:16SENT TO S. HILLS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-04-30 Cont ID  
Sent By shill Date 2015-04-30 Time 07:40 Rev Time 0.00
Received By shill Date 2015-04-01 Time 16:04 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 09:58 Rev Time 0.00
Received By shill Date 2014-11-03 Time 15:12 Sent To  
Notes
2014-11-03 15:12:31INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-29 Cont ID  
Sent By eschneid Date 2014-09-29 Time 13:18 Rev Time 0.00
Received By eschneid Date 2014-08-29 Time 11:08 Sent To  
Notes
2014-08-29 11:09:02SENT TO D HAYES. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 11:05 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 15:50 Sent To  
Notes
2014-07-03 15:50:13TO DAH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-08 Cont ID  
Sent By shill Date 2014-06-05 Time 11:04 Rev Time 0.00
Received By dhayes Date 2014-06-05 Time 09:29 Sent To  
Notes
2014-07-08 11:05:0406/05/14 PER S. HILL
2014-06-20 18:50:136/20 TO ZONING
  
2014-06-15 14:33:396/15 TO MISC 2
  
2014-06-05 09:29:49INCOMING SENT TO ELECTRICAL BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-14 Cont ID  
Sent By albarran Date 2014-04-14 Time 15:46 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2014-04-14 15:47:15SMALL DENIED "R"
2014-04-04 10:53:07ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 4 Status P Date 2015-04-20 Cont ID  
Sent By shill Date 2015-04-30 Time 07:40 Rev Time 0.50
Received By eschneid Date 2015-04-20 Time 16:17 Sent To B
Notes
2015-04-20 16:20:30PASSED
  
 A SHEET SHOWING THAT THE PHOTOMETRIC CALCULATIONS AT
 THE MIDPOINT OF LAKE AVENUE AND WILL NOT EXCEED 0.5
 FOOTCANDLES.

Review Stop Z ZONING
Rev No 3 Status F Date 2014-11-19 Cont ID  
Sent By eschneid Date 2014-11-18 Time 12:39 Rev Time 0.50
Received By eschneid Date 2014-11-18 Time 12:39 Sent To E
Notes
2014-11-18 17:08:04FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: PROVIDE A RECENT SURVEY, LESS THAN
 ONE YEAR OLD, WHICH INCLUDES THE LOCATIONS OF THE
 EXISTING TREES ALONG LAKE AVENUE AND THE EXISTING LIGHT
 POLES. THE SURVEY SHALL BE TO SCALE WITH ALL DIMENSION
 LINES SHOWN. THE PLANS PROVIDED WERE SIGNED AND SEALED
 BY AN ENGINEER AND NOT A SURVEYOR. THE SUBMITTED PLANS
 DO NOT MATCH THE OBSERVED SITE CONDITIONS (EXISTING
 TREES NOT SHOWN ON PLANS) AND THE PROPERTY LINE DOES
 NOT MATCH AN OLDER PLAN FOR THE SITE. THE SETBACKS AND
 ROAD CENTER LINE ARE IN QUESTIONS WITHOUT A SURVEY.
  
 2) REVISED COMMENT: IT IS STATED THAT AN EXISTING TREE
 WILL BE REMOVED TO INSTALL NEW POLE G1. YOU MAY NOT
 REMOVE A REQUIRED BUFFER TREE TO INSTALL A LIGHT POLE
 UNLESS THE PLANNING DIVISION HAS APPROVED A TREE
 ALTERATION PERMIT. THE REMOVED TREE SHALL BE
 RELOCATED/REPLACED WITHIN THE BUFFER. STAFF RECOMMENDS
 THAT THE POLES SHALL BE PLACED TO AVOID REMOVING OR
 RELOCATING TREES.
  
 3) REPEAT COMMENT: THE SOUTHERN A2 POST IS ON PARCEL
 74434404000020010. A SEPARATE PERMIT APPLICATION FOR
 THE WORK ON THE 2ND PARCEL IS REQUIRED. THE SAME PLANS
 MAY BE USED FOR BOTH. ZONING WILL NOT APPROVE THIS
 PERMIT APPLICATION UNTIL THE APPLICATION FOR THE OTHER
 PROPERTY IS SUBMITTED.
  
 4) THE FOLLOWING PREVIOUS COMMENTS APPEAR TO HAVE BEEN
 ADDRESSED, BUT ARE PENDING FINAL VERIFICATION BASED ON
 THE SURVEY.
  
 A. THE SITE PLAN (OR MARKED UP SURVEY) SHALL SHOW THE
 PROPOSED NEW AND REPLACEMENT LIGHT POLES WITH THEIR
 DIMENSIONS FROM THE PROPERTY LINES. PLEASE NOTE THAT
 NEW AND REPLACEMENT POLES SHALL BE LOCATED A MINIMUM OF
 5 FEET FROM THE PROPERTY LINE.
 B. THE PHOTOMETRIC PLAN SHALL CLEARLY SHOW THE
 CENTERLINE OF LAKE AVENUE. HALF OF LAKE AVENUE ABUTTING
 THE SOUTH PORTION OF THE SITE IS RESIDENTIALLY ZONED.
 THE PHOTOMETRIC CALCULATIONS SHALL BE PROVIDED TO THE
 MIDPOINT OF LAKE AVENUE AND SHALL NOT EXCEED 0.5
 FOOTCANDLES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-09-29 Cont ID  
Sent By eschneid Date 2014-09-29 Time 11:40 Rev Time 0.50
Received By eschneid Date 2014-09-29 Time 11:40 Sent To  
Notes
2014-09-29 13:18:09FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: PROVIDE A RECENT SURVEY, LESS THAN
 ONE YEAR OLD, WHICH INCLUDES THE LOCATIONS OF THE
 EXISTING TREES ALONG LAKE AVENUE AND THE EXISTING LIGHT
 POLES. THE SURVEY SHALL BE TO SCALE WITH ALL DIMENSION
 LINES SHOWN.
  
 2) REPEAT COMMENT: THE SITE PLAN (OR MARKED UP SURVEY)
 SHALL SHOW THE PROPOSED NEW AND REPLACEMENT LIGHT POLES
 WITH THEIR DIMENSIONS FROM THE PROPERTY LINES. PLEASE
 NOTE THAT NEW AND REPLACEMENT POLES SHALL BE LOCATED A
 MINIMUM OF 5 FEET FROM THE PROPERTY LINE.
  
 3) REPEAT COMMENT: ONE OF THE NEW POLES ALONG LAKE
 AVENUE APPEARS THAT IT WOULD CONFLICT WITH AN EXISTING
 TREE. THE POLES SHALL BE PLACED TO AVOID TREES AND
 THEIR CANOPY GROWTH.
  
 4) REPEAT COMMENT: THE SOUTHERN A2 POST APPEARS THAT IT
 IS NOT ON PARCEL 74434404000020020, BUT RATHER PARCEL
 74434404000020010. THIS WILL BE VERIFIED WITH THE
 SURVEY. IF THE POST IS ON THE NEIGHBORING PARCEL, THEN
 A SEPARATE PERMIT APPLICATION FOR THE WORK ON THE 2ND
 PARCEL IS REQUIRED. THE SAME PLANS MAY BE USED FOR
 BOTH.
  
 5) REPEAT COMMENT: THE PHOTOMETRIC PLAN SHALL CLEARLY
 SHOW THE CENTERLINE OF LAKE AVENUE. HALF OF LAKE AVENUE
 ABUTTING THE SOUTH PORTION OF THE SITE IS RESIDENTIALLY
 ZONED. THE PHOTOMETRIC CALCULATIONS SHALL BE PROVIDED
 TO THE MIDPOINT OF LAKE AVENUE AND SHALL NOT EXCEED 0.5
 FOOTCANDLES. THE PROVIDED PHOTOMETRIC PLAN HAS BEEN
 UPDATED TO LOWER THE LIGHT LEVELS, BUT WITHOUT THE
 REQUIRED DIMENSIONS OR THE SURVEY, STAFF IS UNABLE TO
 VERIFY IF THIS COMMENT HAS BEEN MET.
  
 6) REPEAT COMMENT: THE LIGHT FIXTURES SHALL BE DESIGNED
 SO THAT GLARE DOES NOT SPILL INTO THE RIGHT-OF-WAY
 (DRIVERS VISION). PLEASE PROVIDE INFORMATION HOW GLARE
 WILL BE CONTROLLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By eschneid Date 2014-07-07 Time 08:44 Rev Time 0.50
Received By eschneid Date 2014-07-07 Time 08:44 Sent To E
Notes
2014-07-07 10:21:19FAILED
  
 1) PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR OLD,
 WHICH INCLUDES THE LOCATIONS OF THE EXISTING TREES
 ALONG LAKE AVENUE AND THE EXISTING LIGHT POLES. THE
 SURVEY SHALL BE TO SCALE WITH ALL DIMENSION LINES
 SHOWN.
  
 2) THE SITE PLAN (OR MARKED UP SURVEY) SHALL SHOW THE
 PROPOSED NEW AND REPLACEMENT LIGHT POLES WITH THEIR
 DIMENSIONS FROM THE PROPERTY LINES. PLEASE NOTE THAT
 NEW AND REPLACEMENT POLES SHALL BE LOCATED A MINIMUM OF
 5 FEET FROM THE PROPERTY LINE.
  
 3) ONE OF THE NEW POLES ALONG LAKE AVENUE APPEARS THAT
 IT WOULD CONFLICT WITH AN EXISTING TREE. THE POLES
 SHALL BE PLACED TO AVOID TREES AND THEIR CANOPY GROWTH.
  
 4) THE SOUTHERN A2 POST APPEARS THAT IT IS NOT ON
 PARCEL 74434404000020020, BUT RATHER PARCEL
 74434404000020010. THIS WILL BE VERIFIED WITH THE
 SURVEY. IF THE POST IS ON THE NEIGHBORING PARCEL, THEN
 A SEPARATE PERMIT APPLICATION FOR THE WORK ON THE 2ND
 PARCEL IS REQUIRED. THE SAME PLANS MAY BE USED FOR
 BOTH.
  
 5) THE PHOTOMETRIC PLAN SHALL CLEARLY SHOW THE
 CENTERLINE OF LAKE AVENUE. HALF OF LAKE AVENUE ABUTTING
 THE SOUTH PORTION OF THE SITE IS RESIDENTIALLY ZONED.
 THE PHOTOMETRIC CALCULATIONS SHALL BE PROVIDED TO THE
 MIDPOINT OF LAKE AVENUE AND SHALL NOT EXCEED 0.5
 FOOTCANDLES. THE PROVIDED PHOTOMETRIC PLAN SEEMS TO
 INDICATE HIGHER LIGHT LEVELS.
  
 6) THE LIGHT FIXTURES SHALL BE DESIGNED SO THAT GLARE
 DOES NOT SPILL INTO THE RIGHT-OF-WAY (DRIVERS VISION).
 PLEASE PROVIDE INFORMATION HOW GLARE WILL BE
 CONTROLLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.