| 2014-04-17 11:12:27 | NOTICE TO FIRE ALARM CONTRACTOR: | | | ALL DOCUMENTATION AS REQUIRED PER NFPA 72 SECTION 4.5 | | | SHALL BE PROVIDED UPON COMPLETION AND BE AVAILABLE FOR | | | FINAL INSPECTION. | | | FOR FINAL INSPECTION THIS SYSTEM SHALL UNDERGO A | | | REACCEPTANCE TEST AS PER NFPA 72, SECTION 10.4.1.2. | | | RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM LOG AS | | | REQUIRED. |
|
|