Plan Review Details - Permit 14030860
Plan Review Stops For Permit 14030860
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-03-28 Cont ID  
Sent By scaldero Date 2014-03-28 Time 10:21 Rev Time 0.00
Received By scaldero Date 2014-03-28 Time 10:21 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-08 Cont ID  
Sent By hmoser Date 2014-04-08 Time 14:16 Rev Time 0.00
Received By hmoser Date 2014-03-20 Time 18:55 Sent To  
Notes
2014-03-20 18:55:10TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-04-08 Cont ID  
Sent By hmoser Date 2014-04-08 Time 13:39 Rev Time 0.00
Received By hmoser Date 2014-04-08 Time 13:09 Sent To  
Notes
2014-04-08 13:38:59PASS PROVISO
 1) PROVIDE A DETAIL FROM THE ENGINEER ON
 SUPPLY EXHAUST CURBS, CURB ADAPTER AND
 DUCT STANDS HOW THEY ARE TIED TO THE ROOF
 PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M) .
 2) THE SLOPE OF THE ROOF IS NOT ON THE PLAN
 REFER TO SECTION 306.5.1 SLOPED ROOFS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676