Plan Review Details - Permit 14040101
Plan Review Stops For Permit 14040101
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 17:43 Rev Time 0.00
Received By shill Date 2014-04-09 Time 17:43 Sent To  
Notes
2014-04-09 17:48:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. . IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 2. IF SHUTTERS ARE USED, SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.4. INCLUDE THE ROOM DESIGNATION.
  
 3. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FBC
 107. FAILURE TO PROVIDE TWO SETS MAY RESULT IN COPY
 FEES.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 17:49 Rev Time 0.00
Received By shill Date 2014-04-09 Time 17:49 Sent To  
Notes
2014-04-03 10:29:54ROUTED TO BUILDING LESS THAN $5000