Plan Review Details - Permit 14031153
Plan Review Stops For Permit 14031153
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 08:51 Sent To  
Notes
2014-05-10 09:46:172010 FBC
  
 EXTERIOR DOORS AND WINDOWS UNDER SEPARATE PERMIT. ( SEE
 PERMIT NUMBER 14031152 )

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 19:35 Rev Time 0.00
Received By albarran Date 2014-05-22 Time 18:44 Sent To I
Notes
2014-05-22 19:21:18APPROVED W/THE FOLLOWING NOTES:
  
 1. AS PER NEC THE INTERIOR OF AN UNDERGROUND (OR IN
 CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET
 LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE
 LISTED ACCORDINGLY.
  
 2. HAVC IN ATTIC NOTICE: HVAC EQUIPMENT INSTALLED IN
 ATTICS ARE SUBJECT TO SPECIFIC NEC REQUIREMENTS:
 NEC 110.33(B) REQUIRES A PERMANENT LADDER TO THE ATTIC
 NEC 210.63 REQUIRES A SERVICE OUTLET INSIDE THE ATTIC
 NEC 210.70 REQUIRES THAT THERE BE A LIGHT INSIDE THE
 ATTIC &
 NEC 410.11 REQUIRES THAT THE LIGHT HAVE A GUARD AROUND
 THE LAMP
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By albarran Date 2014-04-24 Time 14:53 Rev Time 0.00
Received By albarran Date 2014-04-24 Time 14:30 Sent To  
Notes
2014-04-24 14:56:55THE ELECTRICAL PAGE HAS NO ELECTRICAL NOTES
 PROVIDE A RISER DIAGRAM ALONG WITH A PANEL SCHEDULE.
 ALL NEW WORK SHALL COMPLY WITH THE 2008 EDITION OF THE
 NEC
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 19:34 Rev Time 0.00
Received By albarran Date   Time   Sent To PC
Notes
2014-05-22 19:35:18PROCESSED AND SENT TO READY RACK "B"
2014-05-22 16:44:05ROUTE TO M.A'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2014-03-31 Time 08:59 Sent To  
Notes
2014-04-01 09:23:04R21
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 08:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-03 Cont ID  
Sent By llouie Date 2014-04-03 Time 15:38 Rev Time 0.00
Received By llouie Date 2014-04-03 Time 15:38 Sent To  
Notes
2014-04-03 15:41:55NOTES:
  
 * INTERIOR RENOVATIONS APPROVED FOR PRINCIPAL BUILDING
 ONLY; NO CHANGE TO EXISTING BUILDING FOOTPRINT.
  
 * COST OF CONSTRUCTION DOES NOT EXCEED 50 PERCENT VALUE
 OF THE STRUCTURE.
  
 * NEW EXTERIOR STEPS DETECTED AT REAR OF PRINCIPAL
 BUILDING. A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 NEW STEPS.