Plan Review Details - Permit 14040162
Plan Review Stops For Permit 14040162
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-28 Cont ID  
Sent By jwitmer Date 2014-06-28 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2014-06-28 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-28 Cont ID  
Sent By jwitmer Date 2014-04-28 Time 07:18 Rev Time 0.00
Received By jwitmer Date 2014-04-28 Time 06:37 Sent To  
Notes
2014-04-28 07:18:07BUILDING PLAN REVIEW
 PERMIT: 14040162
 ADD: 1855 PALM BEACH LAKES SUITE # B10
 CONT: TBD
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 28/2014
 ACTION: DENIED
  
 1) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
  
 2) PLANS HAVE NOT BEEN STAMPED WITH THE APPROVED STAMP
 FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLET SKYE
 GROUP TENANT COORDINATION STAMP.
  
 3) PLANS DID NOT PROVIDE DETAILS FOR THE ACCESSIBLE
 GRAB BARS REQUIRED IN THE ACCESSIBLE RESTROOMS. 2010 FL
 ACCESS :
  
 3)(1) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 EXCEPT THAT AT WATER CLOSETS FOR CHILDREN?S USE
 COMPLYING WITH 604.9, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION 18 INCHES (455 MM) MINIMUM AND 27
 INCHES (685 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. THE HEIGHT OF THE
 LOWER GRAB BAR ON THE BACK WALL OF A BATHTUB SHALL
 COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 3) 609.7 INSTALLATION. GRAB BARS SHALL BE INSTALLED IN
 ANY MANNER THAT PROVIDES A GRIPPING SURFACE AT THE
 SPECIFIED LOCATIONS AND THAT DOES NOT OBSTRUCT THE
 REQUIRED CLEAR FLOOR SPACE.
  
 3)(3) 609.8 STRUCTURAL STRENGTH. ALLOWABLE STRESSES
 SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A
 VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS (1112 N) IS
 APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-28 Cont ID  
Sent By dhayes Date 2014-06-28 Time 16:13 Rev Time 0.00
Received By dhayes Date 2014-06-28 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-29 Cont ID  
Sent By rlecky Date 2014-04-29 Time 13:47 Rev Time 0.00
Received By rlecky Date 2014-04-29 Time 12:20 Sent To  
Notes
2014-04-29 13:49:3714040162
 1855 PALM BEACH LAKES BLVD
 DSW
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SJ CORDS ARE NOT ACCEPTABLE AS A WIRING METHOD TO
 INTERCONNECT THE LIGHTING FIXTURES. NEC 400.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T
 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING
 CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND
 PANEL BOARDS. 110.26
  
 PROVIDE SPECIFICATIONS AND LISTING FOR THE IFS MAIN
 DISTRIBUTION EQUIPMENT SPECIFIED AND SHOWN AS EXISTING.
 NEC 110.3
  
 THE MASTER PLAN FOR BUILDING 'B' LIMITS THE NUMBER OF
 MAIN DISCONNECTS WHICH MAY BE GROUPED IN ONE LOCATION.
 SHOW LOCATION OF THE MAIN SERVICE WITH DISCONNECTS NEC
 230.2; 230.40; 230.70; 230.71
  
 PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP
 EQUIPMENT. NEC 210.8; 210.63
  
 VENDING MACHINES REQUIRE GFCI PROTECTION. NEC 422.51
  
 PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED
 AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP
 OR WET LOCATIONS. NEC 110.3, 110.8,
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY, VOICE, AND DATA SYSTEMS
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By scaldero Date 2014-04-21 Time 13:16 Rev Time 0.00
Received By scaldero Date 2014-04-21 Time 13:15 Sent To  
Notes
2014-04-21 13:16:28PERMIT # 14040162
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR ON EACH DOOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-28 Cont ID  
Sent By dhayes Date 2014-06-28 Time 16:13 Rev Time 0.00
Received By dhayes Date 2014-06-12 Time 07:29 Sent To  
Notes
2014-06-16 07:29:52RESUBMITTAL SENT TO C31 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 09:56 Rev Time 0.00
Received By eschneid Date 2014-04-14 Time 06:19 Sent To  
Notes
2014-04-15 06:19:28INCOMING SENT TO C19 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-02 Cont ID  
Sent By hmoser Date 2014-05-02 Time 11:37 Rev Time 0.00
Received By hmoser Date 2014-05-02 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-28 Cont ID  
Sent By jwitmer Date 2014-06-28 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2014-06-28 Time 09:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-28 Cont ID  
Sent By jwitmer Date 2014-04-28 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-04-28 Time 06:37 Sent To  
Notes
2014-04-28 07:28:59PLUMBING PLAN REVIEW
 PERMIT: 14040162
 ADD: 1855 PALM BEACH LAKES SUITE # B10
 CONT: TBD
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 28/2014
 ACTION: DENIED
  
 1) P5.1 SANITARY WASTE STICK. ELECTRIC WATER HEATER PAN
 IS SHOWN TO TIE DIRECTLY INTO THE BUILDING DRAIN.
 DISCREPANCY, 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION 107.2.1.3 THE WRITEN DESCRIPTION UNDERTHE
 HEADING PLUMBING FIXTURE SCHEDULE WH-1 INDICATES A 3/4
 INCH DRAIN FROM THE PAN TO THE JR-1.
  
 2) SHEET P5.1 UNDER THE HEADING PLUMBING FIXTURE
 SCHEDULE FD-1 FLOOR DRAIN INDICATES THE USE OF ATRAP
 GAURD DEVICE INSTEAD OF A TRAP PRIMER.
  
 1002.3 PROHIBITED TRAPS.
 THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS
 THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL.
  
 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop POLICE POLICE
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 10:02 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2014-05-06 10:02:14CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY'S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: "THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A 'SAFE' CLIMATE
 WITHIN A BUILT ENVIRONMENT" RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS "QUALITY OF LIFE." A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER'S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 09:48 Rev Time 0.25
Received By eschneid Date 2014-05-06 Time 09:48 Sent To  
Notes
2014-04-21 14:50:544/21/14