Plan Review Details - Permit 14031109
Plan Review Stops For Permit 14031109
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-14 Cont ID  
Sent By rmcdouga Date 2014-04-14 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2014-04-14 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-31 Cont ID  
Sent By rmcdouga Date 2014-03-31 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2014-03-31 Time 13:31 Sent To  
Notes
2014-03-31 14:51:192010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE CERTAIN-TEED MODIFIED
 BITUMEN ROOFING HAS A DESIGN PRESSURE OF 60 PSF, WHICH
 IS TOO LOW FOR THE CORNER AND PERIMETER AREAS. SUBMIT 2
 SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION #7 OF NOA
 NO.13-0204.03.
  
 2) THE PRODUCT APPROVAL FOR THE OWENS CORNING ROOF
 VENT, FL# 16828, HAS NOT BEEN APPROVED BY THE STATE AT
 THIS TIME. IT'S STATUS IS LISTED AS PENDING. PLEASE
 SUBMIT A CURRENT PRODUCT APPROVAL AS REQUIRED BY DCA
 RULE 9N-3.
  
 3) ONLY THE COVERSHEET WAS SUBMITTED FOR THE IKO
 ASPHALT SHINGLES WITH FL# 7006. SUBMIT TWO COPIES OF
 THE INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE
 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-14 Cont ID  
Sent By rmcdouga Date 2014-04-14 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2014-04-09 Time 16:39 Sent To  
Notes
2014-04-10 16:39:54RESUBMITTAL SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.