Plan Review Details - Permit 14031030
Plan Review Stops For Permit 14031030
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-05 Cont ID  
Sent By dhayes Date 2014-05-05 Time 12:58 Rev Time 0.00
Received By dhayes Date 2014-05-05 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 09:40 Rev Time 0.00
Received By skennedy Date 2014-05-09 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-05 Cont ID  
Sent By dhayes Date 2014-05-05 Time 13:03 Rev Time 0.00
Received By dhayes Date 2014-03-27 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-27 Cont ID  
Sent By rregueir Date 2014-03-27 Time 17:13 Rev Time 0.00
Received By rregueir Date 2014-03-27 Time 17:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 09:40 Rev Time 0.00
Received By skennedy Date 2014-05-17 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 08:47 Sent To  
Notes
2014-04-18 10:29:37PLUMBING PLAN REVIEW
 PERMIT:14031030
 ADD: 6651N JOG RD
 CONT:
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:FRI. APRIL 18/2014
 ACTION: DENIED
  
 1) SHEET 200-PL-000 PIPE EQUIPMENT & MATERIAL NOTES:
 NOTE # 4, SANITARY, STORM DRAIN PIPE AND VENT PIPING
 UNDERGROUND & ABOVE GROUND WITHIN FRAME WALLS. BLOCK
 MASONRY OR PIPE CHASE SHALL BE TYPE DWV, TO ASTM D2665,
 D2949 AND D3034. PLEASE REVIEW 2010 FBC-P TABLE 702.1
 ABOVE GROUND DRAINAGE AND VENT AND TABLE 702.2 BOTH
 REQUIRED DMV TO MEET STANDARD ASTM B75, ASTM B88, ASTM
 B 251 OR ASTM B 306. THE USE OF DWV AS STORM SUBSOIL
 DRAIN PIPE WITHIN THE BUILDING IS NOT ALLOWED SEE TABLE
 1102.5.
  
 2) SHEET 200-PL-900 ELEVATION 50'-0" REVISION # 3
 YELLOW BOX WITH COMMENT WHERE WE ROUTE THIS VENT PIPE
 APPEARS THAT THE DESIGNER OF RECORD STILL HAS SOME WORK
 TO DO BEFORE THIS PAGE IS SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2014-06-05 Cont ID  
Sent By skennedy Date 2014-06-05 Time 14:38 Rev Time 0.00
Received By skennedy Date 2014-06-04 Time 14:16 Sent To  
Notes
2014-06-05 14:38:16THE SIGNATURE REPORT CONTAINS ONE FILE URL AS FOLLOWS:
 200-EE-300, HOWEVER THE DRAWING FILE CONTAINS TWO
 DRAWINGS WITH THIS NAME THAT DIFFER IN THAT ONE IS A
 REV1 AND THE OTHER IS A REV3. THE REV1 HAS THE TILLE
 BLOCK NUMBER 200-EE-302.
  
 THE SIGNATURE REPORT CONTAINS ONE FILE URL AS FOLLOWS:
 200-EE-400, HOWEVER THE DRAWING FILE CONTAINS TWO
 DRAWINGS WITH THIS NAME THAT DIFFER IN THAT ONE IS A
 REV1 AND THE OTHER IS A REV4. THE REV1 HAS THE TILLE
 BLOCK NUMBER 200-EE-402.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 07:46 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 07:22 Sent To  
Notes
2014-05-28 07:51:20THE SIGNATURE REPORT IS MISSING SHEET ME501,
 ADDITIONALLY THE REPORT CONTAINS THE FOLLOWING FILE
 NAMES WHICH WERE NOT REVIEWED AND ARE NOT PART OF THIS
 REVIEW; PL600, ME600, EE000, EE100, EE302, EE402.
 EE503, EE600, EE700.