Plan Review Details - Permit 14031056
Plan Review Stops For Permit 14031056
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2015-07-31 Time 19:27 Sent To M
Notes
2015-08-03 07:04:052010 FBC
 ADDITION OF MASTER SUITE
  
 DENIED BY BUILDING
 (REPEAT COMMENT)
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON EACH SHEET OF THE PLANS. CITY
 AMENDMENTS 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-26 Cont ID  
Sent By rmcdouga Date 2014-08-26 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2014-08-26 Time 16:51 Sent To  
Notes
2014-08-26 18:33:192010 FBC
 ADDITION OF MASTER SUITE
  
 DENIED BY BUILDING
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON EACH SHEET OF THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 2) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 GRACE WATER / ICE SHIELD ROOFING UNDERLAYMENT THAT IS
 SPECIFIED ON THE PLANS. DCA RULE 9N-3 (SEE WALL
 SECTIONS 7 & 8 ON SHEET A1.)
  
 3) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By rmcdouga Date 2014-06-03 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2014-06-02 Time 19:01 Sent To  
Notes
2014-06-03 10:03:172010 FBC
 ADDITION OF MASTER SUITE
  
 DENIED BY BUILDING
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS
 107.2.1
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY THE 2010 FBC ENERGY
 CONSERVATION SECTION 40.2. THE FORMS ARE REQUIRED TO BE
 SIGNED AND DATED BY THE PREPARER AND OWNER/AGENT.
  
 3) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE
 STRUCTURE IS LOCATED IN A 170 MPH VULT WIND SPEED AND
 THE DEFAULT EXPOSURE CATEGORY IS "C". CITY AMENDMENTS
 107.5.3
  
 4) SPECIFY THE REQUIRED WIND DESIGN PRESSURES FOR THE
 EXTERIOR OPENINGS ON THE PLANS. CITY AMENDMENTS 107.5.3
  
 5) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 GRACE WATER / ICE SHIELD ROOFING UNDERLAYMENT THAT IS
 SPECIFIED ON THE PLANS. DCA RULE 9N-3
  
 7) THE WINDOW SCHEDULE ON SHEET A1 SPECIFIES THAT ALL
 OF THE WINDOWS ARE SINGLE HUNG. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR HORIZONTAL SLIDING WINDOWS.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 8) THE WINDOW SCHEDULE ON SHEET A1 SPECIFIES PGT
 WINGUARD WINDOWS AND DOORS AND LAWSON PRODUCT APPROVALS
 WERE SUBMITTED. THE DESIGNER DID NOT STATE THAT AN
 APPROVED EQUAL COULD BE USED ON THE PLANS. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-07-31 Cont ID  
Sent By albarran Date 2015-07-31 Time 10:11 Rev Time 0.00
Received By albarran Date 2015-07-31 Time 08:36 Sent To  
Notes
2015-07-31 11:03:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PLEASE NOTE THAT RESUBMITTING INSTRUCTIONS WERE
 PROVIDED YOU WITH THE SECOND ELECTRICAL DENIAL. THOSE
 DIRECTIONS HAVE NOT BEEN FOLLOWED. PLEASE DO SO THIS
 TIME AROUND.
 2. THE RISER DIAGRAM REFLECTS TWO PANEL, THE LOCATION
 OF WHICH ARE NOT INDICATED ON THE PLANS.
 3. A CIRCUIT DIRECTORY AS PER NEC 408.4 SHALL BE
 PROVIDE FOR THE NEW 60 AMP PANEL INDICATED ON THE
 RISER.
 4. YOU SHALL ALSO PROVIDE LOAD CALC FOR THE NEW 60 AMP
 PANEL.
 5. THE RISER SHOWS THE NEW 60 AMP PANEL BEING SERVED
 FROM DISC A, BUT PANEL A DOES NOT REFLECT AN OCPD FOR
 THE NEW PANEL.
 6. YOU SHALL SUBMIT A WHOLE HOUSE FLOOR PLAN INDICATING
 THE RELATION OF THE NEW ADDITION TO THE EXISTING. SHOW
 ON IT THE LOCATION OF THE FPL SERVICE METER, MAIN
 DISCONNECT, ALL ELECTRICAL PANELS AND EXISTING SMOKE
 DETECTORS.
 7. THE ELECTRICAL GFI OUTLET FOR THE HYDROMASSAGE TUB
 SHALL BE IN AN ACCESSIBLE LOCATION AS PER NEC 680.71.
 FURTHERMORE ALL THE ELECTRICAL COMPONENTS SHALL BE
 ACCESSIBLE WITH DAMAGING THE WALLS AS PER NEC 680.73.
 8. ALL REPLACEMENT RECEPTACLES SHALL BE
 TAMPER-RESISTANT AND COMPLY WITH NEC 406.3 (D)(1) TO
 (D)(3)
 9. ALL OUTDOOR RECEPTACLES SHALL BE RATED AS WEATHER
 RESISTANT "WR".
 10 ALL OUTLETS INSTALLED IN CEILING SHALL BE RATED TO
 SUPPORT 50# AS PER NEC 314.27
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2014-07-18 Time   Rev Time 0.00
Received By dhayes Date 2014-07-18 Time 16:09 Sent To  
Notes
2014-07-22 09:48:48DATE: 7/22/2014
 PROJECT: MURRAY RESIDENCE
 PERMIT#: 14031056
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PLEASE REVISE YOUR PLANS TO MAKE THE FOLLOWING
 CORRECTIONS:
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1
  
 2) PROVIDE A SINGLE LINE RISER DIAGRAM, LOAD
 CALCULATION AND A PANEL SCHEDULE INDICATING SIZE OF THE
 ELECTRICAL SERVICE, THE TOTAL CONNECTED LOAD, AND THE
 CAPACITY OF THE PANEL TO FEED THE ADDITIONAL LOAD AND
 CIRCUITRY. INDICATE ON THE PLANS THE LOCATION OF THE
 ELECTRICAL SERVICE AND PANEL . FBC 107.2.1
  
 3) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B) INICATE ON THE PLANS PROPER ACCESS TO
 SERVICE THE UNIT IN THE ATTIC.
  
 4) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3) REVISE PLANS TO INDICATE THE SERVICE LIGHT BY
 THE POINT OF ENTRY TO SERVICE THE MECHANICAL EQUIPMENT
  
 5) THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE
 DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. NEC 440.11
  
 6) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC
 440.14. REVISE THE PLANS TO INDICATE A DISCONNECTING
 MEANS AT OR NEAR THE MECHANICAL EQUIPMENT.
  
 7) AIR HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
  1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED
 WITHIN SIX (6) FEET (1829 MM) OF AN ATTIC ACCESS.
  2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT
 THE UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT
 WORKING PROPERLY.
  3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
 NOTICE TO HOMEOWNER FBC-M 306.3.2
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE AIR
 CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED. YOUR AIR CONDITIONING SYSTEM
 IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING:
 1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR;
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
 REVISE PLANS TO INDICATE COMPLIANCE.
  
 8) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3),
  
 9) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3 AND 314.3.1
 FBC-R 314.3 LOCATION STATES IN PART: "SMOKE ALARMS
 SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS: 1. IN
 EACH SLEEPING ROOM. 2. OUTSIDE EACH SEPARATE SLEEPING
 AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS." THE
 PLANS SUBMITTED INDICATE ONLY ONE SMOKE DETECTOR
 INSTALLED IN THE BEDROOM. PLEASE MAKE A NOTE ON THE
 PLANS INDICATING COMPLIANCE WITH THE ABOVE REFERENCED
 CODE.
  
 10) THERE IS A NOTE ON THE PLAN INDICATING THE TUB IS
 TO BE A HYDRO MASSAGE TUB INSTALLED IN THE NEW MASTER
 BATH. HOWEVER THERE IS NO GFI OUTLET ON THE PLAN IN AN
 ACCESSABLE LOCATION TO FEED IT. PLEASE PROVIDE THE
 PRODUCT APPROVAL SHEETS ON THE PROPSED TUB AND INDICATE
 THE CIRCUIT PROPOSED TO BE USED TO FEED THE NEW OUTLET
 ON THE PANEL SCHEDULE AND INCLUDE THE LOAD IN THE LOAD
 CALCULATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By albarran Date 2014-04-24 Time 11:29 Rev Time 0.00
Received By albarran Date 2014-04-24 Time 10:32 Sent To  
Notes
2014-04-24 11:53:54FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
 1. THE MECHANICAL PLAN SHOWS A NEW MINI-SPLIT A/C
 SYSTEM THAT IS NOT REFLECTED ON THE ELECTRICAL PLANS.
 2. YOU SHALL INCLUDE THIS UNIT ALONG WILL ALL
 ASSOCIATED ELECTRIC, DISCONNECT ETC. ON THE ELECTRICAL
 PLAN.
 3. IF THIS UNIT IS TO BE INSIDE THE ATTIC, ADDITIONAL
 REQUIREMENTS WILL APPLY. JUST TO MENTION A FEW: PROPER
 LIGHTING, A SERVICE OUTLET AND A PERMANENT LADDER
 4. PROVIDE A PANEL SCHEDULE AND LOAD CALCS TO VERIFY
 AMPLE CAPACITY FOR THE ADDED LOAD.
 5. FOR CONVENIENCE AND ENERGY CONSERVATION ONLY, THREE
 WAY SWITCHING SHOULD BE PROVIDE AT THE HALLWAY AND
 MULTIPLE ENTRANCES TO THE BEDROOM.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-06 Cont ID  
Sent By hmoser Date 2015-08-06 Time 13:30 Rev Time 0.00
Received By hmoser Date 2015-06-26 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-27 Cont ID  
Sent By dhayes Date 2014-08-27 Time 15:21 Rev Time 0.00
Received By hmoser Date 2014-07-18 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-03 Cont ID  
Sent By rmcdouga Date 2014-06-03 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2014-03-27 Time 18:09 Sent To  
Notes
2014-03-27 18:11:47INCOMING SENT TO R-05 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 07:06 Sent To  
Notes
2015-08-03 07:06:25IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By rmcdouga Date 2014-06-02 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2014-06-02 Time 18:46 Sent To  
Notes
2014-06-02 18:47:50IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-08-21 Cont ID  
Sent By hmoser Date 2015-08-21 Time 13:15 Rev Time 0.00
Received By hmoser Date 2015-08-21 Time 13:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-08-06 Cont ID  
Sent By hmoser Date 2015-08-06 Time 13:09 Rev Time 0.00
Received By hmoser Date 2015-08-06 Time 11:57 Sent To  
Notes
2015-08-06 13:09:49PLAN DENIED
 1) PROVIDE UP DATED ENERGY CALCULATIONS
 VOID PAGES NOT BEING USED
  
 PLEASE CALL IF YOU HAVE ANY QUESTIONS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-07-29 Cont ID  
Sent By jsaez Date 2014-07-29 Time 15:01 Rev Time 0.00
Received By jsaez Date 2014-07-29 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By jsaez Date 2014-05-29 Time 15:33 Rev Time 0.00
Received By hmoser Date 2014-08-27 Time 15:22 Sent To  
Notes
2014-05-29 15:31:24FAILED MECHANICAL REVIEW AS FOLLOWS:
 1.ENERGY CALCULATION.
 2. PROVIDE MINI SPLIT DETAIL SCHEDULE,C.U., COND DRAIN
 LOCATION.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-22 Cont ID  
Sent By gjohnson Date 2015-07-22 Time 08:31 Rev Time 0.00
Received By gjohnson Date 2015-07-22 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-26 Cont ID  
Sent By rmcdouga Date 2014-08-26 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2014-08-26 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By rmcdouga Date 2014-06-02 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2014-06-02 Time 18:48 Sent To  
Notes
2014-06-02 19:00:562010 FBC
  
 PLUMBING DENIED
  
 1) THE WATER-CLOSET AND SHOWER IN THE PROPOSED BATHROOM
 ARE NOT PROPERLY VENTED. NOT MORE THAN ONE WET-VENTED
 FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION PER FBCR P3108.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-05 Cont ID  
Sent By dkittred Date 2014-08-05 Time 15:37 Rev Time 0.00
Received By dkittred Date 2014-08-05 Time 15:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-28 Cont ID  
Sent By dkittred Date 2014-03-28 Time 10:51 Rev Time 0.00
Received By dkittred Date 2014-03-28 Time 10:22 Sent To  
Notes
2014-03-28 10:50:563/28/14 SENT BACK TO R05. DK
  
2014-03-28 10:50:42PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/28/14
  
 1. SITE PLAN NEEDS TO INDICATE SETBACKS OF THE PROPOSED
 ADDITION TO DEMONSTRATE COMPLIANCE WITH SETBACKS OF THE
 SF7 ZONING DISTRICT (ZLDR SEC. 94-72).
  
 2. THE VALUE OF THE CONSTRUCTION ($47,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($59,683) ACCORDING TO THE
 PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR
 SEC. 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS,
 AT LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-03-28 10:03:133/28/14