Plan Review Details - Permit 14030990
Plan Review Stops For Permit 14030990
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By dhayes Date 2014-04-24 Time 16:21 Rev Time 0.00
Received By dhayes Date 2014-04-24 Time 14:46 Sent To PC
Notes
2014-04-24 16:27:46READY FOR ISSUANCE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-23 Cont ID  
Sent By wjolin Date 2014-04-23 Time 15:28 Rev Time 0.00
Received By wjolin Date 2014-04-23 Time 13:37 Sent To E
Notes
2014-04-23 15:28:49455 HIBISCUS STREET
 PERMIT #14030990
 MASTER #13070994
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER LOCAL AHJ AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION IN LIEU OF A
 SUPERVISORY SIGNAL.
  
 SHEET FA-01: PROVIDE VISUAL ALARM NOTIFICATION IN
 WOMENS' AND MENS' BATHROOMS (#122 & #123).
  
 SHEET FA-02: ADDITIONAL FIRE ALARM NOTIFICATION
 APPLIANCE(S) ARE NEEDED BETWEEN COLUMN LINES 7 - 10 IN
 CORRIDOR #1 (201). TYPICAL ALL FLOORS
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WPB FIRE RESCUE
 561.805.6730
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-24 Cont ID  
Sent By dhayes Date 2014-04-24 Time 16:36 Rev Time 0.00
Received By dhayes Date 2014-04-23 Time 13:37 Sent To  
Notes
2014-03-25 15:26:24ROUTED TO FIRE