Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-25 Cont ID  
Sent By shill Date 2014-04-25 Time 11:31 Rev Time 0.00
Received By shill Date 2014-04-25 Time 11:31 Sent To  
Notes
2014-04-25 11:56:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE DETAILS ON SECTION 1 ARE NOT CONSISTENT WITH UL
 SYSTEM U433. FOR INSTANCE, THE MIN 3" THICK MINERAL
 WOOL IS NOT INCLUDED IN THE WALL SECTION. FBC 703.2.
 PLEASE REVISE.
  
 2. HOW HAS IT BEEN DETERMINED THAT A 1 HOUR SEPARATION
 IS REQUIRED RATHER THAN A 2 HOUR? IF THE BUILDING IS
 FULLY SPRINKLERED, PLEASE NOTE ON THE PLAN. SEE FBC
 508, TABLE 508.4.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By rferguso Date 2014-04-14 Time 13:03 Rev Time 0.00
Received By rferguso Date 2014-04-14 Time 13:03 Sent To  
Notes
2014-04-14 13:14:26400 NORTH FLAGLER DRIVE
 PERMIT #14040100
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 * NO (ADDRESS) PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION. PLEASE PROVIDE AN (ADDRESS) ON THE PLAN
 INDICATING WHERE THE WORK IS BEING PERFORMED.
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE (561)804-4700

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By shill Date 2014-04-25 Time 11:57 Rev Time 0.00
Received By shill Date 2014-04-03 Time 17:13 Sent To  
Notes
2014-04-03 17:13:22REVISION SENT TO FIRE SHELF FOR REVIEW. JG.