Plan Review Details - Permit 14040173
Plan Review Stops For Permit 14040173
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 17:37 Rev Time 0.00
Received By shill Date 2015-01-29 Time 17:37 Sent To  
Notes
2015-01-29 17:46:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENT FROM PREVIOUS REVIEWS, EITHER NOT ADDRESSED,
 PARTIALLY ADDRESSED, OR ADDRESSED INCORRECTLY:
  
 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE
 VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND
 IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED, FBC
 1609.
  
 ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING,
 SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A
 REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP
 DRAWING REVIEW STAMP, OR BY LETTER.
  
 THE ENGINEERING PROVIDED BY MOLNAR JORDAN & ASSOCIATES
 SPECIFIED 6' EMBEDMENT IN REVIEW #3, ENGINEERING BY
 CHRIS ARLANDSON SPECIFIED 7' EMBEDMENT (WHICH IS NO
 LONGER IN THE PACKAGE), AND THE ENGINEERING BY MOLNAR
 JORDAY & ASSOCIATES HAS NOW BEEN REVISED TO 7'. THIS
 WOULD BE ACCEPTABLE EXCEPT THAT THE 7' EMBEDMENT
 STRUCTURAL ENGINEERING (CHRIS ARLANDSON, PE) IS NO
 LONGER A PART OF THIS SUBMITTAL (OR THE ISSUED
 SUBMITTAL).
  
 NEW CALCULATIONS WERE SUBMITTED (PREPARED BY BRIAN J.
 SIELAFF, PE AND TAMARACK GROVE ENGINEERING) WHICH
 REQUIRE AN 8'6" EMBEDMENT (SEE PAGE 7 OF 9). PLEASE
 CORRELATE. A CERTIFICATE OF AUTHORIZATION (BUSINESS
 LICENSE) FOR THE ENGINEERING COMPANY "TAMARACK GROVE
 ENGINEERING" IS REQUIRED, AND THE LICENSE NUMBER IS TO
 BE ON THE CALCULATIONS, FS471, FAC61G15-23.002. REVIEW
 BY DESIGNER OF RECORD IS REQUIRED FOR DELEGATED
 ENGINEERING.
  
 2. VALUE HAS BEEN ADJUSTED PER CONTRACT, PLEASE PAY
 FEES, THIS MAY BE DONE ONLINE, ON OUR AUTOMATED SYSTEM
 BY FOLLOWING THE PROMPTS (561-805-6700), OR AT THE
 BUILDING DIVISION CUSTOMER SERVICE COUNTER.
  
 3. FIXTURE CALCS NOT PROVIDED. PROVIDE AT INSPECTION -
 SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION FOR
 THE FIXTURE CALCS MAY BE REQUIRED, FBC 107, FBC 1609.
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 10:14 Rev Time 0.00
Received By shill Date 2014-12-01 Time 10:14 Sent To  
Notes
2014-12-01 10:14:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ENGINEERING PREVIOUSLY PROVIDED (NOW WITH THE
 VOIDED OLD SET OF PLANS) DOES NOT MATCH THE PLANS AND
 IT IS NOT CLEAR WHETHER THE SAME POLE IS PROPOSED, FBC
 1609.
  
 ENGINEER OF RECORD IS TO REVIEW DELEGATED ENGINEERING,
 SEE FAC61G15. THIS MAY BE DONE BY INCORPORATING A
 REFERENCE TO THE ENGINEERING INTO THE PLAN, A SHOP
 DRAWING REVIEW STAMP, OR BY LETTER.
  
 PLEASE NOTE THAT THE ENGINEERING PROVIDED BY MOLNAR
 JORDAN & ASSOCIATES SPECIFIES 6' EMBEDMENT, ENGINEERING
 BY CHRIS ARLANDSON SPECIFIES 7' EMBEDMENT. THE DESIGNER
 OF RECORD HAS NOT INCLUDED WIND DESIGN CRITERIA. WIND
 DESIGN CRITERIA IS INCLUDED ON WHAT I ASSUMED WAS
 DELEGATED ENGINEERING, BUT THAT IS NOW A PART OF THE
 VOIDED PLANS.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. VALUE
 IS TO INCLUDE LABOR, MATERIALS, ENGINEERING, OVERHEAD
 AND PROFIT FBC 109.
  
 3. PLEASE NOTE THAT THE POLE ENGINEERING WAS APPROVED
 WITH PROVISO. FIXTURE CALCS WERE TO BE SUBMITTED AS A
 REVISION SUBJECT TO FIELD INSPECTOR'S DISCRETION. THIS
 MAY BE SUBMITTED AT THIS TIME (BUT IS NOT REQUIRED).
  
 4. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS FOR PERMIT ISSUANCE. IF THE PREVIOUSLY REVIEWED
 POLE CALCS ARE TO BE A PART OF THE ISSUED PERMIT,
 PLEASE INCLUDE WITH THE NEW SETS. PLEASE DO NOT REMOVE
 ANY OLD SHEETS FROM THE PACKAGE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-03 Cont ID  
Sent By eschneid Date 2014-07-07 Time 10:30 Rev Time 0.00
Received By shill Date 2014-07-03 Time 15:37 Sent To  
Notes
2014-07-03 15:41:26PROVISO - FIXTURES SUBJECT TO WIND PRESSURES TO BE
 SUBMITTED AS A REVISION SUBJECT TO FIELD INSPECTOR'S
 DISCRETION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-20 Cont ID  
Sent By shill Date 2014-06-20 Time 18:53 Rev Time 0.00
Received By shill Date 2014-06-20 Time 18:53 Sent To Z
Notes
2014-06-20 18:53:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, PROVIDE STRUCTURAL DRAWINGS FOR THE LIGHT
 POLE AS PREVIOUSLY REQUESTED BY THE ELECTRICAL
 REVIEWER. INCLUDE WIND DESIGN CRITERIA.
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2015-01-06 Cont ID  
Sent By escheide Date 2015-01-06 Time 15:30 Rev Time 0.00
Received By dhayes Date 2015-01-06 Time 15:24 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 13:42 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 13:42 Sent To  
Notes
2014-11-21 13:45:34ROUTE TO MISC. 1
  
 11/21/14 PROVISO
 THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED
 DOCUMENTATION:
 1.PROVIDE SPEC SHEETS FOR THE POLES AS WELL AS FOR THE
 PROPOSED HEADS.
 2. PROVIDE ENGINEERED WIND LOAD CALCULATIONS OF THE
 POLES WITH THE RESPECTIVE HEADS ATTACHED. FBC-1609
 3. COMPLY WITH ALL THE REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION REQUIREMENTS FOR EXTERIOR LIGHTING. FBC-E
 505.2.4
 4. VERIFY EXISTING WIRING COMPLIES WITH NEC 300.5(B).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT DAVID HAYES (561) 805-6717

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 10:17 Rev Time 0.00
Received By dhayes Date 2014-09-15 Time 10:17 Sent To Z
Notes
2014-09-15 10:17:36DATE: 09/15/2014
 PROJECT: WELLS FARGO
 PERMIT#: 14040173
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 11:54 Rev Time 0.00
Received By dhayes Date 2014-07-08 Time 11:54 Sent To  
Notes
2014-07-08 11:59:15DATE: 7/8/2014
 PROJECT: WELLS FARGO
 PERMIT#: 14040173
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-06-13 Cont ID  
Sent By albarran Date 2014-06-13 Time 12:18 Rev Time 0.00
Received By albarran Date 2014-06-13 Time 12:16 Sent To B
Notes
2014-06-13 12:23:56THIS REVIEW FAILED FOR LACK OF SUPPORTING DOCUMENTS.
 THE COMMENTS MADE ON THE PREVIOUS REVIEWS WERE NOT
 FULLY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By albarran Date 2014-04-14 Time 11:52 Rev Time 0.00
Received By dhayes Date 2014-04-14 Time 14:53 Sent To I
Notes
2014-07-08 11:53:3904/04/14 OUT PER M. ALBARRAN
2014-04-14 15:19:24THIS APPLICATION WAS SUBMITTED WITHOUT ALL THE REQUIRED
 DOCUMENTATION AND NOTES AS MENTIONED BELOW:
 1. YOU SHALL PROVIDE SPEC SHEETS FOR THE POLES AS WELL
 AS FOR THE PROPOSED HEADS.
 2. YOU SHALL PROVIDE ENGINEERED WIND LOAD CALCULATIONS
 OF THE POLES WITH THE RESPECTIVE HEADS ATTACHED.
 3. YOU SHALL COMPLY WITH ALL THE REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION REQUIREMENTS FOR EXTERIOR
 LIGHTING.
 4. IF YOU WILL BE USING EXISTING WIRING, YOU MUST
 VERIFY THAT IT COMPLIES WITH NEC 300.5(B).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT MIKE ALBARRAN (561) 805-6718
  
 ROUTED TO SMALL DENIED BIN "R"

Review Stop I INCOMING/PROCESSING
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-01-30 Cont ID  
Sent By shill Date 2015-01-30 Time 07:22 Rev Time 0.00
Received By shill Date 2015-01-06 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-12-01 Cont ID  
Sent By shill Date 2014-12-01 Time 10:14 Rev Time 0.00
Received By shill Date 2014-11-03 Time 15:15 Sent To  
Notes
2014-11-03 15:16:18INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-29 Cont ID  
Sent By eschneid Date 2014-09-29 Time 13:31 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2014-08-29 11:16:14INCOMING SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 11:59 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 15:38 Sent To  
Notes
2014-07-03 15:38:117/3 TO DAH
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-08 Cont ID  
Sent By dhayes Date 2014-07-08 Time 11:51 Rev Time 0.00
Received By dhayes Date 2014-06-05 Time 09:28 Sent To  
Notes
2014-07-08 11:51:4407/07/14 PER E. SCHNIDER
2014-06-20 18:53:516/20 TO ZONING
  
2014-06-15 14:32:536/15 TO MISC 2
  
2014-06-05 09:28:45INCOMING SENT TO ELECTRIC BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-17 Cont ID  
Sent By albarran Date 2014-04-17 Time 14:24 Rev Time 0.00
Received By albarran Date 2014-04-04 Time 10:52 Sent To  
Notes
2014-04-17 14:24:40SMALL DENIED BIN "R"
2014-04-04 10:52:40ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 4 Status P Date 2015-01-22 Cont ID  
Sent By eschneid Date 2015-01-22 Time 16:26 Rev Time 0.25
Received By eschneid Date 2015-01-22 Time 16:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-11-18 Cont ID  
Sent By eschneid Date 2014-11-18 Time 09:53 Rev Time 0.50
Received By eschneid Date 2014-11-18 Time 09:53 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2014-09-29 Cont ID  
Sent By eschneid Date 2014-09-29 Time 13:28 Rev Time 0.25
Received By eschneid Date 2014-09-29 Time 13:28 Sent To  
Notes
2014-09-29 13:31:20FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: PROVIDE A RECENT SURVEY, LESS THAN
 ONE YEAR OLD, WHICH INCLUDES THE LOCATIONS OF THE
 EXISTING TREES AND THE EXISTING LIGHT POLES. THE SURVEY
 SHALL BE TO SCALE WITH ALL DIMENSION LINES SHOWN.
  
 2) REPEAT COMMENT: THE SITE PLAN (OR MARKED UP SURVEY)
 SHALL SHOW THE PROPOSED NEW AND REPLACEMENT LIGHT POLES
 WITH THEIR DIMENSIONS FROM THE PROPERTY LINES. PLEASE
 NOTE THAT NEW AND REPLACEMENT POLES SHALL BE LOCATED A
 MINIMUM OF 5 FEET FROM THE PROPERTY LINE.
  
 3) REPEAT COMMENT: SOME OF THE NEW POLES APPEAR TO
 CONFLICT WITH EXISTING TREES. THE POLES SHALL BE PLACED
 TO AVOID TREES AND THEIR CANOPY GROWTH.
  
 4) REPEAT COMMENT: THE LIGHT FIXTURES SHALL BE DESIGNED
 SO THAT GLARE DOES NOT SPILL INTO THE ADJACENT
 RIGHTS-OF-WAY (DRIVERS VISION). PLEASE PROVIDE
 INFORMATION HOW GLARE WILL BE CONTROLLED (OKEECHOBEE
 BOULEVARD AND SPENCER DRIVE).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By eschneid Date 2014-07-07 Time 10:23 Rev Time 0.25
Received By eschneid Date 2014-07-07 Time 10:23 Sent To E
Notes
2014-07-07 10:30:26FAILED
  
 1) PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR OLD,
 WHICH INCLUDES THE LOCATIONS OF THE EXISTING TREES AND
 THE EXISTING LIGHT POLES. THE SURVEY SHALL BE TO SCALE
 WITH ALL DIMENSION LINES SHOWN.
  
 2) THE SITE PLAN (OR MARKED UP SURVEY) SHALL SHOW THE
 PROPOSED NEW AND REPLACEMENT LIGHT POLES WITH THEIR
 DIMENSIONS FROM THE PROPERTY LINES. PLEASE NOTE THAT
 NEW AND REPLACEMENT POLES SHALL BE LOCATED A MINIMUM OF
 5 FEET FROM THE PROPERTY LINE.
  
 3) SOME OF THE NEW POLES APPEAR TO CONFLICT WITH
 EXISTING TREES. THE POLES SHALL BE PLACED TO AVOID
 TREES AND THEIR CANOPY GROWTH.
  
 4) THE LIGHT FIXTURES SHALL BE DESIGNED SO THAT GLARE
 DOES NOT SPILL INTO THE ADJACENT RIGHTS-OF-WAY (DRIVERS
 VISION). PLEASE PROVIDE INFORMATION HOW GLARE WILL BE
 CONTROLLED (OKEECHOBEE BOULEVARD AND SPENCER DRIVE).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.