Plan Review Details - Permit 14030980
Plan Review Stops For Permit 14030980
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 10:50 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 10:16 Sent To  
Notes
2014-05-02 10:50:32BUILDING PLAN REVIEW
 PERMIT: 14030980
 ADD: 3421 N AUSTRALIAN AVE
 CONT: TBD
 TEL: (561)502-1957 SOPHIA BARRETT
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2NDREVIEW
 DATE: FRI. MAY 02/ 2014
 ACTION: DENIED
  
 DEFINTIONS:
 313.2.1 FAMILY DAY CARE HOME.
 A FAMILY DAY CARE HOME IS A DAY CARE HOME IN WHICH MORE
 THAN THREE BUT FEWER THAN SEVEN CLIENTS RECEIVE CARE,
 MAINTENANCE AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN TWO CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 313.2.2 GROUP DAY CARE HOME.
 A GROUP DAY CARE HOME IS A DAY-CARE HOME IN WHICH AT
 LEAST SEVEN BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE,
 MAINTENANCE, AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 THIS REVIEW IS BEING COMPLETED AS A GROUP HOME DAY
 CARE.
  
 1) 2ND REQUEST. PLEASE PROVIDE THE AGE OF THE CHILDREN
 THAT WILL BE UNDER YOUR SUPERVISION AND THE AMOUNT OF
 CLIENTS THAT WOULD BE INCAPABLE OF SELF-PRESERVATION.
 FBC-B 313.2.2.
  
 2) NOTE, RESPONSE INDICATES THE CHILDREN WILL USE ONE
 OF THE TWO RESTROOMS, DOES THAT MEAN IF ONE IS OCCUPIED
 THEY WILL BE ABLE TO USE THE OTHER? IF THEY USE THE
 BATHROOM IN THE BEDROOM ARE THE DOORS LOCKABLE? 436.3
 BATHROOM DOORS.
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE IN AN
 EMERGENCY. THE OPENING DEVICE SHALL BE READILY
 ACCESSIBLE TO THE STAFF.
 THE PLANS HAVE A CIRCLED AREA, IS THIS AREA (OFFICE)
 THE AREA OF THE GROUP DAY CARE HOME, IF SO WHERE ARE
 THE BATHROOM FACILITIES?
  
 3)2ND REQUEST, PLEASE PROVIDE THE SIZE OF THE WINDOW IN
 THE GARAGE, 2010 FBC-B1037.8.3
 IN GROUP DAY CARE HOMES, EVERY ROOM USED FOR SLEEPING,
 LIVING OR DINING PURPOSES SHALL HAVE AT LEAST TWO MEANS
 OF ESCAPE, AT LEAST ONE OF WHICH SHALL BE A DOOR OR
 STAIRWAY THAT PROVIDES A MEANS OF NONOBSTRUCTED TRAVEL
 TO THE OUTSIDE OF THE BUILDING AT STREET OR GROUND
 LEVEL. THE SECOND MEANS OF ESCAPE MAY BE A WINDOW.
 PROVIDE THE OVER ALL WINDOW DIMENSIONS AND THAT OF THE
 OPEN VENT.
  
 4) 2ND REQUEST, SINCE THE CHILDREN ARE GOING INTO THE
 REMAINDER OF THE HOUSE TO USE THE BATHROOM FACILITIES
 THEY WILL BE GOING PAST CLOSET DOORS, SHOW COMPLIANCE
 WITH: 2010FBC-B
 436.2 CLOSET DOORS.
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 5) RESPONSE TO SMOKE DETECTOR COMMENT ,ELECTRIC SMOKE
 DETECTORS ARE IN THE OFFICE (SLEEPING ROOM)
 PLEASE SHOW COMPLIANCE WITH ALL OF 436.10.5.
 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1
 SINGLE-STATION SMOKE ALARMS INSTALLED IN ACCORDANCE
 WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT REQUIREMENTS
 OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED WITHIN DAY
 CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2
 WHERE THE DAY CARE HOME IS LOCATED WITHIN A BUILDING OF
 ANOTHER OCCUPANCY, ANY CORRIDORS SERVING THE DAY CARE
 HOME SHALL BE PROVIDED WITH A COMPLETE SMOKE DETECTION
 SYSTEM INSTALLED IN ACCORDANCE WITH NFPA 72.
  
 436.10.5.3
 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED BY THE
 BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4
 SINGLE-STATION SMOKE ALARMS SHALL BE PROVIDED IN ALL
 ROOMS USED FOR SLEEPING.
  
 436.10.5.5
 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED WITHIN A
 LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING UNIT,
 SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 07:43 Sent To  
Notes
2014-04-11 08:35:34BUILDING PLAN REVIEW
 PERMIT: 14030980
 ADD: 3421 N AUSTRALIAN AVE
 CONT: TBD
 TEL: (561)502-1957 SOPHIA BARRETT
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE:
 ACTION: DENIED
  
 DEFINTIONS:
 313.2.1 FAMILY DAY CARE HOME.
 A FAMILY DAY CARE HOME IS A DAY CARE HOME IN WHICH MORE
 THAN THREE BUT FEWER THAN SEVEN CLIENTS RECEIVE CARE,
 MAINTENANCE AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN TWO CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 313.2.2 GROUP DAY CARE HOME.
 A GROUP DAY CARE HOME IS A DAY-CARE HOME IN WHICH AT
 LEAST SEVEN BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE,
 MAINTENANCE, AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 THIS REVIEW IS BEING COMPLETED AS A GROUP HOME DAY
 CARE.
  
 1) PLEASE PROVIDE THE AGE OF THE CHILDREN THAT WILL BE
 UNDER YOUR SUPERVISION AND THE AMOUNT OF CLIENTS THAT
 WOULD BE INCAPABLE OF SELF-PRESERVATION. FBC-B 313.2.2.
  
 2) THE PLANS HAVE A CIRCLED AREA, IS THIS AREA (OFFICE)
 THE AREA OF THE GROUP DAY CARE HOME, IF SO WHERE ARE
 THE BATHROOM FACILITIES?
  
 1037.8.3
 IN GROUP DAY CARE HOMES, EVERY ROOM USED FOR SLEEPING,
 LIVING OR DINING PURPOSES SHALL HAVE AT LEAST TWO MEANS
 OF ESCAPE, AT LEAST ONE OF WHICH SHALL BE A DOOR OR
 STAIRWAY THAT PROVIDES A MEANS OF NONOBSTRUCTED TRAVEL
 TO THE OUTSIDE OF THE BUILDING AT STREET OR GROUND
 LEVEL. THE SECOND MEANS OF ESCAPE MAY BE A WINDOW
  
 436.2 CLOSET DOORS.
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 436.3 BATHROOM DOORS.
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE IN AN
 EMERGENCY. THE OPENING DEVICE SHALL BE READILY
 ACCESSIBLE TO THE STAFF.
 IN ACCORDANCE WITH SECTION 1037.6.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-24 Cont ID  
Sent By albarran Date 2014-04-24 Time 09:45 Rev Time 0.00
Received By albarran Date 2014-04-24 Time 08:52 Sent To I
Notes
2014-04-24 09:56:46AS PER THE FBC-B THIS IS A CHANGE OF FROM FAMILY DAY
 CARE TO GROUP DAY CARE.
 SECTION 436 DAY CARE OCCUPANCIES OF THE FBC REQUIRE A
 FIRE ALARM BE INSTALLED, BUT EXEMPTED WHEN THE DAY CARE
 FACILITY IS LIMITED TO ONLY ONE ROOM.
 AS PER THE FBC-EXISTING BLDG CHAPTER 9 NO ADDITIONAL
 ELECTRICAL REQUIREMENTS ARE MANDATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-05-05 Cont ID  
Sent By pleduc Date 2014-05-05 Time 16:16 Rev Time 0.00
Received By pleduc Date 2014-05-05 Time   Sent To PC
Notes
2014-05-05 16:15:00THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 THE SMOKE DETECTOR AND FIRE EXTINGUISHERS WILL BE
 VERIFIED BY THE FIRE INSPECTOR ON INSPECTION.
  
 PLEASE ALSO NOTE THE LIFE SAFETY COMMENTS FROM THE
 BUILDING DEPARTMENT.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-04-11 Cont ID  
Sent By wjolin Date 2014-04-11 Time 10:51 Rev Time 0.00
Received By wjolin Date 2014-04-11 Time 10:04 Sent To  
Notes
2014-04-11 10:51:253421 NORTH AUSTRALIAN AVENUE
 PERMIT #14030980
 REVIEW COMMENTS - FIRE DEPARTMENT
 CHANGE FROM 5 CLIENTS TO 12 CLIENTS
  
 INDICATE THE AGE RANGE OF CLIENTS AND THE HOURS OF
 OPERATION AT THIS ADDRESS.
  
 INDICATE ALL ROOMS AND AREAS THAT WILL OCCUPY DAY-CARE
 CLIENTS AND WHICH ROOMS WILL BE USED FOR SLEEPING.
  
 SINGLE-STATION OR MULTIPLE-STATION SMOKE ALARMS OR
 SMOKE DETECTION SHALL BE PROVIDED IN ALL ROOMS USED FOR
 SLEEPING.
  
 PROVIDE A FURNITURE LAYOUT FOR ROOMS WITH DAY-CARE
 CLIENTS (TABLES, BEDS, CRIBS, ETC.)
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY. EMERGENCY EGRESS DRILLS
 SHALL BE CONDUCTED MONTHLY.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-05 Cont ID  
Sent By pleduc Date 2014-05-05 Time 16:23 Rev Time 0.00
Received By pleduc Date 2014-04-25 Time 17:52 Sent To PC
Notes
2014-04-28 17:52:23SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-24 Cont ID  
Sent By albarran Date 2014-04-24 Time 09:58 Rev Time 0.00
Received By albarran Date 2014-03-25 Time 11:06 Sent To  
Notes
2014-04-24 09:58:44SAK
2014-03-26 11:06:46B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 10:54 Sent To  
Notes
2014-05-02 10:54:41BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By skennedy Date 2014-04-24 Time 09:25 Rev Time 0.00
Received By skennedy Date 2014-04-24 Time 09:25 Sent To  
Notes
2014-04-24 09:42:16IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 YOU MUST CHECK OUT ONE SET OF PLANS FROM THIS OFFICE,
 AFTER APPROVAL, AND TAKE TO THE PBC IMPACT FEE OFFICE
 FOR THEIR REVIEW. THE PLANS ARE TO BE STAMPED BY THAT
 OFFICE, AND RECEIPT PROVIDED. CONTACT 561 233 5100.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 08:54 Sent To  
Notes
2014-04-11 08:55:17NO MECHANICAL PLANS WERE SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 08:36 Sent To  
Notes
2014-04-11 08:54:34PLUMBING PLAN REVIEW
 PERMIT: 1403 0980
 ADD: 3421 N AUSTRALIAN
 CONT: TBD
 TEL: (561)502-1957
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE:
 ACTION: DENIED
  
 DEFINTIONS:
 313.2.1 FAMILY DAY CARE HOME.
 A FAMILY DAY CARE HOME IS A DAY CARE HOME IN WHICH MORE
 THAN THREE BUT FEWER THAN SEVEN CLIENTS RECEIVE CARE,
 MAINTENANCE AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN TWO CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 313.2.2 GROUP DAY CARE HOME.
 A GROUP DAY CARE HOME IS A DAY-CARE HOME IN WHICH AT
 LEAST SEVEN BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE,
 MAINTENANCE, AND SUPERVISION BY OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY WITH NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 THIS REVIEW IS BEING COMPLETED AS A GROUP HOME DAY
 CARE.
  
 1) THE PLANS HAVE A CIRCLED AREA, IS THIS AREA (OFFICE)
 THE AREA OF THE GROUP DAY CARE HOME, IF SO WHERE ARE
 THE BATHROOM FACILITIES NOR SERVICE SINK ?
 2010FBC-P TABLE 403.1
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-28 Cont ID  
Sent By dkittred Date 2014-03-28 Time 10:40 Rev Time 0.00
Received By dkittred Date 2014-03-28 Time 10:23 Sent To  
Notes
2014-03-28 10:40:533/28/14 SENT BACK TO B1. DK
  
2014-03-28 10:40:09PLANNING AND ZONING COMMENTS:
  
 3/28/14
  
 1. SUBMITTED REQUEST COMPLIES WITH LARGE FAMILY DAYCARE
 HOMES ZLDR SECTION 94-273(D)(19.2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  