Plan Review Details - Permit 14040157
Plan Review Stops For Permit 14040157
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-28 Cont ID  
Sent By jwitmer Date 2014-06-28 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2014-06-28 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-23 Cont ID  
Sent By jwitmer Date 2014-04-23 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2014-04-23 Time 05:49 Sent To  
Notes
2014-04-23 07:28:10BUILDING PLAN REVIEW
 PERMIT: 14040157
 ADD: 1875 PALM BEACH LAKES SUITE # A05
 CONT: TBD
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 23/2014
 ACTION: DENIED
  
 1) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
  
 2) PLANS HAVE NOT BEEN STAMPED WITH THE APPROVED STAMP
 FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLET SKYE
 GROUP TENANT COORDINATION STAMP.
  
 3) SHEET A01:
  
 3A) PLEASE REVIEW THE OCCUPANT LOAD COUNT OF 910
 PERSONS VERSES THE EGRESS PERSON COUNT WHEN TOTALED OF
 747. DISCREPANCY. 910 PERSONS OCCUPANT LOAD COUNT TIMES
 (X) 0.20= 182.0 INCHES.
  
 3B) EGRESS WIDTH PER 2010 FBC-B SECTION 1005.1 MINIMUM
 REQUIRED EGRESS WIDTH.
 THE MEANS OF EGRESS WIDTH SHALL NOT BE LESS THAN
 REQUIRED BY THIS SECTION. THE TOTAL WIDTH OF MEANS OF
 EGRESS IN INCHES (MM) SHALL NOT BE LESS THAN THE TOTAL
 OCCUPANT LOAD SERVED BY THE MEANS OF EGRESS MULTIPLIED
 BY 0.3 INCH (7.62 MM) PER OCCUPANT FOR STAIRWAYS AND BY
 0.2 INCH (5.08 MM) PER OCCUPANT FOR OTHER EGRESS
 COMPONENTS. THE WIDTH SHALL NOT BE LESS THAN SPECIFIED
 ELSEWHERE IN THIS CODE. MULTIPLE MEANS OF EGRESS SHALL
 BE SIZED SUCH THAT THE LOSS OF ANY ONE MEANS OF EGRESS
 SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50
 PERCENT OF THE REQUIRED CAPACITY. THE MAXIMUM CAPACITY
 REQUIRED FROM ANY STORY OF A BUILDING SHALL BE
 MAINTAINED TO THE TERMINATION OF THE MEANS OF EGRESS.
  
 4) PLEASE SEE SHEET A1.2 WITH THE OCCUPANT LOAD OF 1080
 OCCUPANTS, TOTAL OCCUPANTS = 1000 VERSES THE OCCUPANT
 LOAD OF 910 FOUND ON SHEET A01. PLEASE EXPLAIN WHICH OF
 THE OCCUPANT LOADS IS CORRECT, NOTE IF THE 1000 OR MORE
 IS CORRECT THE 2010 FBC-B TABLE 1021.1WOULD REQUIRE A
 4TH EXIT WHICH WOULD REQUIRE THE EXIT ACCESS THROUGH
 THE STOCK/ STORAGE ROOM QND WOULD NEED TO MEET
 THEFOLLOWING REQUIREMENTS:
 2010 FBC-B 014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H,
 S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING
 ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD
 OCCUPANCY GROUP.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
 1. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH A KITCHEN
 AREA SERVING ADJOINING ROOMS CONSTITUTING PART OF THE
 SAME DWELLING UNIT OR SLEEPING UNIT.
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 5) SHEET A2.3 SHOWS THE MEZZANINE AREA, 1ST AND 2ND
 FLOOR, THE 2 HOUR FIRE RATED WALL ASSMBLY, BUT THE DOOR
 LEADING FROM THE 2 HR WALL ASSEMBLY TO THE GENERAL
 SALES FLOOR IS NOT IDENTIFIED. PLEASE REFER TO SHEET
 A3.2 THE DOOR SCHEDULE AND REVIEW ALL THE DOORS 1ST AND
 2ND FLOOR ON THE DOOR SCHEDULE FOR THIS AREA THEY ARE
 ALL WRONG. NO FIRE RATING FOUND FOR THIS DOOR. SHEET
 A7.2 DOORS MATCH THE SCHEDULE BUT DOOR 123 DOES NOT
 HAVE A 1 1/2 HR FIRE RATING. SEE OPENING PROTECTIVES
 2010 FBC-B TABLE 7.15
  
 6) THE PLANS ALSO SHOW A VERTICAL LIFT BUT NO PRODUCT
 INFORMATION WAS PROVIDED ON THE LIFT. 2010 FL
 ACCESSIBILITY CODE 221.1.1 FLORIDA VERTICAL
 ACCESSIBILITY.
 NOTHING IN THIS CODE RELIEVES THE OWNER OF ANY
 BUILDING, STRUCTURE, OR FACILITY GOVERNED BY THIS CODE
 FROM THE DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL,
 REGARDLESS OF WHETHER THE ADA STANDARDS FOR ACCESSIBLE
 DESIGN REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 2010 FL ACCESSIBILITY CODE 408 LIMITED-USE /
 LIMITED-APPLICATION ELEVATORS 408.1 GENERAL.
 LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL COMPLY
 WITH 408 AND WITH ASME A17.1 (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
 THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME
 A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC.
  
 7) NEITHER A2.3, A7.2 NOR E2.1 SHOW ANY SMOKE ALARMS IN
 THE STAIRWWELL CORRIDOR CEILING OR ON THE ADJACENT
 CORRIDOR CEILING # 113. THIS WAS A REQUEST FROM BOTH
 BUILDING & FIRE SINCE THE MEZZANINE DESIGN WAS A HYBRID
 SYSTEM, WITH A OCCUPANT LOAD GRATER THAN 10, THE 2 HOUR
 FIRE RATING AROUND THE STAIR CORRIDOR AND EXIT DOOR TO
 THE EXTERIOR WERE ALSO PART OF THE REQUIREMENTS SINCE
 THE PLANS LACKED 2 MEANS OF EGRESS THIS DESIGN WAS A
 EQUIZALENCY TO UNDER ALTERNANTE MATERIALS AND METHODS.
  
 8) HIGH PILE STORAGE RACKING SYSTEM DOES NOT PROVIDE
 HOW CLOSE THE FIRE SPRINKLERS ARE TO THE RACKING SYSTEM
 WITH THE BOXED CONTENCE ON THE TOP OF THE RACK.
 THERE ARE NO MANUFACTURERS INSTALATION INSTRUCTIONS,
 MAXIMUM LOADING OF RACKS NOR IS THERE INFORMATION AS TO
 THE ANCHORING OF THE RECK SYSTEMS.
 2010 FBC-B 413.1 GENERAL. HIGH-PILED STOCK OR RACK
 STORAGE IN ANY OCCUPANCY GROUP SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-16 Cont ID  
Sent By dhayes Date 2014-05-16 Time 13:00 Rev Time 0.00
Received By dhayes Date 2014-05-16 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-02 Cont ID  
Sent By scaldero Date 2014-07-02 Time 14:04 Rev Time 0.00
Received By scaldero Date 2014-07-02 Time 14:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By scaldero Date 2014-04-21 Time 13:44 Rev Time 0.00
Received By scaldero Date 2014-04-21 Time 13:42 Sent To  
Notes
2014-04-21 13:44:44PERMIT # 14040157
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***OCCUPANT LOAD LISTED ON SHEET "A0.1" DIFFERS FROM
 OCCUPANT LOAD LISTED ON SHEET "A1.2" BY OVER 100
 PERSONS.***
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR ON EACH DOOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-03 Cont ID  
Sent By skennedy Date 2014-07-03 Time 10:57 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-16 Cont ID  
Sent By dhayes Date 2014-05-16 Time 13:39 Rev Time 0.00
Received By dhayes Date 2014-04-14 Time 06:09 Sent To  
Notes
2014-04-15 06:10:42INCOMING SENT TO C16 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-02 Cont ID  
Sent By hmoser Date 2014-05-02 Time 14:18 Rev Time 0.00
Received By hmoser Date 2014-05-02 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-23 Cont ID  
Sent By jwitmer Date 2014-04-23 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2014-04-23 Time 05:50 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 11:58 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2014-05-06 11:58:40CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY'S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: "THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A 'SAFE' CLIMATE
 WITHIN A BUILT ENVIRONMENT" RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS "QUALITY OF LIFE." A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER'S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By eschnied Date 2014-07-01 Time 14:05 Rev Time 1.00
Received By eschneid Date 2014-07-01 Time 14:05 Sent To  
Notes
2014-07-01 14:05:07PASSED W/PROVISOS
  
 1) ZONING SHALL APPROVE ANY SHELVING INSTALLED IN FRONT
 OF THE STOREFRONT WINDOWS AS PART OF THE RACKING SYSTEM
 PERMIT.
  
 2) ALL EXTERIOR SIGNAGE REQUIRES SEPARATE PERMITS, WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-06 Cont ID  
Sent By eschneid Date 2014-05-06 Time 11:58 Rev Time 0.75
Received By eschneid Date 2014-05-06 Time 11:58 Sent To  
Notes
2014-05-06 14:33:57FAILED
  
 PLEASE RESPONE IN WRITING.
  
 1) PLEASE CLARIFY WHY THE TENANT SPACE ON THE SHELL
 PERMIT IS SHOWN AS 32,400 SQ. FT., YET THIS PERMIT
 SHOWS THE SPACE HAVING 31,546 SQ. FT.
  
 2) IT APPEARS FROM THE HIGH PILE STORAGE PLAN, THAT
 THERE WILL BE SOME SORT OF SHELVING INSTALLED IN FRONT
 OF THE STOREFRONT WINDOWS. PLEASE CLARIFY WHAT IS
 HAPPENING IN FRONT OF THE WINDOWS. PLEASE REMEMBER THAT
 THE PALM BEACH OUTLETS DESIGN GUIDELINES REQUIRE THAT
 CUSTOMERS BE ABLE TO LOOK INTO THE STORE FROM THE
 OUTSIDE.
  
 3) ALL EXTERIOR SIGNAGE REQUIRES SEPARATE PERMITS, WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  